ESIE09-08A
Special Control
Function
59
3.2 Defrosting Operation
The defrost operation is performed to solve frost on the outdoor unit heat exchanger when heating mode
is active to recover the heating capacity.
[Conditions to start]
The defrost operation is started referring following conditions.
Outdoor heat exchanger heat transfer co-efficient
Temperature of heat-exchange (Tb) < T
def
*
Timer (25 min. the minimum)
In addition, outdoor heat-exchanger co-efficient is derived from Tc, Te, and the compressor load.
*T
def
can vary but is at least -10°C
[Fan defrosting]
When compressor stops, 80 sec. at low RPM
At start up compressor, 30 sec. at 950 RPM (step 9)
Then goes back to normal RPM
Summary of Contents for ALTHERMA HT ERSQ 011 AA
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit...
Page 125: ...ESIE09 08A Field Setting Test Operation 113...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix...