ERYQ005~007ABV3

 

Outdoor unit for air to water heat pump

 

3P177782-1B

 

Installation manual

 

2

 

 

During installation, attach the refrigerant piping securely before
running the compressor.
If the compressor is not attached and the stop valve is open
during pump-down, air will be sucked in when the compressor is
running, causing abnormal pressure in the freezer cycle which
will lead to breakage and even to injury.

 

 

Be sure to establish an earth. Do not earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock. A high
surge current from lightning or other sources may
cause damage to the outdoor unit.

 

 

Be sure to install an earth leakage circuit breaker.
Failure to do so may cause electrical shock.

 

Cautions

 

 

Do not install the outdoor unit in a place where there is
danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may
catch fire.

 

 

Note for installing the outdoor unit.
In cold areas where the outside air temperature remains below
or around the freezing-point for a few days, the outdoor unit's
drain may freeze. If so, it is recommended to install a heater tape
in order to protect drain from freezing.

 

 

Tighten the flare nut according to the specified method such as
with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after
a long time and cause refrigerant leakage.

 

A

 

CCESSORIES

 

Accessories supplied with the outdoor unit:

 

I

 

NSTALLATION

 

 

 

GUIDELINES

 

Precautions for selecting the location

 

 

Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.

 

 

Choose a location where the hot air discharged from the unit or
the operation noise will not cause a nuisance to the neighbours
of the user.

 

 

Avoid places near a bedroom and the like, so that the operation
noise will cause no trouble.

 

 

There must be sufficient space for carrying the unit into and out
of the site.

 

 

There must be sufficient space for air passage and no
obstructions around the air inlet and the air outlet.

 

 

The site must be free from the possibility of flammable gas
leakage in a nearby place.

 

 

Locate the unit so that the noise and the discharged hot air will
not annoy the neighbours.

 

 

Install units, power cords and inter-unit cables at least 3 m away
from television and radio sets. This is to prevent interference to
images and sounds.

 

 

Depending on radio wave conditions, electromagnetic
interference may still occur even if installed more than 3 m away.

 

 

In coastal areas or other places with salty atmosphere of sulfate
gas, corrosion may shorten the life of the outdoor unit.

 

 

Since drain flows out of the outdoor unit, do not place anything
under the unit which must be kept away from moisture.

 

Selecting a location in cold climates

 

 

To  prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.

 

 

Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.

 

 

To  prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.

 

 

In heavy snowfall areas, select an installation site where the
snow will not affect the unit.

 

Drain plug
Included on the bottom of the packing case.

1

Installation manual

1

 

WARNING

 

 

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

 

 

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

 

NOTE

 

Units cannot be installed hanging from ceiling or
stacked.

 

CAUTION

 

When operating the outdoor unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.

 

Construct a large canopy.

Construct a pedestal.

Install the unit high enough off the ground 
to prevent burying in snow.

Summary of Contents for Altherma ERYQ005ABV3

Page 1: ...INSTALLATION MANUAL ERYQ005ABV3 ERYQ006ABV3 ERYQ007ABV3 Outdoor unit for air to water heat pump ...

Page 2: ...e an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause terminal ove...

Page 3: ...o that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not annoy the ...

Page 4: ...een outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover 3 Stop...

Page 5: ...the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tight...

Page 6: ...ssure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers from t...

Page 7: ...imilar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system Wiring Procedure 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units so that the terminal numbers match see wiring diagram below Tighten the terminal screws securely We recommend a flathead s...

Page 8: ...urely 3 NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installations 1 Single core wire 2 Screw 3 Flat washer 1 Round crimp style terminal 2 Screw 3 Flat washer A A AA 2 3 1 1 3 2 3 3 2 1 1 B B L N 1 2 3 1 3 2 CAUTION 1 In case the use of stranded conductor wires is unavoidable for one reason or another make sure to install round crimp style termina...

Page 9: ...ocal and national legislation NOTE Remark that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the syst...