background image

ERYQ005~007ABV3

Outdoor unit for air to water heat pump

3P177782-1B

Installation manual

6

6

Turn  the liquid stop valve's rod 90 degrees counterclockwise
with a hexagonal wrench to open the valve.

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's
flare and the outdoor unit's flare and the valve rods.
After the check is complete, wipe all soapy water off.

7

Disconnect the charging hose from the gas stop valve's service
port, then fully open the liquid and gas stop valves.

Do not attempt to turn the valve rod beyond its stop.

8

Tighten the valve lids and service port caps for the liquid and
gas stop valves with a torque wrench at the specified torques.
See 

"Connecting the refrigerant piping to the outdoor unit" on

page 4

 for details.

Charging refrigerant

This outdoor unit is factory charged.

Re-charging

In case re-charging is required, refer to the nameplate of the unit. The
nameplate states the type of refrigerant and necessary amount.

Charging additional refrigerant

If the total length of refrigerant piping exceeds 10 m in length,
additionally charge with 20 

g of refrigerant (R410A) for each

additional meter of piping.

Determine the weight of refrigerant to be charged additionally and fill
in the amount in the service sticker on the rear side of the stop valve
cover.

Precautions when adding R410A

Be sure to charge the specified amount of refrigerant in liquid
state to the liquid pipe.
Since this refrigerant is a mixed refrigerant, adding it in gas form
may cause the refrigerant composition to change, preventing
normal operation.

Before charging, check whether the refrigerant cylinder is
equipped with a siphon tube or not (the cylinder should be
marked with "liquid filling siphon attached" or something similar).

Be sure to use tools exclusively for R410A to ensure required
pressure resistance and to prevent foreign materials from mixing
into the system.

Wiring

Procedure

1

Strip the insulation from the wire (20 mm).

2

Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match (see wiring diagram
below). Tighten the terminal screws securely. We recommend a
flathead screwdriver to tighten the screws.
See also caution 2 under 

"Notes to observe" on page 7

  for

wiring guidelines.

Charge the liquid 
refrigerant with the 
cylinder in upright 
position.

Charge the liquid 
refrigerant with the 
cylinder in up-side-down 
position.

WARNING

All wiring must be performed by an authorized
electrician.

The power supply cable and circuit breaker must be
selected in accordance with local and national
regulations.

Do not use tapped wires, stranded conductor wires
(see caution 1 under 

"Notes to observe" on page 7

),

extension cords, or connections from a star system,
as they may cause overheating, electrical shock or
fire.

Do not use locally purchased electrical parts inside
the product and do not branch the power for the
heater tape, etc., from the terminal block. Doing this
may cause electrical shock or fire.

Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, which means that an earth
leakage circuit breaker capable of handling high
harmonics needs to be used in order to prevent
malfunctioning of the earth leakage circuit breaker
itself.

Use an all-pole disconnection type breaker with a
contact separation of at least 3 mm inbetween all
poles.

WARNING

Do not turn ON the safety breaker until all work is
completed.

1

Interconnection between indoor unit and outdoor unit : when 
wire length exceeds 10 m, use Ø2.5 mm wires instead of 
Ø1.5 mm wires.

2

Power supply cable 
(refer to the unit nameplate for maximum running current)

3

Earth

4

Safety breaker

5

Earth leakage circuit breaker

9

10

11

1 2 3

L N

H05VV

2

1

4

5

3

50 Hz

230 V

1 2 3

9 10 11

Summary of Contents for Altherma ERYQ005ABV3

Page 1: ...INSTALLATION MANUAL ERYQ005ABV3 ERYQ006ABV3 ERYQ007ABV3 Outdoor unit for air to water heat pump ...

Page 2: ...e an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause terminal ove...

Page 3: ...o that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not annoy the ...

Page 4: ...een outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover 3 Stop...

Page 5: ...the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tight...

Page 6: ...ssure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers from t...

Page 7: ...imilar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system Wiring Procedure 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units so that the terminal numbers match see wiring diagram below Tighten the terminal screws securely We recommend a flathead s...

Page 8: ...urely 3 NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installations 1 Single core wire 2 Screw 3 Flat washer 1 Round crimp style terminal 2 Screw 3 Flat washer A A AA 2 3 1 1 3 2 3 3 2 1 1 B B L N 1 2 3 1 3 2 CAUTION 1 In case the use of stranded conductor wires is unavoidable for one reason or another make sure to install round crimp style termina...

Page 9: ...ocal and national legislation NOTE Remark that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the syst...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 3P177782 1B ...

Reviews: