Trial Operation and Testing

• Before starting the test run, measure the voltage at the primary side of the safety breaker. 
• Check that all liquid and gas stop valves are fully open.
• Check that piping and wiring all match.
• Initialization of the Multi system can take several minutes depending on the number of indoor units and options used.

1.

Trial operation and testing

1) To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room 

temperature, only heating or cooling (but not both) may be possible.)

2) After the unit is stopped, it will not start again (heating or cooling) for approximately 3 minutes.
3) During the test run, first check the operation of each unit individually. Then also check the simultaneous operation of 

all indoor units.
Check both heating and cooling operation.

4) After running the unit for approximately 20 minutes, measure the temperatures at the indoor unit inlet and outlet. If the 

measurements are above the values shown in the table below, then they are normal.

(When running in one room)

5) During cooling operation, frost may form on the gas stop valve or other parts. This is normal.
6) Operate the indoor units in accordance with the included operation manual. Check that they operate normally.

2.

Fault diagnosis by LED on outdoor unit PCB.

3.

Items to check 

ATTENTION

• Have the customer actually operate the unit while looking at the manual included with the indoor unit. Instruct the customer 

how to operate the unit correctly (particularly cleaning of the air filters, operation procedures, and temperature adjustment).

• Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit 

soon after it is installed, turn off the breaker to avoid wasting electricity.

• If additional refrigerant has been charged because of long piping, list the amount added on the nameplate on the reverse side 

of the stop valve cover.

Cooling

Heating

Temperature difference 
between inlet and outlet

Approx. 8

°

C

Approx. 15

°

C

Diagnosis

LED is flashing

Normal -> check the indoor unit

LED is ON

Turn the power OFF and then ON again. 
If the LED display recurs, the outdoor unit PCB is faulty.

LED is OFF

Power supply fault or turn the power OFF and then ON again. 
If the LED display recurs, the outdoor unit PCB is faulty.

Check item

Consequences of trouble

Check

Are the indoor units installed securely?

Falling, vibration, noise

Has an inspection been made to check for gas leakage?

No cooling, no heating

Has complete thermal insulation been done (gas pipes, liquid 
pipes, indoor portions of the drain hose extension)?

Water leakage

Is the drainage secure?

Water leakage

Are the ground wire connections secure?

Danger in the event of a ground fault

Are the electric wires connected correctly?

No cooling, no heating

Is the wiring in accordance with the specifications?

Operation failure, burning

Are the inlets/outlets of the indoor and outdoor units free of any 
obstructions?

No cooling, no heating

Are the stop valves open?

No cooling, no heating

Do the marks match (room A, room B) on the wiring and piping 
for each indoor unit?

No cooling, no heating

3PEN423316-2K.book  Page 17  Monday, May 15, 2017  1:15 PM

Summary of Contents for 2MXM40M3V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M3V1B 2MXM50M2V1B9 2AMXM40M3V1B 2AMXM50M3V1B 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 2: ...ositivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...tygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i...

Page 4: ...lastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas...

Page 5: ...nnections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the c...

Page 6: ...ep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended...

Page 7: ...e more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since water will...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...0 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer pack...

Page 10: ...e piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher...

Page 11: ...been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the applicable standard...

Page 12: ...nd pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make su...

Page 13: ...arge label supplied with the product Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...erform the test operation with the operation mode set to cooling For the test operation procedure read the installation manual attached to the indoor unit and the manual of the remote controller Force...

Page 16: ...ded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and s...

Page 17: ...ng thermistor is subject to power supply voltage 2 Reconnecting after check When reconnecting be sure to reconnect everything the same way as it was before LED A MULTIMETER DC VOLTAGE RANGE DB1 AC DC...

Page 18: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 19: ...n the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of the PCB inside 4 Go back t...

Page 20: ...nit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity saving function works on the following indoor units...

Page 21: ...correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not...

Page 22: ...e thermistor Propeller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT...

Page 23: ...3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 24: ...3P423316 2K 2017 04 Copyright 2017 Daikin 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Reviews: