7 Installation
Installer reference guide
43
ERHQ+ERLQ011~016 + 16CBV
Daikin Altherma – Low temperature split
4P449970-1 – 2016.06
d
b
a
V3
W1
e
h
f
d
g
e
h
f
g
c
c
a
Switch box
b
Stop valve attachment plate
c
Earth
d
Cable tie
e
Interconnection cable
f
Power supply cable
Only if bottom plate heater is installed (option for ERHQ):
g
Bottom plate heater cable
h
Power supply cable of the bottom plate heater (from the
indoor unit)
INFORMATION
ERLQ units control the bottom plate heater internally (field
wiring NOT required).
4
Fix the cables (power supply, interconnection cable and power
supply of the bottom plate heater (if applicable)) with a cable tie
to the stop valve attachment plate.
5
Route the wiring through the frame and connect it to it.
Routing through
the frame
Choose one of the 3 possibilities:
a
b
a
b
a
b
2
3
1
a
Power supply, earth wiring, and bottom
plate heater wire (if applicable)
b
Interconnection cable
Connecting to the
frame
When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
a b c
d
e
A B
A
Inside of the outdoor unit
B
Outside of the outdoor unit
a
Wire
b
Bush
c
Nut
d
Frame
e
Hose
6
Reattach the service cover. See
"7.11.2 To close the outdoor
unit" on page 49
.
7
Connect an earth leakage circuit breaker and fuse to the power
supply line.
7.10.7
To reposition the air thermistor on the
outdoor unit
This task is only required for ERLQ.
Required accessories:
Thermistor fixture.
Use the one from the accessory bag.
Thermistor fixing plate.
Reuse the one attached to the unit. If necessary,
you can use the spare one from the accessory
bag.
1
3
2
4
5