ESIE09-08A
Field Setting
Test Operation
89
3.1.2
Setting Contents and Code No. – EKHBRD – Indoor unit
EKHBRD*AA
First
code
Second
code
Setting name
Installer setting at variance with
default value
Default
value
Range
Step
Unit
Date
Value
Date
Value
0
Remote control setup
00
User permission level
2
2~3
1
—
01
Room temperature compensation value
0
–5~5
0.5
°C
02
Not applicable. Do not change the default value.
1 (ON)
0/1
—
—
03
Status: space heating schedule timer mode
1 (ON)
0/1
—
—
1
Automatic storage timing for domestic water heating
00
Status: night time storage
1 (ON)
0/1
—
—
01
Night time storage start time
1:00
0:00~
23:00
1:00
hour
02
Status: day time storage
0 (OFF)
0/1
—
—
03
Day time storage start time
15:00
0:00~
23:00
1:00
hour
2
Automatic setback function
00
Status: setback operation
1 (ON)
0/1
—
—
01
Setback operation start time
23:00
0:00~
23:00
1:00
hour
02
Setback operation stop time
5:00
0:00~
23:00
1:00
hour
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
70
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
45
25~80
1
°C
4
Disinfection function
00
Status: disinfection operation
1 (ON)
0/1
—
—
01
Disinfection operation day selection
Fri
Mon~Sun
—
—
02
Disinfection operation start time
23:00
0:00~
23:00
1:00
hour
5
Automatic setback and disinfection set point
00
Set point: disinfection operation temperature
70
60~70
5
°C
01
Disinfection operation time duration
10
5~60
5
min
02
Leaving water setback temperature
5
0~10
1
°C
03
Room setback temperature
18
17~23
1
°C
6
Option setup
00
Domestic hot water tank installed
0 (OFF)
0/1
—
—
01
Optional room thermostat installed
0 (OFF)
0/1
—
—
02
Backup heater kit activation
0 (OFF)
0/1
—
—
03
Solar kit activation
0 (OFF)
0/1
—
—
04
Benefit kWh power supply mode
0
0/2
1
—
Summary of Contents for ALTHERMA HT ERSQ 011 AA
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit...
Page 125: ...ESIE09 08A Field Setting Test Operation 113...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix...