12 Disposal

Installer reference guide

22

35R5V1B RXM20~35R5V1B

R32 Split Series

4P519439-8H – 2020.07

11.2

Precautions when troubleshooting

WARNING

▪ When  carrying  out  an  inspection  on  the  switch  box  of

the  unit,  ALWAYS  make  sure  that  the  unit  is
disconnected  from  the  mains.  Turn  off  the  respective
circuit breaker.

▪ When a safety device was activated, stop the unit and

find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  shunt  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.

DANGER: RISK OF ELECTROCUTION

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out:  power  to  this  appliance  MUST  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

DANGER: RISK OF BURNING/SCALDING

11.3

Solving problems based on
symptoms

11.3.1

Symptom: Indoor units fall, vibrate or
make noise

Possible causes

Corrective action

The indoor units are not installed
securely

Install the indoor units securely.

11.3.2

Symptom: The unit is NOT heating or
cooling as expected

Possible causes

Corrective action

Wrong connection of the
electrical wires

Connect the electrical wires
correctly.

Gas leakage

Check for gas leakage.

11.3.3

Symptom: Water leakage

Possible causes

Corrective action

Incomplete thermal insulation
(gas and liquid piping, indoor
portions of the drain hose
extension)

Make sure the thermal insulation
of the piping and the drain hose
is complete.

Improperly connected drainage

Secure the drainage.

11.3.4

Symptom: Electrical leakage

Possible causes

Corrective action

The unit is NOT earthed correctly Check and correct the

connection of the earth wiring.

11.3.5

Symptom: Unit does NOT function or burn
damage

Possible causes

Corrective action

The wiring was NOT performed
in accordance with the
specifications

Correct the wiring.

11.4

Fault diagnosis using LED on
outdoor unit PCB

LED is…

Diagnosis

flashing

Normal.

▪ Check the indoor unit.

ON

▪ Turn  the  power  OFF  and  back  ON,  and

check  the  LED  within  approximately  3
minutes.
If  the  LED  is  ON  again,  the  outdoor  unit
PCB is faulty.

OFF

1

Supply voltage (for power saving).

2

Power supply fault.

3

Turn  the  power  OFF  and  back  ON,  and
check  the  LED  within  approximately  3
minutes.
If the LED is OFF again, the outdoor unit
PCB is faulty.

DANGER: RISK OF ELECTROCUTION

▪ When  the  unit  is  not  operating,  the  LEDs  on  the  PCB

are turned off in order to save power.

▪ Even when the LEDs are off, the terminal block and the

PCB may be powered.

12

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

12.1

Overview: Disposal

Typical workflow

Disposing of the system typically consists of the following stages:

1

Pumping down the system.

2

Bringing the system to a specialized treatment facility.

INFORMATION

For more details, see the service manual.

12.2

To pump down

Example: 

To  protect  the  environment,  pump  down  when  relocating

the unit or when disposing of the unit.

DANGER: RISK OF EXPLOSION

Pump  down  –  Refrigerant  leakage.

  If  you  want  to  pump

down  the  system,  and  there  is  a  leak  in  the  refrigerant
circuit:

▪ Do NOT use the unit's automatic pump down function,

with  which  you  can  collect  all  refrigerant  from  the
system  into  the  outdoor  unit. 

Possible  consequence:

Self-combustion  and  explosion  of  the  compressor
because of air going into the operating compressor.

▪ Use  a  separate  recovery  system  so  that  the  unit's

compressor does NOT have to operate.

Summary of Contents for ARXM-R

Page 1: ...Installer reference guide R32 Split Series English Installer reference guide R32 Split Series RXM20R5V1B RXM25R5V1B RXM35R5V1B ARXM25R5V1B ARXM35R5V1B ...

Page 2: ... 15 6 5 3 To check for leaks 16 6 5 4 To perform vacuum drying 16 6 6 Charging refrigerant 16 6 6 1 About charging refrigerant 16 6 6 2 About the refrigerant 17 6 6 3 Precautions when charging refrigerant 17 6 6 4 To determine the additional refrigerant amount 17 6 6 5 To determine the complete recharge amount 17 6 6 6 To charge additional refrigerant 17 6 6 7 To fix the fluorinated greenhouse gas...

Page 3: ...ter operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Improper installation or attachment of equipment or accessories could result in electrical shock short circuit leaks fire or other damage to the equipment Only use accessories optional equipment and spare part...

Page 4: ...sed in the duct work air inlet AND outlet are connected directly to the same room by ducting Do NOT use spaces such as a false ceiling as a duct for the air inlet or outlet NOTICE Precautions shall be taken to avoid excessive vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision sh...

Page 5: ... 7 8 38 5 4 2 150 7 8 518 4 4 12 3 7 956 40 1 4 4 165 7 956 539 m kg Amin m2 4 6 20 0 4 8 21 8 5 0 23 6 1 842 5 2 25 6 1 843 4 45 5 4 27 6 2 0 4 83 5 6 29 7 2 2 5 31 5 8 31 8 2 4 5 79 6 0 34 0 2 6 6 39 6 2 36 4 2 8 7 41 6 4 38 7 3 0 8 51 6 6 41 2 3 2 9 68 6 8 43 7 3 4 10 9 7 0 46 3 3 6 12 3 7 2 49 0 3 8 13 7 7 4 51 8 4 0 15 1 7 6 54 6 4 2 16 7 7 8 57 5 4 4 18 3 7 956 59 9 Wall mounted unit b m kg ...

Page 6: ... form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately If the valve is NOT closed immediately remaining pressure might charge additional refrigerant Possible consequence Incorrect refrigerant amount 1 2 4 Water If applicable See the installation manual or installer reference guide of your applic...

Page 7: ...llers Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you MUST read before installing Format Paper in the box of the outdoor unit Outdoor unit installation manual Installation instructions Format Paper in the box of the outdoor unit Installer reference guide Preparation of the installation reference dat...

Page 8: ...the accessories at the bottom of the package 1 1 1 1 1 1 b e c d a f a General safety precautions b Outdoor unit installation manual c Fluorinated greenhouse gases label d Multilingual fluorinated greenhouse gases label e Drain plug located on the bottom of the packing case f Energy label 4 About the unit WARNING FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable 4 1 Overview ...

Page 9: ...RNING Do NOT place objects below the indoor and or outdoor unit that may get wet Otherwise condensation on the main unit or refrigerant pipes air filter dirt or drain blockage may cause dripping and objects under the unit may get dirty or damaged WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an oper...

Page 10: ... winds Example Behind the building b c a If the outdoor unit is exposed to direct sea winds install a windbreaker Height of windbreaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d a Sea wind b Building c Outdoor unit d Windbreaker The outdoor unit is designed for outdoor installation only and for ambient temperatures ranging from 10 50...

Page 11: ... N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped ...

Page 12: ...Use a vibration proof rubber field supply in cases where vibrations may be transmitted to the building Fix the unit securely by means of foundation bolts in accordance with the foundation drawing Prepare 4 sets of M8 or M10 anchor bolts nuts and washers field supply 20 mm 311 5 7 4 2 1 1 mm 2 1 1 a a 100 mm above expected level of snow 6 3 4 To install the outdoor unit 4 M8 M10 6 3 5 To provide dr...

Page 13: ...s when connecting the refrigerant piping INFORMATION Also read the precautions and requirements in the following chapters General safety precautions Preparation DANGER RISK OF BURNING SCALDING CAUTION Use the flare nut fixed to the unit To prevent gas leakage apply refrigeration oil only to the inside of the flare Use refrigeration oil for R32 Do NOT reuse joints CAUTION Do NOT use mineral oil on ...

Page 14: ...ent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing down so that the chips do NOT enter the pipe a b a Cut exactly at right angles b Remove burrs 3 Remove the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the ...

Page 15: ...Service port 2 Connect the gas refrigerant connection from the indoor unit to the gas stop valve of the outdoor unit NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 6 5 Checking the refrigerant piping 6 5 1 About checking the refrigerant piping The outdoor unit s internal refrige...

Page 16: ...rying again NOTICE Make sure to open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor INFORMATION After opening the stop valve it is possible that the pressure in the refrigerant piping does NOT increase This might be caused by e g the closed state of the expansion valve in the outdoor unit ...

Page 17: ... To determine the complete recharge amount INFORMATION If a complete recharge is necessary the total refrigerant charge is the factory refrigerant charge see unit name plate the determined additional amount 6 6 6 To charge additional refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming poten...

Page 18: ...Do NOT branch the power supply for the drain pump etc from the terminal block This could result in electrical shock or fire WARNING Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot DANGER RISK OF ELECTROCUTION All electrical parts including thermistors are powered by the power supply Do not touch them with bare hands DANGER RISK OF EL...

Page 19: ...ock or leakage 3 Open the wire clamp 4 Connect the interconnection cable and power supply as follows 50 Hz 220 240 V c d f a b e a Interconnection cable b Power supply cable c Circuit breaker d Earth leakage circuit breaker e Power supply f Earth 3 5 Tighten the terminal screws securely We recommend using a Phillips screwdriver 6 8 Finishing the outdoor unit installation 6 8 1 To finish the outdoo...

Page 20: ... be closed Power up the unit after it is closed The indoor unit is properly mounted The outdoor unit is properly mounted The system is properly earthed and the earth terminals are tightened The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed...

Page 21: ...at least once a year However applicable legislation might require shorter maintenance intervals NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 10 1 Overview Maintena...

Page 22: ...he connection of the earth wiring 11 3 5 Symptom Unit does NOT function or burn damage Possible causes Corrective action The wiring was NOT performed in accordance with the specifications Correct the wiring 11 4 Fault diagnosis using LED on outdoor unit PCB LED is Diagnosis flashing Normal Check the indoor unit ON Turn the power OFF and back ON and check the LED within approximately 3 minutes If t...

Page 23: ...forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 12 3 To start and stop forced cooling There are 2 methods to perform forced cooling Method 1 Using the indoor unit ON OFF switch if present on the indoor unit Method 2 Using the indoor unit user interface 12 3 1 To start and stop forced cooling using the indoor unit ON OFF switch 1 Pr...

Page 24: ...ITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC RELAY L LIVE L COIL L R REACTOR M STEPPER MOTOR M C COMPRESSOR MOTOR M F FAN MOTOR ...

Page 25: ...or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance instructions Instruction manual specified for a certain product or application which explains if relevant how to install configure operate and or maintain the product or application Accessories Labels manuals ...

Page 26: ......

Page 27: ......

Page 28: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 4P519439 8H 2020 07 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: