Installation manual

13

AZQS100~1Y1B

Split system air conditioners

4P332194-1B – 2015.01

14. Electrical wiring work

14.1. Precautions on electrical wiring work

Use only copper wires.

A main switch or other means for disconnection, having a 
contact separation in all poles, must be incorporated in the fixed 
wiring in accordance with applicable legislation.
Do not turn on the main switch until all the wiring is completed. 

For Y1
Make sure to connect power supply cables in normal phase. If 
connected in reverse phase, the remote controller of the indoor 
unit indicates "

U1

" and the equipment cannot operate. Change 

any two of the three power supply cables (L1, L2, L3) to correct 
phase.
If the contact in the magnetic switch should be forcibly turned on 
while the equipment is inoperative, the compressor will burn out. 
Never try to forcibly turn on the contact.

Never squeeze bundled cables into a unit.

Fix cables so that cables do not make contact with the pipes 
(especially on high pressure side).

Secure the electrical wiring with cable ties as shown in the figure 
in chapter 

"14.2. Connecting power supply and inter-unit wiring" 

on page 13

 so that it does not come in contact with the piping, 

particularly on the high-pressure side.
Make sure no external pressure is applied to the terminal 
connectors.

When installing the earth leakage circuit breaker make sure that 
it is compatible with the inverter (resistant to high frequency 
electrical noise) to avoid unnecessary opening of the earth 
leakage circuit breaker.

As this unit is equipped with an inverter, installing a phase 
advancing capacitor not only will deteriorate power factor 
improvement effect, but also may cause capacitor abnormal 
heating accident due to high-frequency waves. Therefore, never 
install a phase advancing capacitor.

14.2. Connecting power supply and inter-unit wiring

Secure the earth wire to the stop valve attachment plate so that 
it does not slide.

Secure the earth wire to the stop valve attachment plate one 
more time along with the electric wiring and the inter-unit wiring.

Lay the electrical wiring so that the front cover does not rise up 
when doing wiring work and attach the front cover securely.

(See figure 6)

1

Switch box

2

Stop valve mounting plate

3

Ground

4

Tie-wrap

5

Wiring between units

6

Power supply and ground wiring

(See figure 5)

1

Power supply wiring and earth wire

2

Wiring between units

When cables are routed from the unit, a protection sleeve for the 
conduits (PG-insertions) can be inserted at the knock-out hole. 

(See figure 9)

1

Wire

2

Bush

3

Nut

4

Frame

5

Hose

A

Inside

B

Outside

When you do not use a wire conduit, be sure to protect the wires 
with vinyl tubes to prevent the edge of the knock-out hole from 
cutting the wires.

Follow the electric wiring diagram for electrical wiring works.

Form the wires and fix the cover firmly so that the cover may be 
fit in properly.

14.3. Precautions on wiring of power supply and inter-

unit wiring

Use a round crimp-style terminal for connection to the power 
supply terminal board. In case it cannot be used due to 
unavoidable reasons, be sure to observe the following 
instruction.

- Do not connect wires of different gauge to the same power 

supply terminal. (Looseness in the connection may cause 
overheating.)

- When connecting wires of the same gauge, connect them 

according to the below figure.

Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent 
appropriate tightening.

Over-tightening the terminal screws can damage the screws.

See the table below for tightening torques for the terminal 
screws.

WARNING

All wiring must be performed by an authorized 
electrician.

All components procured on the site and all electric 
construction shall comply with the applicable 
legislation.

DANGER: HIGH VOLTAGE

To avoid electrical shock, make sure to disconnect the 
power supply 1 minute or more before servicing the 
electrical parts. Even after 1 minute, always measure the 
voltage at the terminals of main circuit capacitors or 
electrical parts and, before touching, make sure that those 
voltages are 50 V DC or less.

NOTICE

To persons in charge of electrical wiring work:

Do not operate the unit until the refrigerant piping is 
complete. (Running it before the piping is ready will break 
the compressor.)

DANGER

Before obtaining access to terminal devices, all supply 
circuits must be interrupted.

Be sure to install an earth leakage circuit breaker in 
accordance with applicable legislation. Failure to do 
so may cause electrical shock.

CAUTION

Be sure to install the required fuses or circuit breakers.

Tightening torque (N•m)

M4 (X1M)

1.2~1.8

M4 (EARTH)

1.2~1.4

M5 (X1M)

2.0~3.0

M5 (EARTH)

2.4~2.9

1 2 3

1

Round pressure terminal

2

Cut out section

3

Cup washer

Summary of Contents for AZQS100B7V1B

Page 1: ...INSTALLATION MANUAL AZQS100B7V1B AZQS125B7V1B AZQS140B7V1B AZQS100B7Y1B AZQS125B7Y1B AZQS140B7Y1B Split system air conditioners ...

Page 2: ...B 2 4 5 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 9 R410A L1 L2 L3 L1 L2 L3 N 1 2 3 3 3 3 4 4 5 5 6 6 V1 Y1 1 5 4 3 2 6 6 1 3 4 A 2 1 2 1 2 1 2 1 2 3 6 4 5 7 8 9 ...

Page 3: ...o estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertif...

Page 4: ...ns regarding test runs 15 15 4 Failure diagnosis at the moment of first installation 15 16 Wiring diagram 16 Thank you for purchasing this product The original instructions are written in English All other languages are translations of the original instructions 1 Definitions 1 1 Meaning of warnings and symbols Warnings in this manual are classified according to their severity and probability of oc...

Page 5: ...y out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation work may result in accidents due to fall of equipment Make sure that all electrical work is carried out by qualified personnel according to the applicable legislation and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper ...

Page 6: ... advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit or when in thermostat stop operation This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound pressure level is le...

Page 7: ... the indoor and outdoor units piping and wiring lengths come within the allowable ranges Places where water leaking from the unit cannot cause damage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created th...

Page 8: ...oor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind 6 Precautions on installation 6 1 Foundation work Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation In accordance w...

Page 9: ...et space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7 1 Precaution on installation A In case of non stacked installation See figure 1 Unit mm A 1 Single unit installation A 2 Multiple units installation 2 units or more Secure appropriate space when using a s...

Page 10: ...n shall be done by an installer the choice of materials and installation shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuuming is complete Running the system with the valve closed may break the compressor INFORMATION It is forbidden t...

Page 11: ... Torque wrench 2 Spanner 3 Piping union 4 Flare nut Not recommended but in case of emergency Should you be forced to connect the piping without a torque wrench follow the following installation method Tighten the flare nut using a spanner until the tightening torque suddenly increases From that position further tighten the flare nut to the angle listed below 9 2 Brazing guidelines Make sure to blo...

Page 12: ...or refrigerant leaks after tightening the stem cap Cautions on handling the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service port cap securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cap 9 ...

Page 13: ...eight of 10 m A trap is not necessary when the outdoor unit is installed at higher position than the indoor unit 11 Leak test and vacuum drying When all piping work is complete and the outdoor unit is connected to the indoor unit it is necessary to check for any leakages in the refrigerant piping to perform vacuum drying to remove all moisture in the refrigerant piping If there is a possibility of...

Page 14: ...mpleted Refrigerant may only be charged after performing the leak test and vacuum drying see 11 Leak test and vacuum drying on page 10 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site Make sure to charge the refrigerant in liquid state to the liquid pipe Since R410A is a mixed refrigerant its composition changes if charged in...

Page 15: ... the stop valve see 9 3 Stop valve operation on page 8 since vacuum drying can not be performed properly from these ports Outdoor units have 1 port on the piping It is between the heat exchanger and the 4 way valve WARNING Some sections of the refrigerant circuit may be isolated from other sections caused by components with specific functions e g valves The refrigerant circuit therefore features a...

Page 16: ...tween units 6 Power supply and ground wiring See figure 5 1 Power supply wiring and earth wire 2 Wiring between units When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knock out hole See figure 9 1 Wire 2 Bush 3 Nut 4 Frame 5 Hose A Inside B Outside When you do not use a wire conduit be sure to protect the wires with vinyl tubes to preve...

Page 17: ...2 14 8 17 8 Recommended field fuse A 32 40 20 25 Wire type b b Only in protected pipes use H07RN F when protected pipes are not used H05VV U3G H05VV U5G Size Wiring size must comply with the applicable local and national code Wire type of wiring between the units H05VV U4G2 5 CAUTION Select all cables and wire sizes in accordance with applicable legislation After finishing the electrical work conf...

Page 18: ...he following abnormalities before you can diagnose possible malfunction codes Disconnection or wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and remote controller The fuse on the outdoor unit PCB may have run out If the malfunction code E3 E4 L8 or U0 is displayed on the remote controller there is a possibility that the stop valves are...

Page 19: ...t exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated gate bipolar transistor IGBT V2R V1B Diode module V2R IGBT power module X1M Terminal power supply strip X1Y V1B Optional connector X6A Y1B Optional connector Y1E Electronic expansion valve Y1S Solenoid 4 way...