background image

Installation manual

5

ERYQ005~007ABV3

Outdoor unit for air to water heat pump

3P177782-1B

Refrigerant piping work

Pipe handling guidelines

Protect the open end of the pipe against dust and moisture.

All pipe bends should be as gentle as possible. Use a pipe
bender for bending.
Bending radius should be 30 to 40 mm or larger.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the
following:

Insulation material: polyethylene foam
Heat transfer rate: 0.041 to 0.052 kW/mK (0.035 to 0.045 kcal/
mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this
temperature.

Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.

Use separate thermal insulation pipes for gas and liquid
refrigerant pipes.

Purging air and checking gas leakage

When all piping work is completed and the outdoor unit is connected
to the indoor unit, it is necessary to purge the air and check for gas
leakage.

If using additional refrigerant, perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.

Use a hexagonal wrench (4 mm) to operate the stop valve rod.

All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque. See 

"Connecting the

refrigerant piping to the outdoor unit" on page 4

 for details.

1

Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas
stop valve's service port.

2

Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi).
The high-pressure valve subsequently requires no operation.

3

Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).

4

Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump.

Leave as is for 4-5 minutes and make sure that the coupling
meter needle does not go back.

5

Remove the covers from the liquid stop valve and gas stop
valve.

Valve cap tightening torque

Valve cap

Gas pipe

Ø6.4 mm (1/4")

21.6~27.4 N•m

(220~280 kgf•cm)

Ø15.9 mm (5/8")

44.1~53.9 N•m

(450~550 kgf•cm)

Service port cap tightening torque

10.8~14.7 N•m (110~150 kgf•cm)

Pipe size

Pipe insulation

Outer 

diameter

Thickness

Inner diameter

Thickness

6.4 mm (1/4")

0.8 mm

8-10 mm

10 mm

15.9 mm (5/8")

1.0 mm

16-20 mm

13 mm

1

Gas pipe

2

Inter-unit wiring

3

Liquid pipe

4

Liquid pipe insulation

5

Finishing tape

6

Gas pipe insulation

5

6

1

2

4

3

WARNING

Do not mix any substance other than the specified
refrigerant (R410A) into the refrigeration cycle.

When refrigerant gas leaks occur, ventilate the room
as soon and as much as possible.

R410A, as well as other refrigerants, should always
be recovered and never be released directly into the
environment.

CAUTION

Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may damage
the vacuum pump or the unit.

1

Pressure meter

2

Gauge manifold

3

Low-pressure valve (Lo)

4

High-pressure valve (Hi)

5

Charging hoses

6

Vacuum pump

7

Service port

8

Valve lids

9

Gas stop valve

10

Liquid stop valve

Pipe length

15 m

>15 m

Run time

10 minutes

15 minutes

NOTE

If the meter needle does go back, this may
indicate presence of moisture or leaking from
connecting parts. Repeat steps 2 through 4 after
checking all connecting parts and slightly
loosening and retightening the nuts.

1

4

10

2

6

5

3

7 8 9

8

Summary of Contents for Altherma ERYQ005ABV3

Page 1: ...INSTALLATION MANUAL ERYQ005ABV3 ERYQ006ABV3 ERYQ007ABV3 Outdoor unit for air to water heat pump ...

Page 2: ...e an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause terminal ove...

Page 3: ...o that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not annoy the ...

Page 4: ...een outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover 3 Stop...

Page 5: ...the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tight...

Page 6: ...ssure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers from t...

Page 7: ...imilar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system Wiring Procedure 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units so that the terminal numbers match see wiring diagram below Tighten the terminal screws securely We recommend a flathead s...

Page 8: ...urely 3 NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installations 1 Single core wire 2 Screw 3 Flat washer 1 Round crimp style terminal 2 Screw 3 Flat washer A A AA 2 3 1 1 3 2 3 3 2 1 1 B B L N 1 2 3 1 3 2 CAUTION 1 In case the use of stranded conductor wires is unavoidable for one reason or another make sure to install round crimp style termina...

Page 9: ...ocal and national legislation NOTE Remark that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the syst...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 3P177782 1B ...

Reviews: