Field Setting
ESIE09-08A
112
Test Operation
[E] Service mode
[E-00]
Vacuum mode
When recovering/vacuuming of the indoor unit is needed, field setting [E-00] should be activated. It
will force the unit into thermo OFF and will open the expansion valve of the indoor unit R-134a
circuit so full vacuuming is possible.
By default [E-00] = 0, set to 1 to enable the vacuum mode.
Note :
Do not forget to restore the field setting [E-00] to the default value when vacuuming is finished!
When [E-00]=0 is set to 1 (recovery mode), [E-04] can be set to 2 to enhance recovery of the refrigerant.
[E-04]
Pump only operation
When commissioning and installing the unit it is very important to get all air out of the water circuit.
Through this field setting the pump can be operated without actual operation of the unit. By doing so
this will enhance the air removal from the circuit. The pump can operate at different speed:
[E-04]
= 0 normal operation of the unit (default)
[E-04]
= 1 low pump speed operation (pump only, unit is not operating)
[E-04]
= 2 high pump speed operation (pump only, unit is not operating)
Notes :
1. If you select [E-04]=1 or 2 and [6-00]=1, the unit will activate the domestic hot water 3-way valve.
This function is a helpful feature to get all air removed out of the system (as well in space heating as
in domestic hot water heating).
[E-04]=1 or 2 & [6-00]=0 => Pump operation of 20 minutes. 3-Way valve in space heating mode.
[E-04]=1 or 2 & [6-00]=1 => Pump operation of 10 minutes. 3-Way valve in domestic hot water
heating mode.
2. Do not forget to restore the field setting [E-04] to the default value when commissioning is finished!
3. When using thermostatic radiator valves, make sure to open all valves during air purging operation.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
E
Service mode
00
Vacuum mode
0
0/1
—
—
04
Pump only operation
0
0~2
1
—
Summary of Contents for ALTHERMA HT ERSQ 011 AA
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit...
Page 125: ...ESIE09 08A Field Setting Test Operation 113...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix...