7 Electrical installation

Installation manual

14

3AMXF-A9, 3AMXF-A9, 3AMXM-N9

R32 Split series

3P600450-1R – 2022.05

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Use  the  GWP  value  mentioned  on  the  refrigerant  charge
label.

2

Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.

7

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

AC

DC

DC

S20

  S

21

  S

22

  S

23

S92

S93

S40

S80

S7

0

U

    

W

   

  V

D

C

-

FU2

S9

0

S2

4

AL2  AL1

e

f
g

h

a

b

c

d

DC(-)

FU2

a

AL1, AL2 - solenoid valve lead wire connector*

b

S20~24 - electronic expansion valve coil lead wire
connector (room A, B, C, D, E)*

c

S40 – thermal overload relay lead wire and high pressure
switch connector*

d

Multimeter (DC voltage range)

e

S90~93 – thermistor lead wire connector

f

S70 - fan motor lead wire connector

g

S80 - 4-way valve lead wire connector

h

Compressor lead wire connector

*May differ depending on the model.

7.1

Specifications of standard wiring
components

Component

Power supply
cable

Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire type

3- core cable 2.5 mm

2

H05RN-F (60245 IEC 57)

H07RN-F (60245 IEC 66)

3- core cable 4.0 mm

2

H07RN-F (60245 IEC 66)

Interconnection cable
(indoor↔outdoor)

4-core cable 1.5 mm

2

 or

2.5 mm

2

 and applicable for

220~240 V

H05RN-F (60245 IEC 57)

Recommended circuit breaker

20 A

Residual current device

MUST comply with

applicable legislation

Electrical  equipment  must  comply  with  EN/IEC  61000-3-12,  the
European/International  Technical  Standard  setting  the  limits  for
harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.

7.2

To connect the electrical wiring to
the outdoor unit

1

Remove the switch box cover (1 screw).

Summary of Contents for 3AMXM52N2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68A2V1B9...

Page 2: ...d til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vado...

Page 3: ...ila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuo...

Page 4: ...ions 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 as set out in A and judge...

Page 5: ...allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 41 7 35 63 8 R32 41 7 bar...

Page 6: ...re commissioning 17 10 2 Checklist during commissioning 17 10 3 Trial operation and testing 17 10 3 1 About wiring error check 17 10 3 2 To perform a test run 18 10 4 Starting up the outdoor unit 18 1...

Page 7: ...mage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit...

Page 8: ...ion devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Ma...

Page 9: ...1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a...

Page 10: ...em shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units NOTICE The piping and other pressure containing parts shall be sui...

Page 11: ...eration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 ref...

Page 12: ...CE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 5 3 Checking the refrigerant piping...

Page 13: ...ght and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer for more information 6 2 To de...

Page 14: ...by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacit...

Page 15: ...unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn OFF the power supply before servicing Install the switch b...

Page 16: ...on Setting it in the guest rooms is convenient 9 2 1 To set the priority room function 1 Remove the switch cover on the service PCB 2 Set the switch SW4 for the indoor unit for which you want to activ...

Page 17: ...pecified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and have NOT been bypassed Check if ma...

Page 18: ...ling operation 4 When test run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C INFORMATION Test run can be disabled if necessary After the unit is tur...

Page 19: ...onnector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting di...

Page 20: ...6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 15 9CuT d e f k a b c g i j d r A r B r C s t s t s t r A r B r C s t s t s t u u u d p o o n l l m l w x v A v B v C v A...

Page 21: ...nual 21 3AMXF A9 3AMXF A9 3AMXM N9 R32 Split series 3P600450 1R 2022 05 h Distributor r Electronic expansion valve Refrigerant flow cooling i Muffler with filter s Thermistor liquid Refrigerant flow h...

Page 22: ......

Page 23: ......

Page 24: ...3P600450 1R 2022 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Reviews: