Installation manual

5

AZQS100~1Y1B

Split system air conditioners

4P332194-1B – 2015.01

Install a baffle plate on the air suction side of the outdoor unit 
and set the outlet side at a right angle to the direction of the 
wind:

Prepare a water drainage channel around the foundation, to 
drain waste water from around the unit.

If the water drainage of the unit is not easy, please build up the 
unit on a foundation of concrete blocks, etc. (the height of the 
foundation should be maximum 150 mm).

If you install the unit on a frame, please install a waterproof plate 
(field supply) within 150 mm of the underside of the unit in order 
to prevent the invasion of water from the lower direction.

When installing the unit in a place frequently exposed to snow, 
pay special attention to elevate the foundation as high as 
possible.

If you install the unit on a building frame, 
please install a waterproof plate (field 
supply)(within 150 mm of the underside of 
the unit) or use a drain kit in order to avoid 
the drainwater dripping (field supply). (See 
figure).

Make sure that the unit is installed level.

5.2.

Selecting a location in cold climates

To prevent exposure to wind, install the outdoor unit with its 
suction side facing the wall.

Never install the outdoor unit at a site where the suction side 
may be exposed directly to wind.

To prevent exposure to wind, install a baffle plate on the air 
discharge side of the outdoor unit.

In heavy snowfall areas it is very important to select an 
installation site where the snow will not affect the unit and set the 
outlet side at a right angle to the direction of the wind:

6.

Precautions on installation

6.1.

Foundation work

Check the strength and level of the installation ground so that 
the unit will not cause any operating vibration or noise after 
installation.

In accordance with the foundation drawing in the figure, fix the 
unit securely by means of the foundation bolts. (Prepare four 
sets of M12 foundation bolts, nuts and washers each which are 
available on the market.)

It is best to screw in the foundation bolts 
until their length are 20 mm from the 
foundation surface.

Fix the outdoor unit to the foundation bolts using nuts 
with resin washers (1) as shown in the figure. 
If the coating on the fastening area is stripped off, the nuts rust 
easily.
Dimensions (bottom view) (unit of measurement: mm)

A

Front (air outlet side)

B

Leg pitch

C

Bottom frame

D

Drain hole

E

Knock-out hole

NOTICE

When operating the outdoor unit in a low outdoor ambient 
temperature, be sure to follow the instructions described 
below.

1

2

2

3

1

Baffle plate

2

Strong wind

3

Discharge air

NOTICE

If drain holes of the outdoor unit are 
covered by a mounting base or by 
floor surface, raise the unit in order 
to provide a free space of more than 
150 mm under the outdoor unit.

3

3

2

1

4

1

Construct a large 
canopy.

2

Construct a pedestal.

 

Install the unit high 
enough off the ground 
to prevent burying in 
snow.

3

Strong wind

4

Discharge air

•PP

20

1

A

B

B

C

D

E

160

160

620

36
61

262

416

595

285

279

260

161

(345~355)

Summary of Contents for AZQS100B7V1B

Page 1: ...INSTALLATION MANUAL AZQS100B7V1B AZQS125B7V1B AZQS140B7V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B Split system air conditioners ...

Page 2: ...B 2 4 5 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 9 R410A L1 L2 L3 L1 L2 L3 N 1 2 3 3 3 3 4 4 5 5 6 6 V1 Y1 1 5 4 3 2 6 6 1 3 4 A 2 1 2 1 2 1 2 1 2 3 6 4 5 7 8 9 ...

Page 3: ...o estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertif...

Page 4: ...ns regarding test runs 15 15 4 Failure diagnosis at the moment of first installation 15 16 Wiring diagram 16 Thank you for purchasing this product The original instructions are written in English All other languages are translations of the original instructions 1 Definitions 1 1 Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of oc...

Page 5: ...y out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation work may result in accidents due to fall of equipment Make sure that all electrical work is carried out by qualified personnel according to the applicable legislation and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper ...

Page 6: ... advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit or when in thermostat stop operation This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound pressure level is le...

Page 7: ... the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created th...

Page 8: ...oor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind 6 Precautions on installation 6 1 Foundation work Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation In accordance w...

Page 9: ...et space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7 1 Precaution on installation A In case of non stacked installation See figure 1 Unit mm A 1 Single unit installation A 2 Multiple units installation 2 units or more Secure appropriate space when using a s...

Page 10: ...n shall be done by an installer the choice of materials and installation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuuming is complete Running the system with the valve closed may break the compressor INFORMATION It is forbidden t...

Page 11: ... Torque wrench 2 Spanner 3 Piping union 4 Flare nut Not recommended but in case of emergency Should you be forced to connect the piping without a torque wrench follow the following installation method Tighten the flare nut using a spanner until the tightening torque suddenly increases From that position further tighten the flare nut to the angle listed below 9 2 Brazing guidelines Make sure to blo...

Page 12: ...or refrigerant leaks after tightening the stem cap Cautions on handling the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service port cap securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cap 9 ...

Page 13: ...eight of 10 m A trap is not necessary when the outdoor unit is installed at higher position than the indoor unit 11 Leak test and vacuum drying When all piping work is complete and the outdoor unit is connected to the indoor unit it is necessary to check for any leakages in the refrigerant piping to perform vacuum drying to remove all moisture in the refrigerant piping If there is a possibility of...

Page 14: ...mpleted Refrigerant may only be charged after performing the leak test and vacuum drying see 11 Leak test and vacuum drying on page 10 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site Make sure to charge the refrigerant in liquid state to the liquid pipe Since R410A is a mixed refrigerant its composition changes if charged in...

Page 15: ... the stop valve see 9 3 Stop valve operation on page 8 since vacuum drying can not be performed properly from these ports Outdoor units have 1 port on the piping It is between the heat exchanger and the 4 way valve WARNING Some sections of the refrigerant circuit may be isolated from other sections caused by components with specific functions e g valves The refrigerant circuit therefore features a...

Page 16: ...tween units 6 Power supply and ground wiring See figure 5 1 Power supply wiring and earth wire 2 Wiring between units When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knock out hole See figure 9 1 Wire 2 Bush 3 Nut 4 Frame 5 Hose A Inside B Outside When you do not use a wire conduit be sure to protect the wires with vinyl tubes to preve...

Page 17: ...2 14 8 17 8 Recommended field fuse A 32 40 20 25 Wire type b b Only in protected pipes use H07RN F when protected pipes are not used H05VV U3G H05VV U5G Size Wiring size must comply with the applicable local and national code Wire type of wiring between the units H05VV U4G2 5 CAUTION Select all cables and wire sizes in accordance with applicable legislation After finishing the electrical work conf...

Page 18: ...he following abnormalities before you can diagnose possible malfunction codes Disconnection or wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and remote controller The fuse on the outdoor unit PCB may have run out If the malfunction code E3 E4 L8 or U0 is displayed on the remote controller there is a possibility that the stop valves are...

Page 19: ...t exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated gate bipolar transistor IGBT V2R V1B Diode module V2R IGBT power module X1M Terminal power supply strip X1Y V1B Optional connector X6A Y1B Optional connector Y1E Electronic expansion valve Y1S Solenoid 4 way...