BRC2E52C7 / BRC3E52C7
Installation manual
4P368041-1
–
2014.02
34
External Input Interlock Function
16-4
Select “B2 Delay Timer”, “B2 Reset
Timer”, “Reset On/Off”, “Reset Mode”,
“Reset Cool SP” or “Reset Heat SP”
by using the
(Left/Right) buttons
and change the settings by using the
(Up/ Down) buttons.
16-5
Press the Menu/Enter button. The
confirmation screen is displayed.
16-4
16-5
Setting
Return
B2 Delay Timer
B2 Reset Timer
Reset On/Off
Reset Mode
Reset Cool SP
Reset Heat SP
:
1min
:20hrs
:OFF
:--
:22°C
:22°C
External Input Interlock
Press the Menu/Enter
button.
16-6
Select
Yes
and press the Menu/
Enter button. The settings are
entered and the Service Settings
menu returns.
16-7
Disable the Menu/Enter button when
no other settings need to be changed.
To disable, refer to
"4-2 Enable/
disable the Menu/Enter and Cancel
button" on page 12
.
16-6
16-7
Setting
Return
Save the settings?
External Input Interlock
No
Yes
<Service Settings>
Press the Menu/Enter
button.
Parameter
Explanation
Possible values
Default value
B2 Delay Timer
Timer that starts after removing the Key
Card. As long as this timer does not
expire, the unit continues to operate
normally.
0 - 10 minutes
“1 min”
B2 Reset Timer
Timer that starts when Delay Timer has
expired. When this timer expires, the
previous state changes to the "Default
Reset Setting" state.
0 – 20 hours
“20 hrs”
Reset On/Off
"Default Reset Setting" On/Off state.
“ON”, “OFF”, “--“
“OFF”
Reset Mode
"Default Reset Setting" operation mode.
“Auto”, “Cool”, “Heat”,
“Fan”, “--“
“--“
Reset Cool SP
"Default Reset Setting" cooling setpoint.
See indoor unit’s
setpoint range and
setpoint range
limitation, “--“.
“22°C”
Reset Heat SP
"Default Reset Setting" heating setpoint.
See indoor unit’s
setpoint range and
setpoint range
limitation, “--“.
“22°C”
● When a parameter is “--“, this means that nothing will be changed for this parameter and the
current active value is kept.
NOTE