AZQS100~1Y1B

Split system air conditioners

4P332194-1B – 2015.01

Installation manual

2

Service company:

Qualified company which can perform or coordinate the required 
service to the unit.

Applicable legislation:

All international, European, national and local directives, laws, 
regulations and/or codes which are relevant and applicable for a 
certain product or domain.

Accessories:

Equipment which is delivered with the unit and which needs to be 
installed according to instructions in the documentation.

Optional equipment: 

Equipment which can optionally be combined to the products as per 
the subject of this manual.

Field supply:

Equipment which needs to be installed according to instructions in 
this manual, but which are not supplied by Daikin.

2.

Safety considerations

The precautions here, all cover very important topics, so be sure to 
follow them carefully.

All activities described in this manual shall be carried out by an 
installer.

Be sure to wear adequate personal protection equipment (protection 
gloves, safety glasses, …) when performing installation, 
maintenance or service to the unit.

If not sure of installation procedures or operation of the unit, always 
contact your local dealer for advice and information.

Improper installation or attachment of equipment or accessories 
could result in electric shock, short-circuit, leaks, fire or other damage 
to the equipment. Be sure only to use accessories, optional 
equipment and spare parts made by Daikin which are specially 
designed for use with the products as of subject in this manual and 
have them installed by an installer.

Warning

Ask your dealer or qualified personnel to carry out installation 
work. Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks 
or fire.

Perform installation work in accordance with this installation 
manual.
Improper installation may lead to water leakage, electric shocks 
or fire.

The equipment is not intended for use in a potentially explosive 
atmosphere.

Consult your local dealer regarding what to do in case of 
refrigerant leakage. When the unit is to be installed in a small 
room, it is necessary to take proper measures so that the 
amount of any leaked refrigerant does not exceed the 
concentration limit in the event of a leakage. Otherwise, this may 
lead to an accident due to oxygen depletion.

Be sure to use only the specified accessories and parts for 
installation work.
Failure to use the specified parts may result in water leakage, 
electric shocks, fire, or the unit falling.

Install the unit on a foundation that can withstand its weight.
Insufficient strength may result in the fall of equipment and 
causing injury.

Carry out the specified installation work in consideration of 
strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to fall of 
equipment.

Make sure that all electrical work is carried out by qualified 
personnel according to the applicable legislation and this 
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper 
electrical construction may lead to electric shocks or fire.

Make sure that all wiring is secure, using the specified wires and 
ensuring that external forces do not act on the terminal 
connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units, and wiring 
the power supply, form the wires so that the frontside panel can 
be securely fastened.
If the frontside panel is not in place, overheating of the terminals, 
electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work, ventilate the area 
immediately.
Toxic gas may be produced if refrigerant gas comes into contact 
with fire.

After completing the installation work, check to make sure that 
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room 
and comes into contact with a source of fire, such as a fan 
heater, stove or cooker.

When planning to relocate former installed units, you must first 
recover the refrigerant after the pump down operation. Refer to 
chapter 

"13. Pump down operation" on page 12

.

Never directly touch any accidental leaking refrigerant. This 
could result in severe wounds caused by frostbite.

Be sure to install an earth leakage circuit breaker in accordance 
with applicable legislation. Failure to do so may cause electrical 
shock and fire.

DANGER: ELECTRICAL SHOCK

Switch off all power supply before removing the switchbox 
service panel or before making any connections or 
touching electrical parts.

To avoid electric shock, be sure to disconnect the power 
supply 1 minute or more before servicing the electrical 
parts. Even after 1 minute, always measure the voltage at 
the terminals of main circuit capacitors or electrical parts 
and, before touching, be sure that those voltages are 
50 V DC or less.

When service panels are removed, live parts can easily be 
touched by accident. Never leave the unit unattended 
during installation or servicing when the service panel is 
removed.

DANGER: DO NOT TOUCH PIPING AND INTERNAL 
PARTS

Do not touch the refrigerant piping, water piping or internal 
parts during and immediately after operation. The piping 
and internal parts may be hot or cold depending on the 
working condition of the unit.

Your hand may suffer burns or frostbite if you touch the 
piping or internal parts. To avoid injury, give the piping and 
internal parts time to return to normal temperature or, if you 
must touch them, be sure to wear protective gloves.

Summary of Contents for AZQS100B7V1B

Page 1: ...INSTALLATION MANUAL AZQS100B7V1B AZQS125B7V1B AZQS140B7V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B Split system air conditioners ...

Page 2: ...B 2 4 5 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 9 R410A L1 L2 L3 L1 L2 L3 N 1 2 3 3 3 3 4 4 5 5 6 6 V1 Y1 1 5 4 3 2 6 6 1 3 4 A 2 1 2 1 2 1 2 1 2 3 6 4 5 7 8 9 ...

Page 3: ...o estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertif...

Page 4: ...ns regarding test runs 15 15 4 Failure diagnosis at the moment of first installation 15 16 Wiring diagram 16 Thank you for purchasing this product The original instructions are written in English All other languages are translations of the original instructions 1 Definitions 1 1 Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of oc...

Page 5: ...y out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation work may result in accidents due to fall of equipment Make sure that all electrical work is carried out by qualified personnel according to the applicable legislation and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper ...

Page 6: ... advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit or when in thermostat stop operation This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound pressure level is le...

Page 7: ... the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created th...

Page 8: ...oor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind 6 Precautions on installation 6 1 Foundation work Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation In accordance w...

Page 9: ...et space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7 1 Precaution on installation A In case of non stacked installation See figure 1 Unit mm A 1 Single unit installation A 2 Multiple units installation 2 units or more Secure appropriate space when using a s...

Page 10: ...n shall be done by an installer the choice of materials and installation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuuming is complete Running the system with the valve closed may break the compressor INFORMATION It is forbidden t...

Page 11: ... Torque wrench 2 Spanner 3 Piping union 4 Flare nut Not recommended but in case of emergency Should you be forced to connect the piping without a torque wrench follow the following installation method Tighten the flare nut using a spanner until the tightening torque suddenly increases From that position further tighten the flare nut to the angle listed below 9 2 Brazing guidelines Make sure to blo...

Page 12: ...or refrigerant leaks after tightening the stem cap Cautions on handling the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service port cap securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cap 9 ...

Page 13: ...eight of 10 m A trap is not necessary when the outdoor unit is installed at higher position than the indoor unit 11 Leak test and vacuum drying When all piping work is complete and the outdoor unit is connected to the indoor unit it is necessary to check for any leakages in the refrigerant piping to perform vacuum drying to remove all moisture in the refrigerant piping If there is a possibility of...

Page 14: ...mpleted Refrigerant may only be charged after performing the leak test and vacuum drying see 11 Leak test and vacuum drying on page 10 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site Make sure to charge the refrigerant in liquid state to the liquid pipe Since R410A is a mixed refrigerant its composition changes if charged in...

Page 15: ... the stop valve see 9 3 Stop valve operation on page 8 since vacuum drying can not be performed properly from these ports Outdoor units have 1 port on the piping It is between the heat exchanger and the 4 way valve WARNING Some sections of the refrigerant circuit may be isolated from other sections caused by components with specific functions e g valves The refrigerant circuit therefore features a...

Page 16: ...tween units 6 Power supply and ground wiring See figure 5 1 Power supply wiring and earth wire 2 Wiring between units When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knock out hole See figure 9 1 Wire 2 Bush 3 Nut 4 Frame 5 Hose A Inside B Outside When you do not use a wire conduit be sure to protect the wires with vinyl tubes to preve...

Page 17: ...2 14 8 17 8 Recommended field fuse A 32 40 20 25 Wire type b b Only in protected pipes use H07RN F when protected pipes are not used H05VV U3G H05VV U5G Size Wiring size must comply with the applicable local and national code Wire type of wiring between the units H05VV U4G2 5 CAUTION Select all cables and wire sizes in accordance with applicable legislation After finishing the electrical work conf...

Page 18: ...he following abnormalities before you can diagnose possible malfunction codes Disconnection or wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and remote controller The fuse on the outdoor unit PCB may have run out If the malfunction code E3 E4 L8 or U0 is displayed on the remote controller there is a possibility that the stop valves are...

Page 19: ...t exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated gate bipolar transistor IGBT V2R V1B Diode module V2R IGBT power module X1M Terminal power supply strip X1Y V1B Optional connector X6A Y1B Optional connector Y1E Electronic expansion valve Y1S Solenoid 4 way...

Page 20: ...4P332194 1B 2015 01 Copyright 2012 Daikin 4P332194 1 B 0000000 ...

Reviews: