Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.8
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
A.8
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
60
°C (*1)
65°C (*2)
A.8
[0-0D]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-01]
R/W
10~25°C, step: 1°C
15°C
A.8
[1-02]
R/W
[9-01]~[9-00], step: 1°C
35°C
A.8
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
A.8
[1-04]
1
A.8
[1-05]
1
A.8
[1-06]
20
A.8
[1-07]
35
A.8
[1-08]
22
A.8
[1-09]
18
A.8
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.8
[2-01]
R/W
0: No
1: Yes
A.8
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.8
[2-03]
R/W
55~80°C, step: 5°C
70°C
A.8
[2-04]
R/W
5~60 min, step: 5 min
10 min
A.8
[2-05]
R/W
4~16°C, step: 1°C
16°C
A.8
[2-06]
R/W
0: Disabled
1: Enabled
A.8
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[3-00]
R/W
0: No
1: Yes
A.8
[3-01]
0
A.8
[3-02]
1
A.8
[3-03]
4
A.8
[3-04]
2
A.8
[3-05]
1
A.8
[3-06]
R/W
18~30°C, step: A.3.2.4
30°C
A.8
[3-07]
R/W
12~18°C, step: A.3.2.4
12°C
A.8
[3-08]
35
A.8
[3-09]
15
A.8
[4-00]
R/W
0~2
0: Disabled
1: Enabled
A.8
[4-01]
R/W
0: None
1: BSH
2: BUH
A.8
[4-02]
R/W
14~35°C, step: 1°C
25°C (*3)
35°C (*4)
A.8
[4-03]
R/W
0: Limited
1: No limit
2: Most optimum
3: Optimum
4: Only legionella
A.8
[4-04]
2
A.8
[4-05]
0
A.8
[4-06]
0/1
A.8
[4-07]
R/W
0: No
1: Yes
A.8
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.8
[4-09]
R/W
0: Current
1: Power
A.8
[4-0A]
0
A.8
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
A.8
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
A.8
[4-0E]
R/W
0: No
1: Yes
A.8
[5-00]
R/W
0: Allowed
1: Not allowed
A.8
[5-01]
R/W
-15~35°C, step: 1°C
0°C
--
-- (Do not change this value)
Below which outdoor temperature is heating allowed?
Is the installer on site?
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
--
--
--
--
--
--
What is the averaging time for the outdoor temp?
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the disinfection target temperature?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Is auto restart of the unit allowed?
--
--
--
--
--
Operation permission of the booster heater.
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
--
--
What is the BUH operation mode?
Which electric heater has priority?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
What is the equilibrium temperature for the building?
Enable the second step of the backup heater?
Which power limitation mode is required on the system?
Which power limitation type is required?
--
(*1) EHBH*_(*2) EHVH*_
(*3) *04/08*_(*4) *11/16*