background image

5 Piping installation

Installation manual

12

3AMXF-A9, 3AMXF-A9, 3AMXM-N9

R32 Split series

3P600450-1R – 2022.05

e

Inter-unit piping

▪ Connecting a Ø9.5 mm pipe to a Ø12.7 mm gas pipe connection

port

a

b

d

e

c

a

Outdoor unit connection port

b

Reducer no. 2

c

Reducer no. 4

d

Flare nut for Ø12.7 mm

e

Inter-unit piping

Coat the threaded connection port of the outdoor unit where the flare
nut comes in with refrigeration oil.

Flare nut for (mm)

Tightening torque (N•m)

Ø9.5

33~39

Ø12.7

50~60

Ø15.9

62~75

NOTICE

Use  an  appropriate  wrench  to  avoid  damaging  the
connection  thread  by  overtightening  the  flare  nut.  Be
careful NOT to overtighten the nut, or the smaller pipe may
be damaged (about 2/3-1× the normal torque).

5.2.2

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

NOTICE

▪ Use the flare nut fixed to the main unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the  inside  of  the  flare.  Use  refrigeration  oil  for  R32
(FW68DA).

▪ Do NOT reuse joints.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

c

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

5.3

Checking the refrigerant piping

5.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

ALWAYS  use  a  recommended  bubble  test  solution  from
your wholesaler.

NEVER use soap water:

▪ Soap  water  may  cause  cracking  of  components,  such

as flare nuts or stop valve caps.

▪ Soap  water  may  contain  salt,  which  absorbs  moisture

that will freeze when the piping gets cold.

▪ Soap  water  contains  ammonia  which  may  lead  to

corrosion  of  flared  joints  (between  the  brass  flare  nut
and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT open the stop valves before the vacuum drying is
finished.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Be sure to open the gas stop valve after piping installation
and vacuuming. Running the system with the valve closed,
the compressor may break down.

Summary of Contents for 3AMXM52N2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68A2V1B9...

Page 2: ...d til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vado...

Page 3: ...ila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuo...

Page 4: ...ions 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 as set out in A and judge...

Page 5: ...allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 41 7 35 63 8 R32 41 7 bar...

Page 6: ...re commissioning 17 10 2 Checklist during commissioning 17 10 3 Trial operation and testing 17 10 3 1 About wiring error check 17 10 3 2 To perform a test run 18 10 4 Starting up the outdoor unit 18 1...

Page 7: ...mage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit...

Page 8: ...ion devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Ma...

Page 9: ...1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a...

Page 10: ...em shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units NOTICE The piping and other pressure containing parts shall be sui...

Page 11: ...eration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 ref...

Page 12: ...CE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 5 3 Checking the refrigerant piping...

Page 13: ...ght and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer for more information 6 2 To de...

Page 14: ...by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacit...

Page 15: ...unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn OFF the power supply before servicing Install the switch b...

Page 16: ...on Setting it in the guest rooms is convenient 9 2 1 To set the priority room function 1 Remove the switch cover on the service PCB 2 Set the switch SW4 for the indoor unit for which you want to activ...

Page 17: ...pecified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and have NOT been bypassed Check if ma...

Page 18: ...ling operation 4 When test run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C INFORMATION Test run can be disabled if necessary After the unit is tur...

Page 19: ...onnector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting di...

Page 20: ...6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 15 9CuT d e f k a b c g i j d r A r B r C s t s t s t r A r B r C s t s t s t u u u d p o o n l l m l w x v A v B v C v A...

Page 21: ...nual 21 3AMXF A9 3AMXF A9 3AMXM N9 R32 Split series 3P600450 1R 2022 05 h Distributor r Electronic expansion valve Refrigerant flow cooling i Muffler with filter s Thermistor liquid Refrigerant flow h...

Page 22: ......

Page 23: ......

Page 24: ...3P600450 1R 2022 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Reviews: