Installation manual

7

BHF1357

Outdoor unit multi connection piping kit

4PW38477-1

Cutting suction gas reducer (1) and HP/LP gas reducer (2)

Connection piping

Connect the suction gas and HP/LP pipes as shown in the figure
below. Before connecting the pipes, first connect the suction gas
joint and the suction gas reducer (1), the HP/LP joint and the
HP/LP reducer (1) and (2).

See 

"Dimensions for installation" on page 6

  for the location

(height) of the joint. 

Refer to the installation manual delivered with the outdoor unit for
cautions on brazing pipes.

Keep the joint in a horizontal position (see view 

A

).

Connect the HP/LP gas reducer (1) by tilting it ±40° and connect
the HP/LP gas reducer (2), see view 

A

 in the figure below.

Refer to 

"Pipe size selection and cutting position of the joint" on

page 3

 for the cutting requirements.

4. I

NSTALLATION

 

OF

 

LIQUID

 

PIPES

 

AND

 

EQUALIZER

 

PIPES

Cutting the field supplied equalizer pipes

Use the following tables for standard installation (refer to

"Dimensions for installation" on page 6

).

If dimension differ from standard installation, adjust the L dimension
of the equalizer pipes 1 and 2 accordingly.

For L dimension of equalizer pipes 1 and 2, dimension B of the field
supplied angled joint as in table 12 on page 5 has been taken into
account. If dimension B of the angled joint you use is different from
that dimension B, adjust the L dimension of the equalizer pipes 1 and
2 accordingly.

Table 17 

Cutting liquid reducer (1)

Connection piping

Connect the liquid pipes and equalizer pipes as shown in the
figure below.
Before connecting the pipes, first connect the liquid joint and the
liquid reducer (1).

Refer to 

"Dimensions for installation" on page 6

.

Keep the joint in a horizontal position as shown in view A in the
figure below

Connect the liquid reducer (1) in an angle of ±90° and bend the
field supplied liquid pipe up to the stop valve as shown in the
figure.

Refer to the installation manual delivered with the outdoor unit
for cautions on brazing pipes.

Refer to 

"Pipe size selection and cutting position of the joint" on

page 3

 for the cutting requirements.

Suction gas 

reducer (1)

HP/LP gas 

reducer (2)

1

Connection to suction gas 
pipe 1 (field supply)

2

Connection to suction gas joint

3

Cutting position

4

Connection to HP/LP gas pipe 1 
(field supply)

5

Connection to HP/LP gas 
reducer (1)

6

No cutting for 18~24 Hp

1

HP/LP gas accessory pipe (1) supplied with the outdoor unit

2

Suction gas accessory pipe (1) supplied with the outdoor unit

3

HP/LP gas pipe (1) (field supply) refer to table 15 on page 6

4

Suction gas pipe (1) (field supply) refer to table 13 on page 6

5

Joint (1) (angle of 90°) (field supply) refer to table 14 on page 6

6

Joint (3) (angle of 90°) (field supply) refer to table 16 on page 6

7

HP/LP gas pipe (3) (field supply) refer to table 15 on page 6

8

Suction gas joint

9

Suction gas pipe (3) (field supply) refer to table 13 on page 6

10

HP/LP gas joint

11

Suction gas reducer (1)

12

HP/LP gas reducer (2)

13

HP/LP gas reducer (1)

14

Suction gas pipe (field supply) (select the pipe length on site)

15

HP/LP gas pipe (field supply) (select the pipe length on site)

16

Suction gas pipe (4) (field supply) refer to table 13 on page 6

17

Joint (2) (angle of 90°) (field supply) refer to table 14 on page 6

18

Joint (4) (angle of 90°) (field supply) refer to table 16 on page 6

19

HP/LP gas pipe (5) (field supply) refer to table 15 on page 6

20

HP/LP gas pipe (4) (field supply) refer to table 15 on page 6

21

Suction gas pipe (2) (field supply) refer to table 13 on page 6

22

HP/LP gas pipe (2) (field supply) refer to table 15 on page 6

23

Suction gas accessory pipe (2) supplied with the outdoor unit

24

HP/LP gas accessory pipe (2) supplied with the outdoor unit

18 Hp

20~32 Hp

1

4

2

3

3

6

26~32 Hp

5

40

°

24

18 20

8

10

23

22

21

19

18

17

16

18

15

14

11 12

8

17

1

2

3

4

5

13

9 10

7

6

A

A

0

°±

15

view

0

°±

15

Equalizer pipe

Pipe 1 (L mm) Pipe 2 (L mm)

95

120

1

Connection to liquid pipe (field supply)

2

Connection to liquid joint

3

Cutting position

4

No cutting for 18 Hp

L

20~32 Hp

1

2

3

4

Summary of Contents for BHFQ23P907

Page 1: ...INSTALLATION MANUAL BHFQ23P907 BHFQ23P1357 Outdoor unit multi connection piping kit...

Page 2: ...8 6 ID 31 8 ID 25 4 1 ID 31 8 ID 28 6 ID 28 6 ID 25 4 ID 19 1 ID 22 2 ID 25 4 1 ID 22 2 ID 19 1 ID 15 9 ID 19 1 ID 15 9 1 ID 19 1 ID 22 2 ID 25 4 OD 25 4 ID 28 6 1 ID 28 6 ID 31 8 OD 31 8 2 ID 19 1 ID...

Page 3: ...antities and specifications A 1 0 15 view B 1 view 120 mm 500 mm When installing the multi outdoor system connect the units as shown in the figure below If installed in a different order the outdoor u...

Page 4: ...28 6x1 0 1 2H 22 2x1 0 1 2H 15 9x1 0 O 20 22 Hp 28 6x1 0 1 2H 28 6x1 0 1 2H 15 9x1 0 O 24 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 15 9x1 0 O 26 32 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 19 1x1 0 1 2H Total capacity...

Page 5: ...it 50 and connect the HP LP gas reducer 2 see view A in the figure below Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requirements Outdoor unit Pipe 1 L mm...

Page 6: ...n the outdoor and indoor unit All piping must be executed according to instructions in the installation manual of the outdoor unit and an air tight test must be performed after complete installation o...

Page 7: ...6 has been taken into account If dimension B of the angled joint you use is different from that dimension B adjust the L dimension of HP LP gas pipes 1 5 accordingly Table 15 Table 16 1 Liquid joint 3...

Page 8: ...the figure Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requi...

Page 9: ...e type without stoppers If dimension B of the angled joint you use is different from that dimension B and or if the joints for same diameter pipes have stopppers adjust the L dimension of suction gas...

Page 10: ...igure below Bend the field supplied liquid pipe up to the stop valve as shown in the figure below Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer t...

Page 11: ...page 5 6 Liquid reducer 1 7 Liquid pipe 2 field supply select the pipe length on site 8 Equalizer pipe field supply select the pipe length on site 9 Liquid accessory pipe 2 supplied with the outdoor...

Page 12: ...ction gas pipes only For L dimension of suction gas pipes 1 3 dimension B of the field supplied angled joint as in table 25 on page 11 has been taken into account If dimension B of the angled joint yo...

Page 13: ...80 67 262 59 42 44 Hp 80 97 262 59 46 48 Hp 80 97 256 47 Outdoor unit Joint angle of 90 field supply B mm 34 44 Hp 17 46 48 Hp 23 Suction gas reducer 1 Unit A Suction gas reducer 1 Unit B 1 Connectio...

Page 14: ...joint 1 3 Cutting position 4 Connection to liquid joint 2 5 No cutting for 34 Hp 1 Liquid pipe accessory 1 supplied with the outdoor unit 2 Liquid pipe field supply select the pipe length on site 3 Li...

Page 15: ...168 168 244 44 48 212 195 160 168 168 232 Outdoor unit Joint angle of 90 field supply Joint 1 B mm Joint 2 B mm Joint 3 B mm 34 Hp 29 23 23 36 38 Hp 29 29 23 40 Hp 29 29 29 42 Hp 29 29 23 44 48 Hp 29...

Page 16: ...oint 5 angle of 90 field supply refer to table 33 on page 14 22 Suction gas pipe 2 field supply refer to table 30 on page 14 23 HP LP gas pipe 2 field supply refer to table 32 on page 14 24 Suction ga...

Page 17: ...and 3 and HP LP gas reducer 2 and 3 Be sure to foresee enough space for brazing and piping work under the unit 1 Liquid pipe 3 Suction gas pipe 2 HP LP gas pipe 4 Equalizer pipe Suction gas accessory...

Page 18: ...HP LP gas accessory pipe 1 supplied with the outdoor unit 8 HP LP gas reducer 1 9 Suction gas reducer 2 10 HP LP gas pipe field supply select the pipe length on site 11 HP LP gas reducer 3 12 HP LP ga...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium Copyright Daikin 4PW38477 1...

Reviews: