6 Electrical installation
Installation manual
15
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
Outdoor water piping insulation
NOTICE
Outside piping.
Make sure the outside piping is insulated
as instructed to protect against hazards.
For piping in free air, it is recommended to use the insulation
thickness as shown in below table as a minimum (with λ=0.039 W/
mK).
Piping length (m)
Minimum insulation thickness
(mm)
<20
19
20~30
32
30~40
40
40~50
50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
be
reached
via
professional.standbyme.daikin.eu
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X3M
0.88 ±10%
X4M
2.45 ±10%
X5M
0.88 ±10%
X7M
0.88 ±10%
X9M
2.45 ±10%
X10M
0.88 ±10%
6.3
Connections to the outdoor unit
Item
Description
Power supply (main)
"6.3.2 To connect the main power
Power supply (backup
heater)
(in case of outdoor unit
with integrated backup
heater)
"6.3.3 To connect the backup heater
Backup heater kit +
Bypass valve kit
(in case of external
backup heater kit)
20].
User interface
22].
Shut-off valve
"6.3.6 To connect the shut-off
24].
Electricity meters
"6.3.7 To connect the electricity
Domestic hot water
pump
"6.3.8 To connect the domestic hot
Alarm output
25].
Space cooling/heating
operation control
"6.3.10 To connect the space cooling/
Changeover to
external heat source
control
"6.3.11 To connect the changeover to
Power consumption
digital inputs
27].
Safety thermostat
thermostat (normally closed
contact)"
Smart Grid