background image

8

English

Refrigerant Piping Work

4.

Purging air and checking gas leakage

WARNING

• Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Be sure to check for gas leaks.
• During tests never pressurize the appliances with a pressure higher than the maximum allowable pressure (as indicated on the 

nameplate of the unit).

• Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.

• When piping work is completed, it is necessary to purge the air and check for gas leakage.
• Be sure to perform vacuum pumping for all the rooms at the same time.
• Be sure to use the special tools for the R32 (gauge manifold, charge hose, vacuum pump, vacuum pump adapter, etc.).
• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque. 

1) Connect the charge hose protrusions (the side for pushing the pin) for low pressure and high pressure on the gauge manifold to 

the gas stop valve service port for rooms 

A and B

.

2) Fully open gauge manifold’s low-pressure valve (Lo) and high-pressure valve (Hi).

3) Apply vacuum pumping for 20 minutes or longer. Check that the compound pressure gauge reads –0.1MPa (–76cmHg).

4) After checking the vacuum, close the low pressure and high pressure valves on the gauge manifold and stop the vacuum 

pump. (Leave as is for 4-5 minutes and make sure the coupling meter needle does not go back. ) If it does go back, this may 
indicate the presence of moisture or leaking from connecting parts.
After inspecting all the connection and loosening then retightening the nuts, repeat steps 2)

 →

 3)

 →

 4).

5) Remove the valve caps on the liquid and gas stop valves at the pipes for rooms A and B.

6) Open the valve rods on the liquid stop valves for rooms A and B by turning them 90° counterclockwise using a hex wrench. 

Close them 5 seconds later and check for gas leaks.
After checking for gas leaks, check the areas around flares on the indoor unit, and the areas around flares and valve rods on 
the outdoor unit by applying soapy water.
Wipe down thoroughly after the check is complete.

7) Remove the charge hose from the gas stop valve service ports at the pipes for rooms A and B and completely open the liquid 

and gas stop valves at the pipes for rooms A and B. 
(Stop the valve rods as far as they go and do not attempt to turn them any further.)

8) Use a torque wrench to tighten the valve caps and service port caps on the liquid and gas stop valves at the pipes for rooms A 

and B to the designated torque.

Room B gas 
stop valve

Room B liquid 
stop valve

Room A gas 
stop valve

Room A liquid 
stop valve

Valve cap

Service port

Compound 
gauge

Gauge manifold

Low-pressure valve

High-pressure valve

Charge hose

Vacuum pump

Vacuum pump adapter

3PEN423316-2K.book  Page 8  Monday, May 15, 2017  1:15 PM

Summary of Contents for 2MXM40M3V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M3V1B 2MXM50M2V1B9 2AMXM40M3V1B 2AMXM50M3V1B 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 2: ...ositivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...tygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i...

Page 4: ...lastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas...

Page 5: ...nnections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the c...

Page 6: ...ep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended...

Page 7: ...e more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since water will...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...0 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer pack...

Page 10: ...e piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher...

Page 11: ...been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the applicable standard...

Page 12: ...nd pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make su...

Page 13: ...arge label supplied with the product Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...erform the test operation with the operation mode set to cooling For the test operation procedure read the installation manual attached to the indoor unit and the manual of the remote controller Force...

Page 16: ...ded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and s...

Page 17: ...ng thermistor is subject to power supply voltage 2 Reconnecting after check When reconnecting be sure to reconnect everything the same way as it was before LED A MULTIMETER DC VOLTAGE RANGE DB1 AC DC...

Page 18: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 19: ...n the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of the PCB inside 4 Go back t...

Page 20: ...nit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity saving function works on the following indoor units...

Page 21: ...correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not...

Page 22: ...e thermistor Propeller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT...

Page 23: ...3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 24: ...3P423316 2K 2017 04 Copyright 2017 Daikin 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Reviews: