SiEN04-306D
Specifications
Specifications
17
50Hz 230V
Note:
MAX. interunit piping length: 30m
MIN. interunit piping length: 1.5m
MAX. interunit height difference: 20m
Amount of additional charge of refrigerant 20g/m for piping length exceeding 10m
The data are based on the conditions shown in the table below.
Model
Indoor Units
FTKS71BAVMB
FTS50BVMB
FTS60BVMB
Outdoor Units
RKS71B3VMB
RS50B(2)VMB
RS60B(2)VMB
Capacity
Rated (Min.~Max.)
kW
7.1 (0.9~8.0)
5.0
6.0
Btu/h
24,240 (3,070~27,310)
17,070
20,480
kcal/h
6,110 (770~6,880)
4,300
5,160
Moisture Removal
L/h
4.5
2.9
3.9
Running Current (Rated)
A
11.1
7.3
9.3
Power Consumption
Rated (Min.~Max.)
W
2,530 (450~3,070)
1,660
2,120
Power Factor
%
99.1
98.9
99.1
COP
W/W
2.81
3.01
2.83
Piping
Connections
Liquid
mm
φ
6.4
φ
6.4
φ
6.4
Gas
mm
φ
15.9
φ
12.7
φ
12.7
Drain
mm
φ
18.0
φ
18.0
φ
18.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Indoor Unit
FTKS71BAVMB
FTS50BVMB
FTS60BVMB
Front Panel Color
White
White
White
Air Flow Rate
m
3
/min
(cfm)
H
16.7 (590)
11.5 (406)
16.4 (579)
M
14.2 (501)
9.8 (346)
13.6 (491)
L
11.6 (409)
8.3 (293)
11.6 (409)
SL
10.6 (374)
—
—
Fan
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output
W
43
40
43
Speed
Steps
5 Steps, Silent and Auto
5 Steps and Auto
5 Steps and Auto
Air Direction Control
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Right, Left, Horizontal and Downward
Air Filter
Removable/Washable/Mildew Proof
Removable/Washable/Mildew Proof
Removable/Washable/Mildew Proof
Running Current (Rated)
A
0.20
0.18
0.18
Power Consumption (Rated)
W
45
40
40
Power Factor
%
96.4
96.6
96.6
Temperature Control
Microcomputer Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
290×1,050×238
290×795×230
290×1,050×230
Packaged Dimensions (H×W×D)
mm
337×1,147×366
280×840×338
337×1,147×366
Weight
kg
12
9
12
Gross Weight
kg
17
13
17
Operation
Sound
H/M/L/SL
dBA
46/42/37/34
44/35
45/36
Sound Power
H
dBA
63
63
63
Outdoor Unit
RKS71B3VMB
RS50B(2)VMB
RS60B(2)VMB
Casing Color
Ivory White
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
2YC45BXD
2YC32HXD
2YC32HXD
Motor Output
W
1,900
1,500
1,500
Refrigerant Oil
Type
FVC50K
FVC50K
FVC50K
Charge
L
0.75
0.65
0.65
Refrigerant
Type
R-410A
R-410A
R-410A
Charge
kg
1.70
1.20
1.70
Air Flow Rate
m
3
/min (cfm)
H
51.5 (1,818)
47.7(1,684)
47.6 (1,680)
L
41.5 (1,465)
44.1(1,557)
44.1 (1,557)
Fan
Type
Propeller
Propeller
Propeller
Motor Output
W
53
53
53
Running Current (Rated)
A
10.90
7.12
9.12
Power Consumption (Rated)
W
2,485
1,620
2,080
Power Factor
%
99.1
98.9
99.2
Starting Current
A
11.1
7.3
9.3
Dimensions (H×W×D)
mm
735×825×300
735×825×300
735×825×300
Packaged Dimensions (H×W×D)
mm
784×960×390
784×960×390
784×960×390
Weight
kg
55
49
52
Gross Weight
kg
59
53
57
Operation
Sound
H
dBA
52
47
49
Sound Power
H
dBA
66
63
64
Drawing No.
3D050879
3D040786A
3D040787A
Conversion Formula
kcal/h=kW×860
Btu/h=kW×3414
cfm=m
3
/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
7.5m
Summary of Contents for ARXS50C2VMB
Page 109: ...Instruction SiEN04 306D 100 System Configuration ...
Page 199: ...Outdoor Unit SiEN04 306D 190 Removal Procedure ...
Page 203: ...Others SiEN04 306D 194 Others ...
Page 214: ...SiEN04 306D Wiring Diagrams Appendix 205 FTKD18 24 28BVMS ...
Page 216: ...SiEN04 306D Wiring Diagrams Appendix 207 RKD18 24 28BVMS ...