background image

English

11

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve caps on the liquid and the gas stop valves at the pipes for rooms A 

and B. 

2) Run the unit on forced cooling. (Refer to the instructions below.)
3) After 5 to 10 minutes, close the liquid stop valves at the pipes for rooms A and B 

using a hex wrench.

4) After 2 to 3 minutes, stop the forced cooling operation as quickly as possible after the 

gas stop valves at the pipes for rooms A and B have been shut off.

5) Turn the power breaker off. 

 CAUTION

Run the air conditioner to cool both rooms A and B when performing a pump down.

1.

Forced cooling operation

1-1. Using the indoor unit start/stop button.

1) Press the start/stop button on the indoor unit in either room A or B for 5 seconds continuously.

The units in both rooms will start.

2) Forced cooling operation will end after around 15 minutes and the unit will stop automatically. Press the start/stop 

button on the indoor unit to force the operation to stop.

1-2. Using the indoor unit’s remote controller

Perform the test operation with the operation mode set to cooling. For the test operation procedure read the installation 
manual attached to the indoor unit and the manual of the remote controller.
•  Forced cooling operation will stop automatically after around 30 minutes.
To stop the operation, press the ON/OFF button.

 CAUTION

If the outside temperature is -10°C or lower, the safety device might start, preventing operation. In this situation, warm the out-
side temperature thermistor on the outdoor unit to -10°C or warmer. Operation will start.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

 WARNING

The unit is accompanied with the label below. Please read the following instructions carefully.

WARNING

1)

2)

3)

4)

5)

•  When the refrigeration circuit has a leak, do not execute pump down with the compressor.
•  Use recovery system into separate cylinder.
•  Warning, explosive hazard exists when executing pump down.
•  Pump down with compressor can lead to self-combustion due to air entering during pump 

down.

Used symbols:

1)

 Warning sign (ISO 7010 – W001)

2)

 Warning, Explosive material (ISO 7010 – W002)

3)

 Read Operator’s manual (ISO 7000 – 0790)

4)

 Operator’s manual; operating instructions (ISO 7000 – 1641)

5)

 Service indicator; read technical manual (ISO 7000 – 1659)

3PEN423316-2K.book  Page 11  Monday, May 15, 2017  1:15 PM

Summary of Contents for 2MXM40M3V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models 2MXM40M3V1B 2MXM50M2V1B9 2AMXM40M3V1B 2AMXM50M3V1B 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 2: ...ositivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo...

Page 3: ...tygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i...

Page 4: ...lastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas...

Page 5: ...nnections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the c...

Page 6: ...ep the area around the unit clean The temperature of refrigerant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended...

Page 7: ...e more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since water will...

Page 8: ...prevent air from getting in between the copper piping and the insulation tube Be sure to do this if the outdoor unit is installed above Cut thermal insulation pipe to an appropriate length and wrap it...

Page 9: ...0 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer pack...

Page 10: ...e piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher...

Page 11: ...been used once already Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislation In Europe the EN378 is the applicable standard...

Page 12: ...nd pressure gauge reads 0 1MPa 76cmHg 4 After checking the vacuum close the low pressure and high pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make su...

Page 13: ...arge label supplied with the product Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP...

Page 14: ...e WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous instal...

Page 15: ...erform the test operation with the operation mode set to cooling For the test operation procedure read the installation manual attached to the indoor unit and the manual of the remote controller Force...

Page 16: ...ded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and s...

Page 17: ...ng thermistor is subject to power supply voltage 2 Reconnecting after check When reconnecting be sure to reconnect everything the same way as it was before LED A MULTIMETER DC VOLTAGE RANGE DB1 AC DC...

Page 18: ...STOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT...

Page 19: ...n the side and remove the top plate of the outdoor unit 2 Remove the electric box cover by sliding it being careful not to bend the electric box hook 3 Cut the jumper J23 of the PCB inside 4 Go back t...

Page 20: ...nit and sets the indoor unit into standby electricity saving mode thus reducing the power consumption of the air conditioner The standby electricity saving function works on the following indoor units...

Page 21: ...correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not...

Page 22: ...e thermistor Propeller fan ON heating Muffler 9 5CuT 9 5CuT 9 5CuT Branch pipe Muffler Gas stop valve Muffler Gas stop valve 9 5CuT 9 5CuT Thermistor gas Thermistor liquid Thermistor gas 6 4CuT 6 4CuT...

Page 23: ...3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Page 24: ...3P423316 2K 2017 04 Copyright 2017 Daikin 3PEN423316 2K book Page 1 Monday May 15 2017 1 15 PM...

Reviews: