background image

ERYQ005~007ABV3

Outdoor unit for air to water heat pump

3P177782-1B

Installation manual

8

T

EST

 

RUN

 

AND

 

FINAL

 

CHECK

Trial operation and testing

1

Measure the voltage at the primary side of the safety breaker.
Check that it is 230 V.

2

Carry out the test operation in accordance with the indoor
installation manual and operation manual to ensure that all
functions and parts are working properly.

Items to check

P

UMP

 

DOWN

 

OPERATION

In order to protect the environment, be sure to pump down when
relocating or disposing of the unit. The pump down operation will
extract all refrigerant from the piping into the outdoor unit.

Pump down procedure

1

Remove the valve lid from liquid stop valve and gas stop valve.

2

Carry out the forced cooling operation.

3

After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<–10°C)), close the liquid stop valve
with a hexagonal wrench.

4

After 2-3 minutes, close the gas stop valve and stop forced
cooling operation.

Forced cooling operation

1

Press the forced operation switch SW1 to begin forced cooling.

2

Press the forced operation switch SW1 again to stop forced
cooling.

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.

NOTE

Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

NOTE

The unit requires a small amount of power in
its standby mode. If the system is not to be
used for some time after installation, shut off
the circuit breaker to eliminate unnecessary
power consumption.

If the circuit breaker trips to shut off the
power to the outdoor unit, the system will
restore the original operation mode when the
power supply is restored.

Check

Symptom

Outdoor unit is installed properly 
on solid base.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes 
are thermally insulated.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for 
interconnecting wire connections.

Inoperative or burn damage

Outdoor unit air intake and 
exhaust is free of obstructions. 
Stop valves are opened.

Incomplete cooling/heating 
function

NOTE

Have the customer actually operate the unit while
looking at the manual included with the indoor unit.
Instruct the customer how to operate the unit correctly.

1

Gas stop valve

2

Close

3

Hexagonal wrench

4

Valve lid

5

Liquid stop valve

1

Forced operation switch SW1

1

3

2

4

4

5

LED-A

SW4

ON

AB

C

D

S102

SW1

S2

1

Summary of Contents for Altherma ERYQ005ABV3

Page 1: ...INSTALLATION MANUAL ERYQ005ABV3 ERYQ006ABV3 ERYQ007ABV3 Outdoor unit for air to water heat pump ...

Page 2: ...e an extension cord Do not put other loads on the power supply use a dedicated power circuit Failure to do so may cause abnormal heat electric shock or fire Use the specified types of wires for electrical connections between the indoor and outdoor unit Firmly clamp the interconnecting wires so that their terminals receive no external stress Incomplete connections or clamping may cause terminal ove...

Page 3: ...o that the operation noise will cause no trouble There must be sufficient space for carrying the unit into and out of the site There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet The site must be free from the possibility of flammable gas leakage in a nearby place Locate the unit so that the noise and the discharged hot air will not annoy the ...

Page 4: ...een outdoor unit and indoor unit 3 m Maximum allowable height difference between outdoor unit and indoor unit 15 m Additional refrigerant required for refrigerant pipe exceeding 10 m in length 20 g m Gas pipe outer diameter 15 9 mm 5 8 Liquid pipe outer diameter 6 4 mm 1 4 100 350 1200 50 50 350 100 100 350 50 1 Wrap the insulation pipe with finishing tape from bottom to top 2 Service cover 3 Stop...

Page 5: ...the flare nut from the stop valve and put the flare nut on the pipe 4 Flare the pipe Set exactly at the position shown below 5 Check that the flaring is properly made Connecting the refrigerant piping to the outdoor unit 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare use refrigeration oil for R410A 2 Align the centres of both flares and tight...

Page 6: ...ssure valve Lo and completely close its high pressure valve Hi The high pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1 MPa 760 mm Hg 4 Close the gauge manifold s low pressure valve Lo and stop the vacuum pump Leave as is for 4 5 minutes and make sure that the coupling meter needle does not go back 5 Remove the covers from t...

Page 7: ...imilar Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system Wiring Procedure 1 Strip the insulation from the wire 20 mm 2 Connect the connection wires between the indoor and outdoor units so that the terminal numbers match see wiring diagram below Tighten the terminal screws securely We recommend a flathead s...

Page 8: ...urely 3 NOTE This unit must be earthed For earthing follow the applicable local standard for electrical installations 1 Single core wire 2 Screw 3 Flat washer 1 Round crimp style terminal 2 Screw 3 Flat washer A A AA 2 3 1 1 3 2 3 3 2 1 1 B B L N 1 2 3 1 3 2 CAUTION 1 In case the use of stranded conductor wires is unavoidable for one reason or another make sure to install round crimp style termina...

Page 9: ...ocal and national legislation NOTE Remark that during the first running period of the unit required power input may be higher than stated on the nameplate of the unit This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the syst...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 3P177782 1B ...

Reviews: