Refrigerant Piping Work

5.

Charging refrigerant

1-1. Charging additional refrigerant

• If the total length of refrigerant piping exceeds 20m, add refrigerant. (The maximum total length of refrigerant piping for all 

rooms is 30m.) 

A: Amount to add
B: Length of refrigerant piping minus 20. (Total for all rooms)

1-2. Completely recharging refrigerant

• The total amount that must be added is the amount listed on the machine nameplate and the amount of the additional 

refrigerant.

 CAUTION

• Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long 

period of time.

• Do not overfill with refrigerant. This will break the compressor.

Precautions for compressor

WARNING

Electric shock hazard 

• Use this compressor on a grounded system only.
• Turn power OFF before servicing.
• Replace terminal cover before applying power.

Injury hazard

• Wear protective goggles.

Explosion or fire hazard

• Use tubing cutter to remove compressor.
• Do NOT use torch. System contains refrigerant under pressure.
• Do NOT drive under air or vacuum condition.
• Use only approved refrigerants and lubricants.

Burn hazard 

• Do NOT touch with bare hands during or immediately following operation.

g=20X

A

B

6

5

Please fill in with indelible ink, 

  the factory refrigerant charge of the product, 

tCO

2

eq calculation according to the formula (rounded up 

to 2 decimal places)

  the additional refrigerant amount charged in the field and

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases. 
Do not vent gases into the atmosphere.

Refrigerant type:
GWP

 value:

factory refrigerant charge of the 
product: 
see unit name plate 

additional refrigerant amount 
charged in the field 

total refrigerant charge 

greenhouse gas emissions

 of the 

total refrigerant charge expressed 
as tonnes CO

2

-equivalent 

outdoor unit

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port 
(e.g. onto the inside of the stop valve cover).

GWP = global warming potential 

(1)

(1)

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

1000

GWP × kg

=

=

+

kg

=

kg

=

GWP: 675

675

R32

R32

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. 
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.

NOTICE

In Europe, the 

greenhouse gas emissions 

of the total refrigerant charge in the system (expressed as tonnes CO

-equivalent) 

is  used  to  determine  the  maintenance intervals. Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000

Use the GWP value mentioned on the refrigerant charge label. This GWP value is based on the 4th IPCC 

Assessment 

Report.  The  GWP  value  mentioned  in  the manual might be outdated (i.e., based on the 3rd IPCC Assessment Report).

3PEN423316-2K.book  Page 9  Monday, May 15, 2017  1:15 PM

Summary of Contents for 2MXM40M3V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M3V1B 2MXM50M2V1B9 2AMXM40M3V1B 2AMXM50M3V1B 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 2: ...ositivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...tygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i...

Page 4: ...lastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas...

Page 5: ...nnections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the c...

Page 6: ...ep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended...

Page 7: ...e more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since water will...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...0 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer pack...

Page 10: ...e piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher...

Page 11: ...been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the applicable standard...

Page 12: ...nd pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make su...

Page 13: ...arge label supplied with the product Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...erform the test operation with the operation mode set to cooling For the test operation procedure read the installation manual attached to the indoor unit and the manual of the remote controller Force...

Page 16: ...ded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and s...

Page 17: ...ng thermistor is subject to power supply voltage 2 Reconnecting after check When reconnecting be sure to reconnect everything the same way as it was before LED A MULTIMETER DC VOLTAGE RANGE DB1 AC DC...

Page 18: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 19: ...n the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of the PCB inside 4 Go back t...

Page 20: ...nit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity saving function works on the following indoor units...

Page 21: ...correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not...

Page 22: ...e thermistor Propeller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT...

Page 23: ...3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 24: ...3P423316 2K 2017 04 Copyright 2017 Daikin 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Reviews: