5 Piping installation

Installation manual

10

3AMXF-A9, 3AMXF-A9, 3AMXM-N9

R32 Split series

3P600450-1R – 2022.05

(mm)

353

600

240

240

a

a

100 mm above expected level of snow

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(large,  small)  with  the  outdoor  unit.  Take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

NOTICE

If  the  drain  holes  of  the  outdoor  unit  are  blocked  up  by  a
mounting base or floor surface, place additional foot bases
≤30 mm under the outdoor unit's feet.

▪ Use a drain socket for drainage if necessary.

a

a

Drain hole

To close the drain holes and attach the drain
socket

1

Install  drain  caps  (accessory  f)  and  (accessory  g).  Make  sure
the edges of the drain caps close off the holes completely.

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (large).

b

Drain hole. Install a drain cap (small).

c

Drain hole for drain socket

5

Piping installation

5.1

Preparing refrigerant piping

5.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Liquid piping

Gas piping

3× Ø6.4 mm (1/4")

1× Ø9.5 mm (3/8")

2× Ø12.7 mm (1/2")

INFORMATION

Usage  of  reducers  might  be  required  based  on  the  indoor
unit.  See 

"5.2.1  Connections  between  outdoor  and  indoor

unit using reducers"

 [

4

 11] for more information.

Refrigerant piping material

Piping material:

 phosphoric acid deoxidised seamless copper

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

5.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Summary of Contents for 3AMXM52N2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 3AMXM52N2V1B9 3AMXF52A2V1B9 3MXF52A2V1B9 3MXF68A2V1B9...

Page 2: ...d til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vado...

Page 3: ...ila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuo...

Page 4: ...ions 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 as set out in A and judge...

Page 5: ...allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 41 7 35 63 8 R32 41 7 bar...

Page 6: ...re commissioning 17 10 2 Checklist during commissioning 17 10 3 Trial operation and testing 17 10 3 1 About wiring error check 17 10 3 2 To perform a test run 18 10 4 Starting up the outdoor unit 18 1...

Page 7: ...mage and even injury CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit...

Page 8: ...ion devices of the unit Do NOT touch live parts for 10 minutes after the power supply is turned off because of high voltage risk Please note that some sections of the electric component box are hot Ma...

Page 9: ...1 2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up a b c c d a...

Page 10: ...em shall be made with permanent joints when inside an occupied space except joints directly connecting the piping to the indoor units NOTICE The piping and other pressure containing parts shall be sui...

Page 11: ...eration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces non permanent joints are NOT allowed for R32 ref...

Page 12: ...CE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 5 3 Checking the refrigerant piping...

Page 13: ...ght and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Contact your installer for more information 6 2 To de...

Page 14: ...by the power supply Do NOT touch them with bare hands DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacit...

Page 15: ...unit installation 8 1 To finish the outdoor unit installation DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn OFF the power supply before servicing Install the switch b...

Page 16: ...on Setting it in the guest rooms is convenient 9 2 1 To set the priority room function 1 Remove the switch cover on the service PCB 2 Set the switch SW4 for the indoor unit for which you want to activ...

Page 17: ...pecified wires are used for the interconnection cable The fuses circuit breakers or locally installed protection devices are installed according to this document and have NOT been bypassed Check if ma...

Page 18: ...ling operation 4 When test run is finished set the temperature to a normal level In cooling mode 26 28 C in heating mode 20 24 C INFORMATION Test run can be disabled if necessary After the unit is tur...

Page 19: ...onnector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting di...

Page 20: ...6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 15 9CuT d e f k a b c g i j d r A r B r C s t s t s t r A r B r C s t s t s t u u u d p o o n l l m l w x v A v B v C v A...

Page 21: ...nual 21 3AMXF A9 3AMXF A9 3AMXM N9 R32 Split series 3P600450 1R 2022 05 h Distributor r Electronic expansion valve Refrigerant flow cooling i Muffler with filter s Thermistor liquid Refrigerant flow h...

Page 22: ......

Page 23: ......

Page 24: ...3P600450 1R 2022 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...

Reviews: