8 Configuration
Installer reference guide
54
ERHQ+ERLQ011~016 + 16CBV
Daikin Altherma – Low temperature split
4P449970-1 – 2016.06
#
Code
Description
[A.2.1.9]
[F-0D]
<< continuation
▪ 1 (Sample)(default): The pump is ON
when there is heating demand and the
leaving water temperature has NOT
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 5 minutes to
check the water temperature and
demand
heating
if
necessary.
Remark:
Sample is NOT available in
external room thermostat control or
room thermostat control.
a
b
d
e
f
c
g
b
c
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
continued >>
#
Code
Description
[A.2.1.9]
[F-0D]
<< continuation
▪ 2 (Request): Pump operation based
on request.
Example:
Using a room
thermostat creates thermo ON/OFF
condition. When there is no such
demand, the pump is OFF.
Remark:
Request is NOT available in leaving
water temperature control.
a
d
e
b
b
c
b
c
c
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation
8.2.3
Quick wizard: Options
Domestic hot water settings
This chapter only applies if the optional domestic hot water tank is
installed.
INFORMATION
▪ If there is no optional backup heater installed, you must
install a domestic hot water tank ([E‑05]=1). Otherwise
an error code (UA-17) will occur.
▪ If domestic hot water tank EKHWS, EKHWE or
EKHWET is installed ([E‑07]=0), you must install a
domestic hot water pump ([D‑02]=3 or 4).
Following settings must be made accordingly.
#
Code
Description
[A.2.2.1]
[E-05]
DHW operation:
Can the system prepare domestic hot
water?
▪ 0 (No)(default): NOT installed.
▪ 1 (Yes): Installed.
[A.2.2.3]
[E-07]
During domestic hot water preparation,
the heat pump can be assisted by an
electrical heater to ensure the domestic
hot water preparation even for high
desired tank temperatures.
DHW tank type:
▪ 0 (Type 1)(default): Tank with anti-
legionella heater installed at the side
of the tank.
▪ 5 (Type 6): Tank with anti-legionella
heater installed at the top of the tank.
Range: 0~6. However, values 1~4 and 6
are not applicable for this setting. If the
setting is set to 6, an error code will
appear and the system will NOT operate.
[A.2.2.A]
[D-02]
The indoor unit offers the possibility to
connect a field supplied domestic hot
water pump (On/OFF type). Depending
on the installation and configuration on
the user interface, we distinguish its
functionality.
DHW pump:
▪ 0 (No)(default): NOT installed.
▪ 1 (Secondary rtrn): Installed for instant
hot water when water is tapped. The
end-user sets the operation timing
(weekly
schedule
time)
of
the
domestic hot water pump when it
should run. Control of this pump is
possible through the indoor unit.
▪ 2
(Disinf.
shunt):
Installed
for
disinfection.
It
runs
when
the
disinfection function of the domestic
hot water tank is running. No further
settings are needed.
▪ 3 (Circul. Pump): Installed for tank
preheating. Necessary for EHBH_CBV
without backup heater. It runs when
the domestic hot water tank is being
preheated. No further settings are
needed.
▪ 4 (CP & disinf. Sh): Combination of 2
and 3. It runs when the disinfection
function of the domestic hot water tank
is running, or when the domestic hot
water tank is being preheated. No
further settings are needed.
See also illustrations below.