Installation manual

13

BHF1357

Outdoor unit multi connection piping kit

4PW38477-1

Cutting liquid reducer (1)

Connection piping

Connect the liquid pipes and equalizer pipes as shown in the
figure below.
Before connecting the pipes, first connect the liquid joint and the
liquid reducer (1).

Refer to 

"Dimensions for installation" on page 11

.

Keep the joint in a horizontal position, see view 

A

 in the figure

below.

Connect the liquid reducer (1) in an angle of 40° and bend the
field supplied liquid pipe up to the stop valve as shown in the
figure.

Refer to the installation manual delivered with the outdoor unit
for cautions on brazing pipes.

Refer to 

"Pipe size selection and cutting position of joints." on

page 10

 for the cutting requirements.

5. A

FTER

 

CONNECTION

 

OF

 

THE

 

PIPING

Follow the instructions in the paragraph 

"After connection of the

piping" on page 5

.

I

N

 

CASE

 

OF

 

LOWER

 

FRONT

 

PIPING

 

1. E

XTERIOR

2. D

IMENSIONS

 

FOR

 

INSTALLATION

Dimensions for standard installation

Liquid reducer (1)

Unit A

Liquid reducer (1)

Unit B

1

Connection to liquid pipe 
(field supply)

2

Connection to liquid joint (1)

3

Cutting position

4

Connection to liquid joint (2)

5

No cutting for 34 Hp

1

Liquid pipe accessory (1) supplied with the outdoor unit

2

Liquid pipe (field supply) (select the pipe length on site)

3

Liquid joint (1)

4

Equalizer pipe (1) (field supply) refer to table 28 on page 12

5

Liquid reducer (1)

6

Joint (angle of 90°) (field supply) refer to table 29 on page 12

7

Equalizer pipe (2) (field supply) refer to table 28 on page 12

8

Equalizer pipe (field supply) (select the pipe length on site)

9

Equalizer accessory pipe (1) supplied with the outdoor unit

10

Liquid joint (2)

11

Equalizer joint

12

Liquid pipe accessory (2) supplied with the outdoor unit

13

Liquid pipe accessory (3) supplied with the outdoor unit

1

2

1

4

5

34~48 Hp

3

36~48 Hp

3

4

9

6 7

40

°

7

3

8 2

13

A

2

1

A

view

4

9

7

6

11

5

10

12

2

7 8 9

6

4

2

5

3

0

°±

15

1

Liquid joint (1)

5

Equalizer pipe

2

HP/LP gas joint (1)

6

Liquid joint (2)

3

To indoor unit

7

HP/LP gas joint (2)

4

Suction gas joint (1)

8

Suction gas joint (2)

1

Liquid pipe

2

Suction gas pipe

3

HP/LP gas pipe

4

Equalizer pipe

5

Bottom frame

NOTE

When the dimensions exceed these of the standard
installation, extend the pipes between the outdoor unit
and the joint accordingly (field supply).

A

A

3

2

1

7
8

6

4

5

A

A

A

A

5

5

121
167
186
260

2

69

109

A

detail

1 2

3

4 5

181

148

152

198

Summary of Contents for BHFQ23P907

Page 1: ...INSTALLATION MANUAL BHFQ23P907 BHFQ23P1357 Outdoor unit multi connection piping kit...

Page 2: ...8 6 ID 31 8 ID 25 4 1 ID 31 8 ID 28 6 ID 28 6 ID 25 4 ID 19 1 ID 22 2 ID 25 4 1 ID 22 2 ID 19 1 ID 15 9 ID 19 1 ID 15 9 1 ID 19 1 ID 22 2 ID 25 4 OD 25 4 ID 28 6 1 ID 28 6 ID 31 8 OD 31 8 2 ID 19 1 ID...

Page 3: ...antities and specifications A 1 0 15 view B 1 view 120 mm 500 mm When installing the multi outdoor system connect the units as shown in the figure below If installed in a different order the outdoor u...

Page 4: ...28 6x1 0 1 2H 22 2x1 0 1 2H 15 9x1 0 O 20 22 Hp 28 6x1 0 1 2H 28 6x1 0 1 2H 15 9x1 0 O 24 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 15 9x1 0 O 26 32 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 19 1x1 0 1 2H Total capacity...

Page 5: ...it 50 and connect the HP LP gas reducer 2 see view A in the figure below Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requirements Outdoor unit Pipe 1 L mm...

Page 6: ...n the outdoor and indoor unit All piping must be executed according to instructions in the installation manual of the outdoor unit and an air tight test must be performed after complete installation o...

Page 7: ...6 has been taken into account If dimension B of the angled joint you use is different from that dimension B adjust the L dimension of HP LP gas pipes 1 5 accordingly Table 15 Table 16 1 Liquid joint 3...

Page 8: ...the figure Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requi...

Page 9: ...e type without stoppers If dimension B of the angled joint you use is different from that dimension B and or if the joints for same diameter pipes have stopppers adjust the L dimension of suction gas...

Page 10: ...igure below Bend the field supplied liquid pipe up to the stop valve as shown in the figure below Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer t...

Page 11: ...page 5 6 Liquid reducer 1 7 Liquid pipe 2 field supply select the pipe length on site 8 Equalizer pipe field supply select the pipe length on site 9 Liquid accessory pipe 2 supplied with the outdoor...

Page 12: ...ction gas pipes only For L dimension of suction gas pipes 1 3 dimension B of the field supplied angled joint as in table 25 on page 11 has been taken into account If dimension B of the angled joint yo...

Page 13: ...80 67 262 59 42 44 Hp 80 97 262 59 46 48 Hp 80 97 256 47 Outdoor unit Joint angle of 90 field supply B mm 34 44 Hp 17 46 48 Hp 23 Suction gas reducer 1 Unit A Suction gas reducer 1 Unit B 1 Connectio...

Page 14: ...joint 1 3 Cutting position 4 Connection to liquid joint 2 5 No cutting for 34 Hp 1 Liquid pipe accessory 1 supplied with the outdoor unit 2 Liquid pipe field supply select the pipe length on site 3 Li...

Page 15: ...168 168 244 44 48 212 195 160 168 168 232 Outdoor unit Joint angle of 90 field supply Joint 1 B mm Joint 2 B mm Joint 3 B mm 34 Hp 29 23 23 36 38 Hp 29 29 23 40 Hp 29 29 29 42 Hp 29 29 23 44 48 Hp 29...

Page 16: ...oint 5 angle of 90 field supply refer to table 33 on page 14 22 Suction gas pipe 2 field supply refer to table 30 on page 14 23 HP LP gas pipe 2 field supply refer to table 32 on page 14 24 Suction ga...

Page 17: ...and 3 and HP LP gas reducer 2 and 3 Be sure to foresee enough space for brazing and piping work under the unit 1 Liquid pipe 3 Suction gas pipe 2 HP LP gas pipe 4 Equalizer pipe Suction gas accessory...

Page 18: ...HP LP gas accessory pipe 1 supplied with the outdoor unit 8 HP LP gas reducer 1 9 Suction gas reducer 2 10 HP LP gas pipe field supply select the pipe length on site 11 HP LP gas reducer 3 12 HP LP ga...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium Copyright Daikin 4PW38477 1...

Reviews: