Outdoor Unit
SiEN04-306D
182
Removal Procedure
2.4
Removal of the Reactor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the electrical box.
1. Remove the partition plate.
1
Release the clamp by
pliers.
2
Loosen the two screws
of the partition plate.
The partition plate is fixed to
the bottom frame with a
claw.
P
a
rtition pl
a
te
(R272
3
)
(R2724)
Claw