background image

8 Configuration

Installer reference guide

21

35R5V1B RXM20~35R5V1B
R32 Split Series
4P519439-8H – 2020.07

7.6

Starting up the outdoor unit

See  the  indoor  unit  installation  manual  for  configuration  and
commissioning of the system.

8

Configuration

8.1

Facility setting

Use  this  function  for  cooling  at  low  outdoor  temperature.  This
function  is  designed  for  facilities  such  as  equipment  of  computer
rooms. NEVER use in a residence or office where people occupy the
space.

8.2

To set the facility mode

When cutting jumper J6 on the PCB, the operation range will expand
to –15°C. The facility mode will stop if the outdoor temperature drops
below –20°C and resume when the temperature rises again.

J12

J11

J9

J8

J6

J5

INFORMATION

▪ The  indoor  unit  may  produce  Intermittent  noise  due  to

the outdoor unit fan turning ON and/or OFF.

▪ Do  NOT  place  humidifiers  or  other  items  which  might

raise humidity in rooms when you use the facility mode.

▪ Cutting jumper J6 sets the indoor unit fan to the highest

speed.

▪ Do  NOT  use  this  setting  in  residences  or  offices  with

people.

9

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do for the maintenance of the unit.

▪ Explain  the  user  about  energy  saving  tips  as  described  in  the

operation manual.

10

Maintenance and service

NOTICE

Maintenance  MUST  be  done  by  an  authorized  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

10.1

Overview: Maintenance and
service

This chapter contains information about:

▪ Maintenance safety precautions

▪ The yearly maintenance of the outdoor unit

10.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel, remove the fuses or open the protection devices
of the unit.

▪ Do NOT touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

▪ Please  note  that  some  sections  of  the  electric

component box are hot.

▪ Make sure you do NOT touch a conductive section.

▪ Do NOT rinse the unit. This may cause electric shocks

or fire.

10.3

Checklist for yearly maintenance
of the outdoor unit

Check the following at least once a year:

▪ Heat exchanger

The heat exchanger of the outdoor unit can get blocked up due to
dust,  dirt,  leaves,  etc.  It  is  recommended  to  clean  the  heat
exchanger  yearly.  A  blocked  heat  exchanger  can  lead  to  too  low
pressure or too high pressure leading to worse performance.

11

Troubleshooting

11.1

Overview: Troubleshooting

This chapter describes what you have to do in case of problems.

It contains information about solving problems based on symptoms.

Before troubleshooting

Carry  out  a  thorough  visual  inspection  of  the  unit  and  look  for
obvious defects such as loose connections or defective wiring.

Summary of Contents for ARXM-R

Page 1: ...Installer reference guide R32 Split Series English Installer reference guide R32 Split Series RXM20R5V1B RXM25R5V1B RXM35R5V1B ARXM25R5V1B ARXM35R5V1B ...

Page 2: ... 15 6 5 3 To check for leaks 16 6 5 4 To perform vacuum drying 16 6 6 Charging refrigerant 16 6 6 1 About charging refrigerant 16 6 6 2 About the refrigerant 17 6 6 3 Precautions when charging refrigerant 17 6 6 4 To determine the additional refrigerant amount 17 6 6 5 To determine the complete recharge amount 17 6 6 6 To charge additional refrigerant 17 6 6 7 To fix the fluorinated greenhouse gas...

Page 3: ...ter operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Improper installation or attachment of equipment or accessories could result in electrical shock short circuit leaks fire or other damage to the equipment Only use accessories optional equipment and spare part...

Page 4: ...sed in the duct work air inlet AND outlet are connected directly to the same room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet NOTICE Precautions shall be taken to avoid excessive vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision sh...

Page 5: ... 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg Amin m2 4 6 20 0 4 8 21 8 5 0 23 6 1 842 5 2 25 6 1 843 4 45 5 4 27 6 2 0 4 83 5 6 29 7 2 2 5 31 5 8 31 8 2 4 5 79 6 0 34 0 2 6 6 39 6 2 36 4 2 8 7 41 6 4 38 7 3 0 8 51 6 6 41 2 3 2 9 68 6 8 43 7 3 4 10 9 7 0 46 3 3 6 12 3 7 2 49 0 3 8 13 7 7 4 51 8 4 0 15 1 7 6 54 6 4 2 16 7 7 8 57 5 4 4 18 3 7 956 59 9 Wall mounted unit b m kg ...

Page 6: ... form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately If the valve is NOT closed immediately remaining pressure might charge additional refrigerant Possible consequence Incorrect refrigerant amount 1 2 4 Water If applicable See the installation manual or installer reference guide of your applic...

Page 7: ...llers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the outdoor unit Outdoor unit installation manual Installation instructions Format Paper in the box of the outdoor unit Installer reference guide Preparation of the installation reference dat...

Page 8: ...the accessories at the bottom of the package 1 1 1 1 1 1 b e c d a f a General safety precautions b Outdoor unit installation manual c Fluorinated greenhouse gases label d Multilingual fluorinated greenhouse gases label e Drain plug located on the bottom of the packing case f Energy label 4 About the unit WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable 4 1 Overview ...

Page 9: ...RNING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and objects under the unit may get dirty or damaged WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an oper...

Page 10: ... winds Example Behind the building b c a If the outdoor unit is exposed to direct sea winds install a windbreaker Height of windbreaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d a Sea wind b Building c Outdoor unit d Windbreaker The outdoor unit is designed for outdoor installation only and for ambient temperatures ranging from 10 50...

Page 11: ... N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped ...

Page 12: ...Use a vibration proof rubber field supply in cases where vibrations may be transmitted to the building Fix the unit securely by means of foundation bolts in accordance with the foundation drawing Prepare 4 sets of M8 or M10 anchor bolts nuts and washers field supply 20 mm 311 5 7 4 2 1 1 mm 2 1 1 a a 100 mm above expected level of snow 6 3 4 To install the outdoor unit 4 M8 M10 6 3 5 To provide dr...

Page 13: ...s when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation DANGER RISK OF BURNING SCALDING CAUTION Use the flare nut fixed to the unit To prevent gas leakage apply refrigeration oil only to the inside of the flare Use refrigeration oil for R32 Do NOT reuse joints CAUTION Do NOT use mineral oil on ...

Page 14: ...ent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing down so that the chips do NOT enter the pipe a b a Cut exactly at right angles b Remove burrs 3 Remove the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the ...

Page 15: ...Service port 2 Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 6 5 Checking the refrigerant piping 6 5 1 About checking the refrigerant piping The outdoor unit s internal refrige...

Page 16: ...rying again NOTICE Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor INFORMATION After opening the stop valve it is possible that the pressure in the refrigerant piping does NOT increase This might be caused by e g the closed state of the expansion valve in the outdoor unit ...

Page 17: ... To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the factory refrigerant charge see unit name plate the determined additional amount 6 6 6 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming poten...

Page 18: ...Do NOT branch the power supply for the drain pump etc from the terminal block This could result in electrical shock or fire WARNING Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DANGER RISK OF EL...

Page 19: ...ock or leakage 3 Open the wire clamp 4 Connect the interconnection cable and power supply as follows 50 Hz 220 240 V c d f a b e a Interconnection cable b Power supply cable c Circuit breaker d Earth leakage circuit breaker e Power supply f Earth 3 5 Tighten the terminal screws securely We recommend using a Phillips screwdriver 6 8 Finishing the outdoor unit installation 6 8 1 To finish the outdoo...

Page 20: ... be closed Power up the unit after it is closed The indoor unit is properly mounted The outdoor unit is properly mounted The system is properly earthed and the earth terminals are tightened The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed...

Page 21: ...at least once a year However applicable legislation might require shorter maintenance intervals NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 10 1 Overview Maintena...

Page 22: ...he connection of the earth wiring 11 3 5 Symptom Unit does NOT function or burn damage Possible causes Corrective action The wiring was NOT performed in accordance with the specifications Correct the wiring 11 4 Fault diagnosis using LED on outdoor unit PCB LED is Diagnosis flashing Normal Check the indoor unit ON Turn the power OFF and back ON and check the LED within approximately 3 minutes If t...

Page 23: ...forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 12 3 To start and stop forced cooling There are 2 methods to perform forced cooling Method 1 Using the indoor unit ON OFF switch if present on the indoor unit Method 2 Using the indoor unit user interface 12 3 1 To start and stop forced cooling using the indoor unit ON OFF switch 1 Pr...

Page 24: ...ITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR ...

Page 25: ...or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels manuals ...

Page 26: ......

Page 27: ......

Page 28: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 4P519439 8H 2020 07 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: