6 Preparation
Installer reference guide
24
ERHQ+ERLQ011~016 + 16CBV
Daikin Altherma – Low temperature split
4P449970-1 – 2016.06
a
b
c
b
a
Baffle plate
b
Prevailing wind direction
c
Air outlet
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging 10~43°C in cooling mode and –
25~25°C in heating mode.
6.2.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
INFORMATION
You can use the optional snow cover (EK016SNC).
a
b
c
c
d
a
Snow cover or shed
b
Pedestal (minimum height = 150 mm)
c
Prevailing wind direction
d
Air outlet
6.2.3
Installation site requirements of the
indoor unit
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Mind the measurement guidelines:
Maximum refrigerant piping length between indoor
unit and outdoor unit
ERHQ: 75 m
(95 m)
(a)
ERLQ: 50 m
(70 m)
(a)
Minimum refrigerant piping length between indoor
unit and outdoor unit
3 m
Maximum height difference between indoor unit and
outdoor unit
30 m
Maximum distance between the 3‑way valve and
the indoor unit (for installations with domestic hot
water tank)
3 m
Maximum distance between the domestic hot water
tank and the indoor unit (for installations with
domestic hot water tank)
10 m
(a)
Parenthesised figure represents the equivalent length.
▪ Mind the following spacing installation guidelines:
≥1
150
200
200
10
10
500
(mm)
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full
of water into account.
Make sure, in the event of a water leak, water cannot cause any
damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~35°C.
6.2.4
Installation site requirements of the
backup heater
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Mind the measurement guidelines:
Maximum distance between the backup heater and
the indoor unit
10 m
▪ Mind the following spacing installation guidelines: