background image

BHF1357

Outdoor unit multi connection piping kit

4PW38477-1

Installation manual

16

I

N

 

CASE

 

OF

 

BOTTOM

 

PIPING

1. E

XTERIOR

2. I

NSTALLATION

 

OF

 

SUCTION

 

GAS

 

AND

 

HP/LP 

GAS

 

PIPES

Cutting the field supplied and unit suppled gas pipes

For suction gas pipes only
For L dimension of suction gas pipe 1, dimension B of the field
supplied angled joint as in table 25 on page 11 has been taken
into account. Further, connection of gas pipes and the field
supplied straight size joints are of the type without stoppers. If
dimension B of the angled joint you use is different from that
dimension B and/or if the straight size joints have stopppers,
adjust the L dimension of suction gas pipe 1 accordingly.

Table 35 (for outdoor unit C)

For HP/LP gas pipes only
For L dimension of HP/LP gas pipes 1~3, dimension B of the
field supplied angled joint as in table 27 on page 12 has been
taken into account. Further, connection of gas pipes and the
field supplied joints for same diameter are of the type without
stoppers. If dimension B of the angled joint you use is different
from that dimension B and/or if the joints for same diameter
pipes have stopppers, adjust the L dimension of HP/LP gas
pipes 1~3 accordingly.

Table 36 

Cutting suction gas reducer (1), (2) and (3) and HP/LP
gas reducer (2) and (3)

Be sure to foresee enough space for brazing and piping
work under the unit.

1

Liquid pipe

3

Suction gas pipe

2

HP/LP gas pipe

4

Equalizer pipe

Suction gas accessory 

pipe (3)

(delivered with the unit)

Suction gas pipe 1

(field supply)

Outdoor unit

B (mm)

L (mm)

34~38 Hp

0

(b)

137

40~46 Hp

0

(b)

102

48 Hp

41

98

a = cutting position
b = no cutting required

85

109

107

168

310

A

A

A

A

A

A

A

detail

A

A

A

A

A

A

A

49

4

4

4

4

4

B

a

L

Outdoor unit

Pipe 1 

L (mm)

Pipe 2 

L (mm)

Pipe 3 

L (mm)

(field supply) (field supply) (field supply)

34~44 Hp

155

86

94

46+48 Hp

119

110

82

Suction gas 

reducer (1)

Unit A

Suction gas 

reducer (1)

Unit B

1

Connection to suction gas 
accessory pipe 1 

2

Connection to suction gas 
joint

 

(1)

3

Cutting position

4

Connection to suction gas 
accessory pipe 2

5

Connection to suction gas 
joint (2)

6

Connection to suction gas pipe
(field supply)

7

Connection to suction gas 
joint (2)

8

No cutting for 34~40 Hp

Suction gas 

reducer (2)

Suction gas 

reducer (3)

HP/LP gas 

reducer (2) 

Unit A

HP/LP gas 

reducer (2) 

Unit B

HP/LP gas 

reducer (3) 

1

Connection to HP/LP gas 
pipe 1

2

Connection to HP/LP gas 
reducer (1)

3

Cutting position

4

Connection to HP/LP gas 
pipe 2

5

No cutting for 34~40 Hp

6

Connection to HP/LP gas 
pipe (field supply)

7

Connection to HP/LP gas 
joint (2)

8

No cutting for 34+36 Hp

L

34~48 Hp

1

2

3

34 Hp

36~48 Hp

4

5

3

42~48 Hp

6

7

34~38+42 Hp

40+44~48 Hp

6

3

3

8

7

4

3

5

42~48 Hp

2

5

6

3

38~42 Hp

44~48 Hp

1

3

34~48 Hp

2

7

Summary of Contents for BHFQ23P907

Page 1: ...INSTALLATION MANUAL BHFQ23P907 BHFQ23P1357 Outdoor unit multi connection piping kit...

Page 2: ...8 6 ID 31 8 ID 25 4 1 ID 31 8 ID 28 6 ID 28 6 ID 25 4 ID 19 1 ID 22 2 ID 25 4 1 ID 22 2 ID 19 1 ID 15 9 ID 19 1 ID 15 9 1 ID 19 1 ID 22 2 ID 25 4 OD 25 4 ID 28 6 1 ID 28 6 ID 31 8 OD 31 8 2 ID 19 1 ID...

Page 3: ...antities and specifications A 1 0 15 view B 1 view 120 mm 500 mm When installing the multi outdoor system connect the units as shown in the figure below If installed in a different order the outdoor u...

Page 4: ...28 6x1 0 1 2H 22 2x1 0 1 2H 15 9x1 0 O 20 22 Hp 28 6x1 0 1 2H 28 6x1 0 1 2H 15 9x1 0 O 24 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 15 9x1 0 O 26 32 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 19 1x1 0 1 2H Total capacity...

Page 5: ...it 50 and connect the HP LP gas reducer 2 see view A in the figure below Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requirements Outdoor unit Pipe 1 L mm...

Page 6: ...n the outdoor and indoor unit All piping must be executed according to instructions in the installation manual of the outdoor unit and an air tight test must be performed after complete installation o...

Page 7: ...6 has been taken into account If dimension B of the angled joint you use is different from that dimension B adjust the L dimension of HP LP gas pipes 1 5 accordingly Table 15 Table 16 1 Liquid joint 3...

Page 8: ...the figure Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requi...

Page 9: ...e type without stoppers If dimension B of the angled joint you use is different from that dimension B and or if the joints for same diameter pipes have stopppers adjust the L dimension of suction gas...

Page 10: ...igure below Bend the field supplied liquid pipe up to the stop valve as shown in the figure below Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer t...

Page 11: ...page 5 6 Liquid reducer 1 7 Liquid pipe 2 field supply select the pipe length on site 8 Equalizer pipe field supply select the pipe length on site 9 Liquid accessory pipe 2 supplied with the outdoor...

Page 12: ...ction gas pipes only For L dimension of suction gas pipes 1 3 dimension B of the field supplied angled joint as in table 25 on page 11 has been taken into account If dimension B of the angled joint yo...

Page 13: ...80 67 262 59 42 44 Hp 80 97 262 59 46 48 Hp 80 97 256 47 Outdoor unit Joint angle of 90 field supply B mm 34 44 Hp 17 46 48 Hp 23 Suction gas reducer 1 Unit A Suction gas reducer 1 Unit B 1 Connectio...

Page 14: ...joint 1 3 Cutting position 4 Connection to liquid joint 2 5 No cutting for 34 Hp 1 Liquid pipe accessory 1 supplied with the outdoor unit 2 Liquid pipe field supply select the pipe length on site 3 Li...

Page 15: ...168 168 244 44 48 212 195 160 168 168 232 Outdoor unit Joint angle of 90 field supply Joint 1 B mm Joint 2 B mm Joint 3 B mm 34 Hp 29 23 23 36 38 Hp 29 29 23 40 Hp 29 29 29 42 Hp 29 29 23 44 48 Hp 29...

Page 16: ...oint 5 angle of 90 field supply refer to table 33 on page 14 22 Suction gas pipe 2 field supply refer to table 30 on page 14 23 HP LP gas pipe 2 field supply refer to table 32 on page 14 24 Suction ga...

Page 17: ...and 3 and HP LP gas reducer 2 and 3 Be sure to foresee enough space for brazing and piping work under the unit 1 Liquid pipe 3 Suction gas pipe 2 HP LP gas pipe 4 Equalizer pipe Suction gas accessory...

Page 18: ...HP LP gas accessory pipe 1 supplied with the outdoor unit 8 HP LP gas reducer 1 9 Suction gas reducer 2 10 HP LP gas pipe field supply select the pipe length on site 11 HP LP gas reducer 3 12 HP LP ga...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium Copyright Daikin 4PW38477 1...

Reviews: