Troubleshooting by Indication on the Remote Controller
Troubleshooting
219
[CHECK 1] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Short circuit
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
particles
←Check to be sure the stop valve is open.
←Conduct visual checks for pipe conditions.
←Is there any temperature difference caused before
and after the filter or branch pipe.
Faulty indoor
unit electronic
expansion valve
←Are the coil resistance and insulation
normal?
Faulty high
pressure
control
Faulty valve coil
Faulty valve body
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *1.)
Faulty
control
Faulty high pressure sensor
Faulty indoor unit
liquid pipe thermistor
Faulty control PCB
←Are the electrical characteristics normal?
←In the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure
sensor?
High suction
air
temperature
of the
condenser
[In heating]
High suction air
temperature of
indoor unit
High ambient temperature
←Is the suction air temperature not more than 27°C?
←Is the indoor temperature not more than 27°C?
Faulty suction air thermistor of indoor unit
High suction air temperature of outdoor unit
Faulty outdoor temperature thermistor of outdoor unit
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←Is the outdoor temperature not more than 16°CWB?
←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
←Is the heat exchanger clogged? (In cooling)
←Is air or else mixed in the refrigerant system?
Decreased
fan airflow
rate
Decreased
fan
output
Faulty fan
motor
←Can the fan motor be rotated with hands?
Are the motor coil resistance and insulation
normal?
←If a spare PC board is mounted, is the
capacity setting properly made?
Faulty control
PC board
(Including
capacity setting)
High air
passage
resistance
Dirty filter
←Is the air filter clogged?
Obstacle
←Is there any obstacle in the air passage?
Excessive refrigerant charging
Improper model selection
[In heating]
←Refer to P.173.
←Is the indoor unit too small compared to
the large-sized outdoor unit?
*1: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control” on P.72.)
C: SDK04009
Summary of Contents for ALTHERMA HT ERSQ 011 AA
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit...
Page 125: ...ESIE09 08A Field Setting Test Operation 113...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix...