Troubleshooting
SiEN04-306D
122
Service Diagnosis
4.12 Discharge Pipe Temperature Control
remote control
Display
F3
Method of
Malfunction
Detection
The discharge pipe temperature control (stop, frequency drooping, etc.) is checked with the
temperature being detected by the discharge pipe thermistor.
Malfunction
Decision
Conditions
If a stop takes place 6 times successively due to abnormal discharge pipe temperature, the
system will be shut down.
If the temperature being detected by the discharge pipe thermistor rises above 120°C, the
compressor will stop. (The error is cleared when the temperature has dropped below
107°C.)
Stop temperatures (in case of 5.0kW class)
(1) 110°C : above 45Hz (rising), above 40Hz (dropping)
(2) 102°C : 30~45Hz (rising), 25~40Hz (dropping)
(3) 98°C : below 30Hz (rising), below 25Hz (dropping)
The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed
Causes
Refrigerant shortage
Four way valve malfunctioning
Discharge pipe thermistor defective
(heat exchanger or outdoor temperature thermistor defective)
Outdoor unit PCB defective
Water mixed in the local piping
Electronic expansion valve defective
Stop valve defective
Troubleshooting
Check No.4
Refer to P.139
Check No.6
Refer to P.141
Check No.11
Refer to P.144
Replace a defective
thermistor.
Replace the valve itself or
the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R2846)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check No. 6
Check the thermistors.
Malfunctioning
z
Discharge pipe thermistor
z
Outdoor unit heat exchanger thermistor
z
Outdoor temperature thermistor
z
Refrigerant shortage
z
Four way valve malfunctioning
z
Water mixed
z
Stop valve defective
Malfunctioning
Functioning
Functioning
Functioning
C
heck No.
11
Check the refrigerant line.
Malfunctioning
C
heck No.
4
Check the electronic expansion
valve.
Summary of Contents for ARXS50C2VMB
Page 109: ...Instruction SiEN04 306D 100 System Configuration ...
Page 199: ...Outdoor Unit SiEN04 306D 190 Removal Procedure ...
Page 203: ...Others SiEN04 306D 194 Others ...
Page 214: ...SiEN04 306D Wiring Diagrams Appendix 205 FTKD18 24 28BVMS ...
Page 216: ...SiEN04 306D Wiring Diagrams Appendix 207 RKD18 24 28BVMS ...