C-Series

[Applied Models]

z

Inverter Multi : Cooling Only

z

Inverter Multi : Heat Pump 

Si12 - 411A

Summary of Contents for 2MKD58BVM

Page 1: ...C Series Applied Models zInverter Multi Cooling Only zInverter Multi Heat Pump Si12 411A ...

Page 2: ...M 4MKD90BVMA 4MKS58BVMB 8 3MKD75BVM 4MKS75BVMB 4MKD75BVM 4MKS90BVMB 4MKD90BVM zHeat Pump Indoor Unit FTXE25BVMA FTXS20CVMB 9 FLXS25BVMB FTXS25BVMA FTXE35BVMA FTXS25CVMB 9 8 FLXS35BVMB FTXS35BVMA FTXD50BVMA FTXS35CVMB 9 8 FLXS50BVMB FTXS50BVMA 8 FTXD60BVMA FTXS50BVMB FLXS60BVMB FTXS60BVMA 8 FTXD71BVMA FTXS60BVMB FVXS25BVMB FTXS71BVMA 8 CDXD25CVMA FTXS71BVMB FVXS35BVMB CDXS25CVMA CDXD35CVMA ATXS20CV...

Page 3: ...r Standing Type 66 1 6 Outdoor Units 69 Part 4 Function and Control 71 1 Main Functions 72 1 1 Frequency Principle 72 1 2 Power Airflow Dual Flaps Wide Angle Louvers and Auto Swing 74 1 3 Fan Speed Control for Indoor Units 75 1 4 Programme Dry Function 76 1 5 Automatic Operation 77 1 6 Night Set Mode 78 1 7 Intelligent Eye 79 1 8 Home Leave Operation 81 1 9 Inverter Powerful Operation 82 1 10 Othe...

Page 4: ... and Cleaning 149 2 14 Troubleshooting 159 Part 6 Service Diagnosis 163 1 Caution for Diagnosis 164 1 1 Troubleshooting with the Operation Lamp 164 2 Problem Symptoms and Measures 166 3 Service Check Function 167 4 Code Indication on the Remote Controller 168 4 1 Error Codes and Description of Fault 168 5 Troubleshooting 169 5 1 Indoor Units 169 5 2 Outdoor Units 170 5 3 Indoor Unit PCB Abnormalit...

Page 5: ...n Motor 232 1 6 Removal of Electronic Expansion Valve and Thermistor 234 1 7 Removal of Sound Insulation and Reactor 235 1 8 Removal of Shunt 237 1 9 Removal of Solenoid Valve and Four Way Valve 238 1 10 Removal of Compressor 240 2 Outdoor Unit 50 52 58 68 75 Class 242 2 1 Removal of Outer Panels 242 2 2 Removal of Electrical BOX 243 2 3 Removal of PCB 247 2 4 Removal of Fan Motor 250 2 5 Removal ...

Page 6: ...Si12 411A Table of Contents v Index i Drawings Flow Charts v ...

Page 7: ...Si12 411A vi Table of Contents ...

Page 8: ... plug socket before disassembling the equipment for a repair Working on the equipment that is connected to a power supply can cause an electrical shook If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits do not touch any electrically charged sections of the equipment If the refrigerant gas discharges during the repair work do not touch the dischargi...

Page 9: ...se the welder in a well ventilated place Using the welder in an enclosed room can cause oxygen deficiency Warning Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work Never attempt to modify the equipment The use of inappropriate parts or tools can cause an electrical shock excessive heat generation or fire When relocating the e...

Page 10: ...as leaks be sure to locate the leak and repair it before charging the refrigerant After charging refrigerant make sure that there is no refrigerant leak If the leak cannot be located and the repair work must be stopped be sure to perform pump down and close the service valve to prevent the refrigerant gas from leaking into the room The refrigerant gas itself is harmless but it can generate toxic g...

Page 11: ... and repair it if the equipment is not properly grounded Improper grounding can cause an electrical shock Be sure to measure the insulation resistance after the repair and make sure that the resistance is 1 Mohm or higher Faulty insulation can cause an electrical shock Be sure to check the drainage of the indoor unit after the repair Faulty drainage can cause the water to enter the room and wet th...

Page 12: ...Si12 411A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 1 1 Cooling Only Models 2 1 2 Heat Pump Models 8 ...

Page 13: ...Reliability Durability Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode ...

Page 14: ...ility Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ce...

Page 15: ... Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Appl...

Page 16: ...wer Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Application Outdoor U...

Page 17: ...rability Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High...

Page 18: ...e Reliability Durability Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mod...

Page 19: ...ty Durability Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic...

Page 20: ...er Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 1 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Application Outdoor ...

Page 21: ...rability Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High...

Page 22: ...ility Auto Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 1 1 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic Hig...

Page 23: ...ilure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow 3 Step Airflow H P Only Wiring Error Check Comfort Control Auto Fan Speed Anticorrosion Treatment of Outdoor Heat Exchanger Indoor Unit Silent Operation Flexibility Multi Split Split Type Compatible Indoor Unit Night Quiet Mode Automatic Flexible Voltage Correspondence Outdoor Unit Silent Operation Manual Hig...

Page 24: ...e Reliability Durability Auto Restart after Power Failure 3 D Airflow Self Diagnosis Digital LED Display 3 Step Airflow H P Only Wiring Error Check Comfort Control Auto Fan Speed Anticorrosion Treatment of Outdoor Heat Exchanger Indoor Unit Silent Operation Night Quiet Mode Automatic Flexibility Multi Split Split Type Compatible Indoor Unit Outdoor Unit Silent Operation Manual Intelligent Eye Flex...

Page 25: ...to Restart after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Ap...

Page 26: ...wer Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 1 1 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Application Outdo...

Page 27: ...art after Power Failure Horizontal Auto Swing Right and Left Self Diagnosis Digital LED Display 3 D Airflow Wiring Error Check 3 Step Airflow H P Only Anticorrosion Treatment of Outdoor Heat Exchanger Comfort Control Auto Fan Speed Flexibility Multi Split Split Type Compatible Indoor Unit Indoor Unit Silent Operation Flexible Voltage Correspondence Night Quiet Mode Automatic High Ceiling Applicati...

Page 28: ...Si12 411A Specifications 17 Part 2 Specifications 1 Specifications 18 1 1 Indoor Units Cooling Only 18 1 2 Outdoor Units Cooling Only 30 1 3 Indoor Units Heat Pump 36 1 4 Outdoor Units Heat Pump 51 ...

Page 29: ...Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm φ18 0 φ18 0 Drawing No 3D040693 3D040694 Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FTKD50BVM FTKD60BVM Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 16 8 593 17 5 618 M 14 0 494 14 6 515 L 11 8 417 12 2 431 SL 10 4 367 ...

Page 30: ...d Air Filter Removable Washable Mildew Proof Running Current Rated A 0 23 0 22 0 21 0 23 0 22 Power Consumption Rated W 50 Power Factor 98 8 98 8 99 2 98 8 98 8 Temperature Control Microcomputer Control Dimensions H W D mm 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 Weight kg 12 Gross Weight kg 17 Operation Sound H M L SL dBA 46 42 37 34 Heat Insulation Both Liquid and Gas Pipes Pipin...

Page 31: ...es Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm φ18 0 φ18 0 Drawing No 3D040697 3D040698 Model FTKD50BVMA FTKD60BVMA Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 16 8 593 17 5 618 M 14 0 494 14 6 515 L 11 8 417 12 2 431 SL 10 4 367 10 8 381 Fan Type Cross Flow Fan Cross Flow Fan Motor Output W 43 43 Speed Steps 5 Steps Silen...

Page 32: ...d Air Filter Removable Washable Mildew Proof Running Current Rated A 0 23 0 22 0 21 0 23 0 22 Power Consumption Rated W 50 Power Factor 98 8 98 8 99 2 98 8 98 8 Temperature Control Microcomputer Control Dimensions H W D mm 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 Weight kg 12 Gross Weight kg 17 Operation Sound H M L SL dBA 46 42 37 34 Heat Insulation Both Liquid and Gas Pipes Pipin...

Page 33: ...tion Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D044242B 3D044243B Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FTKS35CVMB 9 8 FTKS50BVMB Rated Capacity 3 5kW Class 5 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 7 7 272 11 4 402 M 6 0 212 9 7 342 L 4 4 155 8 0 282 SL 3 8 134 7 1 251 Fan Type Cross Flow Fan Cross Flow Fan ...

Page 34: ...le Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 20 Power Consumption Rated W 40 45 Power Factor 96 6 96 4 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D mm 290 1 050 238 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 337 1 147 366 Weight kg 12 12 Gross Weight kg 17 17 Operation Sound H M L SL dBA 45 41 36 33 46 42 ...

Page 35: ... 33 31 29 35 33 31 29 External Static Pressure Pa 40 40 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046077A 3D046078A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model CDKD50CVM CDKD60CVM Rated Capacity 5 0kW Class 6 0kW Class Fro...

Page 36: ...35 33 31 29 External Static Pressure Pa 40 40 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046073A 3D046074A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model CDKD50CVMA CDKD60CVMA Rated Capacity 5 0kW Class 6 0kW Class Front Panel...

Page 37: ...9 External Static Pressure Pa 40 40 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046065A 3D046066A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model CDKS50CVMB CDKS60CVMB Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color Air...

Page 38: ...d Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm φ18 0 φ18 0 Drawing No 3D036717 3D036718 Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FLK50AVMA FLK60AVMA Rated Capacity 5 0W Class 5 7kW Class Front Panel Color Almond White Almond White Air Flow Rates m min cfm H 11 4 402 12 0 424 M 10 0 353 10 6 374 L 8 5 300 9 3 328 SL 7 5 265 8 3 293 Fan Ty...

Page 39: ...on Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D040166A 3D040167A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FLKS50BVMB FLKS60BVMB Rated Capacity 5 0W Class 5 7kW Class Front Panel Color Almond White Almond White Air Flow Rates m min cfm H 11 4 402 12 0 424 M 10 0 353 10 7 378 L 8 5 300 9 3 328 SL 7 5 265 8 3 293 Fan Type Sirocco Fan Sirocco ...

Page 40: ...9 Operation Sound H M L SL dBA 38 32 26 23 39 33 27 24 Sound Power H dBA 54 55 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D040164A 3D040165A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FVKS50BVMB Rated Capacity 5 0kW Class Front Panel Color Almond White Air ...

Page 41: ...ting Current A 6 9 6 5 Dimensions H W D mm 735 936 300 735 936 300 Packaged Dimensions H W D mm 784 960 357 784 960 357 Weight kg 55 55 Gross Weight kg 59 59 Operation Sound dBA 46 46 Piping Connection Liquid mm φ 6 4 2 φ 6 4 3 Gas mm φ12 7 2 φ12 7 3 Drain mm φ16 0 φ16 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit W...

Page 42: ...ons H W D mm 735 936 300 735 936 300 Packaged Dimensions H W D mm 784 960 357 784 960 357 Weight kg 58 58 Gross Weight kg 62 62 Operation Sound dBA 48 48 Piping Connection Liquid mm φ 6 4 1 φ 9 5 2 φ 6 4 2 φ 9 5 2 Gas mm φ12 7 1 φ15 9 2 φ12 7 2 φ15 9 2 Drain mm φ16 0 φ16 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit...

Page 43: ...4 Power Consumption W H 60 L 41 Starting Current A 12 1 Dimensions H W D mm 908 900 320 Packaged Dimensions H W D mm 942 926 394 Weight kg 66 Gross Weight kg 77 Operation Sound dBA 48 Piping Connection Liquid mm φ 6 4 2 φ 9 5 2 Gas mm φ12 7 1 φ15 9 3 Drain mm φ25 0 Heat Insulation Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit Wiring Max Piping Length m 70 for...

Page 44: ...sions H W D mm 735 936 300 908 900 320 Packaged Dimensions H W D mm 784 960 357 942 926 394 Weight kg 58 66 Gross Weight kg 62 77 Operation Sound dBA 48 48 Piping Connection Liquid mm φ 6 4 1 φ 9 5 2 φ 6 4 2 φ 9 5 2 Gas mm φ12 7 1 φ15 9 2 φ12 7 1 φ15 9 3 Drain mm φ16 0 φ 25 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interu...

Page 45: ...735 936 300 735 936 300 Packaged Dimensions H W D mm 784 960 357 784 960 357 Weight kg 55 55 Gross Weight kg 59 59 Operation Sound dBA 46 46 Sound Power dBA 59 59 Piping Connection Liquid mm φ 6 4 3 φ 6 4 4 Gas mm φ 9 5 3 φ 9 5 2 φ 12 7 2 Drain mm φ18 0 φ18 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit Wiring 3 for ...

Page 46: ...908 900 320 Packaged Dimensions H W D mm 784 960 357 942 926 394 Weight kg 58 66 Gross Weight kg 62 77 Operation Sound dBA 48 48 Sound Power dBA 61 61 Piping Connection Liquid mm φ 6 4 4 φ 6 4 4 Gas mm φ9 5 2 φ12 7 1 φ15 9 1 φ9 5 1 φ12 7 1 φ15 9 2 Drain mm φ18 0 φ 25 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit Wir...

Page 47: ...s Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm φ18 0 φ18 0 Drawing No 3D040689 3D040690 Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FTXD50BVMA FTXD60BVMA Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 16 8 593 17 5 618 17 5 618 18 7 660 M ...

Page 48: ...Filter Removable Washable Mildew Proof Running Current Rated A 0 23 0 22 0 21 0 23 0 22 0 23 0 22 0 21 0 23 0 22 Power Consumption Rated W 50 50 Power Factor 98 8 98 8 99 2 98 8 98 8 98 8 98 8 99 2 98 8 98 8 Temperature Control Microcomputer Control Dimensions H W D mm 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 Weight kg 12 Gross Weight kg 17 Operation Sound H M L SL dBA 46 42 37 34 ...

Page 49: ...ion Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D044245B 3D044246B Model FTXS35CVMB 9 8 FTXS50BVMB Cooling Heating Cooling Heating Rated Capacity 3 5kW Class 5 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 7 7 272 8 1 286 11 4 402 12 6 445 M 6 0 212 6 7 237 9 7 342 10 8 381 L 4 4 155 5 3 187 8 0 282 8 9 314 SL 3 8 134 4 6 162 7 1 251 7 7 272 Fan T...

Page 50: ...wnward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 18 0 20 0 20 0 22 Power Consumption Rated W 40 45 45 50 Power Factor 96 6 97 8 96 4 97 6 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D mm 290 1 050 238 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 337 1 147 366 Weight kg 12 12 Gross Weight kg 17...

Page 51: ...ion Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D044251B 3D044252B Model ATXS35CVMB 9 ATXS50CVMB Cooling Heating Cooling Heating Rated Capacity 3 5kW Class 5 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 7 7 272 8 1 286 11 4 402 12 6 445 M 6 1 215 6 7 237 9 7 342 10 8 381 L 4 4 155 5 3 187 8 0 282 8 9 314 SL 3 8 134 4 6 162 7 1 251 7 7 272 Fan Typ...

Page 52: ... mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D046602 3D046603 Model FTXS50BVMA 8 FTXS60BVMA 8 Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color White White Air Flow Rates m min cfm H 11 4 402 12 6 444 16 2 573 17 4 613 M 9 8 346 10 9 385 13 9 490 15 3 539 L 8 7 306 9 3 329 11 9 420 13 1 464 SL 7 7 271 8 2 291 10 7 378 11 7 412 Fan Type ...

Page 53: ...ntal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 21 0 21 Power Consumption Rated W 50 50 Power Factor 99 2 99 2 Temperature Control Microcomputer Control Dimensions H W D mm 290 1 050 238 Packaged Dimensions H W D mm 337 1 147 366 Weight kg 12 Gross Weight kg 17 Operation Sound H M L SL dBA 46 42 37 34 46 42 37 34 Sound Power H dBA 63 63 Heat Insulation Both Liqui...

Page 54: ...31 29 35 33 31 29 External Static Pressure Pa 40 40 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046069A 3D046070A Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model CDXD50CVMA CDXD60CVMA Cooling Heating Cooling Heating Rated Capaci...

Page 55: ...xternal Static Pressure Pa 40 40 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046061A 3D046062A Model CDXS50CVMB CDXS60CVMB Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color Air Flow Rates m min cfm H 12 0 424 1...

Page 56: ...9 5 Drain mm VP20 O D φ 26 I D φ 20 VP20 O D φ 26 I D φ 20 Drawing No 3D046469 3D046470 Model CDXS50CVMA CDXS60CVMA Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 6 0kW Class Front Panel Color Air Flow Rates m min cfm H 12 0 424 12 0 424 16 0 565 16 0 565 M 11 0 388 11 0 388 14 8 523 14 8 523 L 10 0 353 10 0 353 13 5 477 13 5 477 SL 8 4 297 8 4 297 11 2 395 11 2 395 Fan Type Sirocco Fa...

Page 57: ...as Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ12 7 Drain mm φ18 0 φ18 0 Drawing No 3D036690 3D036691 Conversion Formulae kcal h kW 860 Btu h kW 3414 cfm m min 35 3 Model FLX50AVMA FLX60AVMA Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 5 7kW Class Front Panel Color Almond White Almond White Air Flow Rates m min cfm H 11 4 402 12 1 427 12 0 424 12 8 452 M 10 0 353 9 8 ...

Page 58: ...uid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D040174A 3D040175A Model FLXS50BVMB FLXS60BVMB Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 5 7kW Class Front Panel Color Almond White Almond White Air Flow Rates m min cfm H 11 4 402 12 1 427 12 0 424 12 8 452 M 10 0 353 9 8 346 10 7 378 10 6 374 L 8 5 300 7 5 265 9 3 328 8 4 297 SL 7 5 265 6 8 240 8 3 293 7 5 26...

Page 59: ...n Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D046600 3D046601 Model FLXS50BVMA FLXS60BVMA Cooling Heating Cooling Heating Rated Capacity 5 0kW Class 5 7kW Class Front Panel Color Almond White Almond White Air Flow Rates m min cfm H 11 4 402 12 1 427 12 0 424 12 8 452 M 10 0 353 9 8 346 10 7 378 10 6 374 L 8 5 300 7 5 265 9 3 328 8 4 297 SL 7 5 265 6 8 240 8 3 293 7 5...

Page 60: ...ht kg 19 19 Operation Sound H M L SL dBA 38 32 26 23 38 32 26 23 39 33 27 24 39 34 29 26 Sound Power H dBA 54 55 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Piping Connection Liquid mm φ 6 4 φ 6 4 Gas mm φ 9 5 φ 9 5 Drain mm φ18 0 φ18 0 Drawing No 3D040172A 3D040173A Model FVXS50BVMB Cooling Heating Rated Capacity 5 0kW Class Front Panel Color Almond White Air Flow Rates m ...

Page 61: ...zontal Upward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 14 0 14 0 26 0 32 Power Consumption Rated W 32 32 55 70 Power Factor 99 4 99 4 92 0 95 1 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D mm 600 650 195 600 650 195 Packaged Dimensions H W D mm 714 770 294 714 770 294 Weight kg 13 13 Gross Weight kg 19 ...

Page 62: ...t A 10 1 10 2 Dimensions H W D mm 735 936 300 908 900 320 Packaged Dimensions H W D mm 784 960 357 942 926 394 Weight kg 59 73 Gross Weight kg 63 80 Operation Sound dBA 48 49 48 49 Piping Connection Liquid mm φ 6 4 3 φ 6 4 3 φ 9 5 1 Gas mm φ12 7 2 φ15 9 1 φ 9 5 1 φ12 7 1 φ15 9 2 Drain mm φ16 0 φ 25 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for ...

Page 63: ... 735 936 300 735 936 300 Packaged Dimensions H W D mm 784 960 357 784 960 357 Weight kg 55 59 Gross Weight kg 59 63 Operation Sound dBA 46 47 48 49 Sound Power dBA 59 60 61 62 Piping Connection Liquid mm φ 6 4 3 φ 6 4 4 Gas mm φ9 5 2 φ12 7 1 φ9 5 2 φ12 7 2 Drain mm φ18 0 φ18 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Inter...

Page 64: ...ting Current A 8 7 Dimensions H W D mm 908 900 320 Packaged Dimensions H W D mm 942 926 394 Weight kg 73 Gross Weight kg 80 Operation Sound dBA 48 49 Sound Power dBA 61 62 Piping Connection Liquid mm φ 6 4 4 Gas mm φ 9 5 2 φ12 7 1 φ15 9 1 Drain mm φ 25 0 Heat Insulation Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit Wiring Max Interunit Piping Length m 70 for ...

Page 65: ...36 300 Packaged Dimension H W D mm 784 990 400 Weight kg 55 Gross Weight kg 59 Operation Sound Sound Pressure dBA 46 47 Silent Mode dBA Sound Power dBA 59 60 Piping Connection Liquid mm φ 6 4 3 Gas mm φ 9 5 2 φ12 7 1 Drain mm φ18 0 Heat Insulation Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply 4 for Interunit Wiring Max Piping Length m 45 for Total of Each Room 25 for One Roo...

Page 66: ... 735 936 300 908 900 320 Packaged Dimensions H W D mm 784 960 357 1 025 926 388 Weight kg 59 73 Gross Weight kg 63 80 Operation Sound dBA 48 49 48 49 Sound Power dBA 61 62 61 62 Piping Connection Liquid mm φ 6 4 4 φ 6 4 4 Gas mm φ9 5 2 φ12 7 2 φ 9 5 2 φ12 7 1 φ15 9 1 Drain mm φ18 0 φ 25 0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes No of Wiring Connection 3 for Power Supply...

Page 67: ...Specifications Si12 411A 56 Specifications ...

Page 68: ...it Board Connector Wiring Diagram 1 Printed Circuit Board Connector Wiring Diagram 58 1 1 Wall Mounted Type 20 25 35 Class 58 1 2 Wall Mounted Type 50 60 71 Class 61 1 3 Duct Connected Type 63 1 4 Floor Ceiling Suspended Dual Type 64 1 5 Floor Standing Type 66 1 6 Outdoor Units 69 ...

Page 69: ...l to 5 rooms 5 S26 Connector for signal receiver PCB 6 S27 Connector for control PCB 7 S32 Connector for heat exchanger thermistor 8 S35 Connector for INTELLIGENT EYE Sensor PCB 1 V1 Varistor 2 JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function Refer to page 259 for more detail 3 SW7 Forced operation ON OFF switch 4 LED1 LED for o...

Page 70: ...ector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 59 PCB JP21 JB JA JC 5V GND 12V R2413 SW7 PCB 1 Control S1 5V Check S27 S7 S6 S26 S32 JA S35 S21 V1 JB JC GND 12V Check PCB 2 Signal reciever PCB 3 Intelligent eye sensor ...

Page 71: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 60 Printed Circuit Board Connector Wiring Diagram PCB Detail ...

Page 72: ...29 S36 Connector for control PCB 7 S28 Connector for signal receiver PCB 8 S32 Connector for heat exchanger thermistor 9 S35 Connector for Intelligent Eye sensor PCB 10 S38 Connector for display PCB 1 V1 Varistor 2 JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function Refer to page 259 for detail 3 SW1 Forced operation ON OFF switch ...

Page 73: ...Connector Wiring Diagram PCB Detail PCB 1 Control PCB indoor unit PCB 2 Signal Receiver PCB PCB 3 Buzzer PCB PCB 4 Display PCB PCB 5 Intelligent Eye sensor PCB S1 V1 FU1 S6 S8 S26 R2860 S28 S32 JC JB JA LED A S21 S35 SW1 S29 R2861 R2862 RTH1 S38 S27 LED1 LED2 LED3 S37 R2863 S36 R2864 ...

Page 74: ... fan motor 4 S21 Connector for centralized control to 5 rooms 5 S26 Connector for display PCB 6 S32 Connector for room temp Heat exchanger thermistor 1 V1 Varistor 2 JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function Refer to page 259 for more detail 3 SW1 Forced operation ON OFF switch 4 LED1 LED for operation green 5 LED2 LED fo...

Page 75: ... control PCB 6 S26 Connector for signal receiver PCB 7 S31 Connector for room temperature thermistor 8 S32 Connector for heat exchanger thermistor 9 S37 Connector for power supply PCB 1 V1 Varistor 2 JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function Refer to page 259 for detail 3 SW1 Forced operation ON OFF switch 4 SW2 Select sw...

Page 76: ...Si12 411A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 65 Power Supply PCB PCB 2 Display PCB PCB 3 Signal Receiver PCB PCB 4 ...

Page 77: ... S26 Connector for power supply PCB 1 6 S202 S204 S8 Connector for control PCB 2 7 S25 Connector for display PCB 3 8 S301 S302 Connector for fan motors 1 V1 Varistor 2 JA Address setting jumper JB Fan speed setting when compressor is OFF on thermostat JC Power failure recovery function Refer to page 259 for detail 3 SW1 Forced operation ON OFF switch 4 SW2 Changing upward air flow limit switch 5 S...

Page 78: ...Si12 411A Printed Circuit Board Connector Wiring Diagram Printed Circuit Board Connector Wiring Diagram 67 Power Supply PCB PCB 1 ...

Page 79: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 68 Printed Circuit Board Connector Wiring Diagram Control PCB PCB 2 Display PCB PCB 3 Signal Receiver PCB PCB 4 ...

Page 80: ... S22 Connector for electronic expansion valve coil C port 4 S23 Connector for electronic expansion valve coil D port 5 S31 Connector for CN14 6 S32 Connector for CN11 7 S33 Connector for S34 8 S40 Connector for overload relay 9 S71 Connector for S72 10 S80 Connector for four way valve coil 11 S90 Connector for thermistor outdoor air heat exchanger and discharge pipe 12 S92 Connector for gas pipe t...

Page 81: ...Printed Circuit Board Connector Wiring Diagram Si12 411A 70 Printed Circuit Board Connector Wiring Diagram ...

Page 82: ... Function of Main Structural Parts 85 2 1 Main Structural Parts 85 2 2 Function of Thermistor 86 3 Control Specification 90 3 1 Mode Hierarchy 90 3 2 Frequency Control 91 3 3 Controls at Mode Changing Start up 93 3 4 Discharge Pipe Control 94 3 5 Input Current Control 94 3 6 Freeze up Protection Control 95 3 7 Heating Peak cut Control 95 3 8 Fan Control 96 3 9 Moisture Protection Function 2 96 3 1...

Page 83: ...le explains the conversion principle Drawing of Inverter The following drawing shows a schematic view of the inverter principle Phase Description 1 The supplied AC power source is converted into the DC power source for the present 2 The DC power source is reconverted into the three phase AC power source with variable frequency When the frequency increases the rotation speed of the compressor incre...

Page 84: ...air condition with a small room temperature variation Energy saving heating and cooling Once the set temperature is reached the energy saving operation enables to maintain the room temperature at low power Frequency Limits The following table shows the functions that define the minimum and maximum frequency Forced Cooling Heating Operation For more information refer to Forced operation mode on pag...

Page 85: ...omfortable air distribution Auto Swing In case of Wall Mounted Type 50 60 71 Class The following table explains the auto swing process for heating cooling dry and fan Outline of 3 D Airflow Alternative repetition of vertical and horizontal swing motions enables uniform air conditioning of the entire room This function is effective for starting the air conditioner Detail of the Action When the hori...

Page 86: ...perates H tap 50 90 rpm 2 Fan stops during defrost operation Automatic Air Flow Control for Heating The following drawing explains the principle for fan speed control for heating Automatic Air Flow Control for Cooling The following drawing explains the principle of fan speed control for cooling Step Cooling Heating Dry mode LLL Heating thermostat OFF 20 25 35kW class 500 860 rpm During powerful op...

Page 87: ...set by the microcomputer is divided into two zones Then the unit operates in the dry mode with an appropriate capacity for each zone to maintain the temperature and humidity at a comfortable level Room temperature at startup Temperature ON point at which operation starts Frequency switching point Temperaturedifference for operation stop 24ºC Room temperature at startup 0 5ºC 1 5ºC 18ºC 18ºC 1 0ºC ...

Page 88: ...ler setting temperature plus correction value correction value cooling 0 deg heating 2 deg 3 Operation ON OFF point and mode switching point are as follows Heating Cooling switching point Room temperature Main unit setting temperature 2 5 deg Cooling Heating switching point Room temperature Main unit setting temperature 2 5 deg Thermostat ON OFF point is the same as the ON OFF point of cooling or ...

Page 89: ...ght Set circuit continues heating or cooling the room at the set temperature for the first one hour then automatically raises the temperature setting slightly in the case of cooling or lowers it slightly in the case of heating for economical operations This prevents excessive heating in winter and excessive cooling in summer to ensure comfortable sleeping conditions and also conserves electricity ...

Page 90: ... microcomputer doesn t have a signal from the sensor in 20 minutes it judges that nobody is in the room and operates the unit in temperature sifted 2 C from the set temperature Cooling 2 C higher Dry 1 C higher and Auto according to the operation mode at that time 1 In case of Fan mode the fan speed reduces by 50 rpm If the sensor detects the outputs 10 times sec or more it judges humans exist 1se...

Page 91: ...s so as to prevent this phenomena After this 40 minutes the prohibition of the thermostat off is cancelled and it can realize the conditions to conduct thermostat off depending on the room temperature In or after this forty minutes if the sensor detects human motion detection signal it let the set temperature and the fan speed return to the original set point keeping a normal operation Others The ...

Page 92: ...ed the function becomes effective when the operation is started If this button is pressed in powerful operation the powerful operation is reset and this function becomes effective The HOME LEAVE button is ineffective in dry mode and fan mode 2 Details of Function A mark representing HOME LEAVE is indicated on the liquid crystal display of the remote controller The indoor unit is operated according...

Page 93: ...es In case of Wall Mounted Type 50 60 71 Class Ex Powerful operation in cooling mode Operation mode Fan speed Target set temperature Cooling H tap 90 rpm 18 C Dry Dry rotating speed 50 rpm Normally targeted temperature in dry operation Approx 2 C Heating H tap 90 rpm 30 C Fan H tap 90 rpm Automatic Same as cooling heating in Powerful operation The target is kept unchanged R4571 Target temp Fan 90r...

Page 94: ...his button 1 10 4 Photocatalytic Deodorizing Filter Photocatalytic Deodorizing Filter demonstrates powerful oxidation characteristics when subjected to harmless ultraviolet light Photocatalytic deodorizing power is recovered simply by exposing the filter to the sun for 6 hours once every 6 months 1 10 5 Air Purifying Filter A double structure made up of a bacteriostatic filter and an Air Purifying...

Page 95: ...ality occur the LCD remote controller displays error code These indications allow prompt maintenance operations 1 10 9 Auto restart Function Even if a power failure including one for just a moment occurs during the operation the operation restarts in the condition before power failure automatically when power is restored Note It takes 3 minutes to restart the operation because the 3 minute standby...

Page 96: ...Swing compressor being operated by INV control Heat Pump Model Cooling Only Model Note 1 Expansion Valve In Case of 2MK X EVA B 3MK X EVA C 4MK X EVA D 2 Liquid pipe thermistor R410A Type only 2 Four way valve 1 Compressor 3 Solenoid valve EVB EVC EVD EVA Receiver 4 Expansion valve R2433 SV D 1 Compressor EVB EVC EVD EVA 4 Expansion valve R2434 ...

Page 97: ...arge piping is lower than the temperature of outdoor heat exchanger a disconnected discharge pipe thermistor can be detected B Discharge Pipe Thermistor DOT 1 Discharge pipe thermistor is used to control a discharge pipe If the temperature of discharge pipe used in place of the inner temperature of the compressor rises abnormally the operating frequency drops or the operation must be halted 2 A di...

Page 98: ...indoor heat exchanger temperature a disconnected discharge pipe thermistor can be detected 5 An indoor heat exchanger thermistor is used for detecting incorrect wiring During the operation of checking incorrect wiring refrigerant is passed in order from the port A to detect a heat exchanger temperature and then wiring and piping will be checked 6 An indoor heat exchanger thermistor is used for sub...

Page 99: ... of the discharge piping is lower than the temperature of outdoor heat exchanger a disconnected discharge pipe thermistor can be detected B Discharge Pipe Thermistor DOT 1 Discharge pipe thermistor is used to control a discharge pipe If the temperature of discharge pipe used in place of the inner temperature of the compressor rises abnormally the operating frequency drops or the operation must be ...

Page 100: ...ng the cooling operation if the temperature drops abnormally the operating frequency becomes lower then the operation must be halted 3 An indoor heat exchanger thermistor is used for anti icing control During the cooling operation if the heat exchanger temperature in the room where operation is halted becomes 1 C or if the room temperature heat exchanger in the room where operation is halted becom...

Page 101: ...during forced operation Determine Operating Mode Judge the operating mode command set by each room in accordance with the instructing procedure and determine the operating mode of the system The following procedure will be taken as the modes conflict with each other 1 The system will follow the mode determined first First push first set 2 For the rooms set with different mode select stand by mode ...

Page 102: ...et a minimum value as an upper limit frequency among the frequency upper limits of the following functions Compressor protection input current discharge pipes Low Hz high pressure peak cutting freeze up protection defrost 3 Determine lower limit frequency Set a maximum value as an lower limit frequency among the frequency lower limits of the following functions Four way valve operating compensatio...

Page 103: ...ency Up Down by D Signal 1 P control Calculate a total of the D value in each sampling time 20 seconds and adjust the frequency according to its difference from the frequency previously calculated 2 I control If the operating frequency is not change more than a certain fixed time adjust the frequency up and down according to the Σ D value obtaining the fixed Σ D value When the Σ D value is small l...

Page 104: ...tion stopped Detail The OFF delay of four way valve Energize the coil for 150 sec after unit operation is stopped 3 3 3 Four Way Valve Operation Compensation Outline Heat Pump Only At the beginning of the operation as the four way valve is switched acquire the differential pressure required for activating the four way valve by having output the operating frequency which is more than a certain fixe...

Page 105: ...stop zone the compressor operation stops If a drooping current is continues for 1 0 second after rushing on the drooping zone the frequency will be 2 Hz drooping Repeating the above drooping continues until the current rushes on the drooping zone without change In the unchanged zone the frequency limit will remain In the return reset zone the frequency limit will be cancelled Limitation of current...

Page 106: ...sec from changing number of operation room Control in Each Zone 3 7 Heating Peak cut Control Outline Heat Pump Only During heating operation the signals being sent form the indoor unit allow the operating frequency limitation and prevent abnormal high pressure The signal from the indoor unit must be divided as follows Detail Conditions for Start Controlling Judge the controlling start with the ind...

Page 107: ...turned OFF for 30 seconds Tap Control in Indoor Outdoor Unit Silent Operation 1 When Cooling Operation When the outdoor air temperature is less than 37 C the fan tap must be set to L 2 When Heating Operation When the outdoor air temperature is more than 4 C the fan tap must be turned to L only for heat pump model 3 9 Moisture Protection Function 2 Outline In order to obtain the dependability of th...

Page 108: ...minutes of accumulated time pass since the start of the operation or ending the defrosting Conditions for Canceling Defrost The target heat exchanger temperature as the canceling condition is selected in the range of 4 C Te 12 C according to the air temperature as the following formula The target heat exchanger temperature 45 65 ambient temperature 14 The defrost operation surely operates in 120 s...

Page 109: ...e is fully closed 1 Electronic expansion valve is fully closed when turning on the power 2 Pressure equalizing control Room Distribution Control 1 Gas pipe isothermal control 2 SC control Only for Heat Pump Model Open Control 1 Electronic expansion valve control when starting operation 2 Control when frequency changed 3 Control for defrosting only for heat pump model 4 Oil recover control 5 Contro...

Page 110: ...re equalizing control Gas pipe isothermal control SC control only for heat pump model Control when frequency changed Control for abnormally high discharge pipe temperature Liquid pipe temperature control for stopped rooms Dew prevention control for indoor rotor Oil recovery control Indoor freeze up protection control Liquid pipe temperature control When power is turned ON Cooling 1 room operation ...

Page 111: ... be super heated or moistened 3 12 5 High Temperature of the Discharge Pipe When the compressor is operating if the discharge pipe temperature exceeds a certain value open the electronic expansion valve and remove the refrigerant to the low pressure side and lower discharge temperature 3 12 6 Oil Recovery Function Outline The electronic expansion valve opening in the cooling stopped room must be s...

Page 112: ...emperature difference between the maximum heat exchanger temperature of connected room and the temperature of liquid pipe thermistor becomes constant 3 12 10 Disconnection of the Discharge Pipe Thermistor Outline Detect a disconnected discharge pipe thermistor by comparing the discharge pipe temperature with the condensation temperature If any is disconnected open the electronic expansion valve ac...

Page 113: ...cy is changed When the target pipe temperature control is active if the target frequency is changed for a specified value in a certain time period cancel the target discharge pipe temperature control and change the opening of the target electronic expansion valve according to the shift ...

Page 114: ...rrent exceeds 30 A the compressor gets interrupted too 3 13 3 Insufficient Gas Control Outline If a power consumption is below the specified value in which the frequency is higher than the specified frequency it must be regarded as gas insufficient In addition to such conventional function if the discharge temperature is higher than the target discharge pipe temperature and more than the specified...

Page 115: ...t abnormal but the indoor unit which is not in the freezing prohibiting zone is present in more than 1 room 1 The indoor unit is not abnormal The indoor unit which is not in the peak cut prohibited zone is present in more than 1 room 2 The outdoor unit is not abnormal and not in the 3 minute stand by mode 3 The operating mode of the outdoor unit is the stop mode 4 The slide selection switch of the...

Page 116: ...e indoor unit heat exchanger thermistor is disconnected An indoor unit is in trouble if a trouble occurs during the wiring error checking Emergency stop Any of the LED indicators 1 4 stays on Note 1 It takes about 10 15 minutes after pressing the wiring error check switch to complete the checking Wrong wiring between the upper and lower units cannot be self corrected 2 Wrongly connected liquid and...

Page 117: ...rced operation is over LED1 Room A wiring LED2 Room B wiring 1st flashing LED Port A piping 2nd flashing LED Port B piping The first stay on LED means the room that is connected with Port A The next stay on LED means the one connected with Port B Example Let s suppose the LED indicators are flashing as follows The above means that Port A is connected with Port B and Port B with Room A or self corr...

Page 118: ...room can be set as the priority room Control start conditions Priority room setting is made AND Powerful signal from the priority room unit is received Note The operation mode of the priority room unit has precedence Cancellation of control The control function is canceled when the Powerful operation mode is switched off or 20 minutes elapse after Powerful Operation started 3 16 3 Powerful Operati...

Page 119: ...ting to only heat H Short circuit pins 1 and 3 of the connector S15 Setting to only cool C short circuit pins 3 and 5 of the connector S15 The following specifications apply to the connector housing and pins JST products Housing VHR 5N Pin SVH 21T 1 1 Note that forced operation is also possible in COOL HEAT mode COOL mode C HEAT mode H 5 C 3 H 1 R1397 ...

Page 120: ...cautions 112 2 3 Names of Parts 114 2 4 Preparation before Operation 126 2 5 AUTO DRY COOL HEAT FAN Operation 129 2 6 Adjusting the Air Flow Direction 131 2 7 POWERFUL Operation 137 2 8 OUTDOOR UNIT SILENT Operation 138 2 9 HOME LEAVE Operation 139 2 10 INTELLIGENT EYE Operation 141 2 11 TIMER Operation 145 2 12 Note for Multi System 147 2 13 Care and Cleaning 149 2 14 Troubleshooting 159 ...

Page 121: ...d to know a clever method of using it In order to meet this expectation of the users giving sufficient explanations taking enough time can be said to reduce about 80 of the requests for servicing However good the installation work is and however good the functions are the customer may blame either the room air conditioner or its installation work because of improper handling The installation work ...

Page 122: ...60AVMA Read before Operation Safety Precautions 112 112 112 112 Names of Parts 114 117 120 123 Preparation before Operation 126 126 126 126 Operation AUTO DRY COOL HEAT FAN Operation 129 129 129 129 Adjusting the Air Flow Direction 131 133 135 POWERFUL Operation 137 137 137 137 OUTDOOR UNIT SILENT Operation 138 138 138 138 HOME LEAVE Operation 139 139 139 139 INTELLIGENT EYE Operation 141 143 TIME...

Page 123: ...igerant check the content of the repairs with our service staff Do not attempt to install the air conditioner by your self Incorrect work will result in water leakage electric shocks or fire For installation consult the dealer or a qualified technician In order to avoid electric shock fire or injury if you detect any abnormally such as smell of fire stop the operation and turn off the breaker And ...

Page 124: ...ge Incomplete draining may cause wetting of the building furniture etc Do not operate the air conditioner with wet hands Do not wash the indoor unit with excessive water only use a slightly wet cloth Do not place things such as vessels containing water or anything else on top of the unit Water may pene trate into the unit and degrade electrical insulations resulting in an electric shock To install...

Page 125: ...Instruction Si12 411A 114 System Configuration 2 3 Names of Parts FTK X E 25 35 B Names of parts Indoor Unit ON OFF 1 3 4 5 6 7 9 10 11 2 14 15 16 8 12 13 ...

Page 126: ...h once to start operation Push once again to stop it The operation mode refers to the following table This switch is useful when the remote controller is missing 13 Operation lamp green 14 TIMER lamp Yellow 15 HOME LEAVE lamp red 16 Signal receiver It receives signals from the remote controller When the unit receives a signal you will hear a short beep Operation start beep beep Settings changed be...

Page 127: ... this button once to start operation Press once again to stop it 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN 8 SILENT button for OUTDOOR UNIT SILENT operation Only works for multi connection 9 FAN setting button It selects the air flow rate setting 10 SWING button 11 SENSOR button for INTELLIGENT EYE operation 12 ON TIMER button 13 OFF TIMER button 14 TIMER Setting ...

Page 128: ...Si12 411A Instruction System Configuration 117 FTK X D 50 60 71 B Names of parts Indoor Unit Main unit control panel 7 14 11 12 13 4 3 1 2 9 10 8 6 5 16 15 ...

Page 129: ...VE Operation 14 Indoor Unit ON OFF switch 2Push this switch once to start operation Push once again to stop it 2The operation mode refer to the following table 2This switch is useful when the remote controller is missing 15 Room temperature sensor 2It senses the air temperature around the unit 16 Signal receiver 2It receives signals from the remote controller 2When the unit receives a signal you w...

Page 130: ...once to start operation Press once again to stop it 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN 8 SILENT button for OUTDOOR UNIT SILENT operation 9 FAN setting button It selects the air flow rate setting 10 SENSOR button for INTELLIGENT EYE operation 11 SWING button Flap Horizontal blade 12 SWING button Louver Vertical blades 13 ON TIMER button 14 OFF TIMER button 1...

Page 131: ...Instruction Si12 411A 120 System Configuration CDK X D 25 35 50 60 C Names of parts Indoor Unit 3 6 8 9 10 7 1 4 5 2 ...

Page 132: ...Operation lamp green 8 TIMER lamp yellow 9 HOME LEAVE lamp red LIghts up when you use HOME LEAVE operation 10 Indoor Unit ON OFF switch Push this switch once to start operation Push once again to stop it This switch is useful when the remote controller is missing The operation mode refers to the following table Outdoor Unit 11 Air inlet Back and side 12 Refrigerant piping and inter unit cable 13 D...

Page 133: ... It changes the temperature setting 6 ON OFF button Press this button once to start operation Press once again to stop it 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN 8 SILENT button for OUTDOOR UNIT SILENT operation 9 FAN setting button It selects the air flow rate setting 10 ON TIMER button 11 OFF TIMER button 12 TIMER Setting button It changes the time setting 13 ...

Page 134: ...the ceiling or to a wall The descriptions contained in this manual show the case when installation is being carried out to the ceiling The methods of operation used are the same when installing to a wall CAUTION Before opening the front grille be sure to stop the operation and turn the breaker OFF O N OFF 1 2 3 4 5 6 11 12 10 7 9 8 13 14 ...

Page 135: ...art operation Push once again to stop it 2 Push the switch using an object with a sharp tip such as a pen 2 This switch is useful when the remote controller is missing 14 Signal receiver 2 It receives signals from the remote controller 2 When the unit receives a signal you will hear a short beep 2 Operation start beep beep 2 Settings changed beep 2 Operation stop beeeeep 2 The operation mode refer...

Page 136: ...t changes the temperature setting 6 ON OFF button Press this button once to start operation Press once again to stop it 7 MODE selector button It selects the operation mode AUTO DRY COOL HEAT FAN 8 OUTDOOR UNIT SILENT button 9 FAN setting button It selects the air flow rate setting 10 SWING button 11 ON TIMER button 12 OFF TIMER button 13 TIMER Setting button It changes the time setting 14 TIMER C...

Page 137: ...ame type and replace the two old batteries together When the system is not used for a long time take the batteries out We recommend replacing once a year although if the remote controller display begins to fade or if reception deteriorates please replace with new alkali batteries Using manganese batteries reduces the lifespan The attached batteries are provided for the initial use of the system Th...

Page 138: ...each the unit 2 Fix the holder to a wall a pillar etc with the screws supplied with the holder 3 Place the remote controller in the remote controller holder ATTENTION About remote controller Never expose the remote controller to direct sunlight Dust on the signal transmitter or receiver will reduce the sensitivity Wipe off dust with soft cloth Signal communication may be disabled if an electronic ...

Page 139: ...ir conditioner for a long period for example in spring or autumn turn the breaker OFF Use the air conditioner in the following conditions Operation outside this humidity or temperature range may cause a safety device to disable the system C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SWING SILENT SENSOR ON CANCEL OFF 1 3 2 Recommended temperature setting For cooling 26 C 28 C For heating 20 C 2...

Page 140: ... the button advances the mode setting in sequence AUTO DRY COOL HEAT FAN 2 Press ON OFF button The OPERATION lamp lights up To stop operation 3 Press ON OFF button again Then OPERATION lamp goes off To change the temperature setting 4 Press TEMPERATURE adjustment button DRY or FAN mode AUTO or COOL or HEAT mode The temperature setting is not variable Press to raise the temperature and press to low...

Page 141: ...t air around all parts of the room After the start of heating operation it takes some time before the room gets warmer In heating operation frost may occur on the outdoor unit and lower the heating capacity In that case the system switches into defrosting operation to take away the frost During defrosting operation hot air does not flow out of indoor unit Note on DRY operation The computer chip wo...

Page 142: ...n to increase your com fort To adjust the horizontal blades flaps 1 Press SWING button The display will light up and the flaps will begin to swing 2 When the flaps have reached the desired position press SWING button once more The display will go blank The flaps will stop moving C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SWING SILENT SENSOR ON CANCEL OFF O N 1 2 ...

Page 143: ...s on the operation mode See the figure ATTENTION Always use a remote controller to adjust the flaps angle If you attempt to move it forcibly with hand when it is swinging the mechanism may be broken Be careful when adjusting the louvres Inside the air outlet a fan is rotating at a high speed In DRY mode or COOL mode In HEAT or FAN mode When stop operation Upper limit in cooling Lower limit in cool...

Page 144: ...en the flap have reached the desired position press SWING button once more The display will go blank The flap will stop moving To adjust the vertical blades louvers 3 Press SWING button The display will light up and the louvers will begin to swing 4 When the louvers have reached the desired position press the SWING button once more The display will go blank The louvers will stop moving C TEMP ON O...

Page 145: ...ed the flaps swinging range depends on the operation mode See the figure Three Dimensional 3 D Airflow Using three dimensional airflow circulates cold air which tends to collected at the bottom of the room and hot air which tends to collect near the ceiling throughout the room preventing areas of cold and hot developing ATTENTION Always use a remote controller to adjust the flaps angle If you atte...

Page 146: ...e your com fort To adjust the horizontal blade flap 1 Press SWING button The display will light up and the flaps will begin to swing 2 When the flaps have reached the desired position press SWING button once more The display will go blank The flaps will stop moving C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SWING SILENT ON CANCEL OFF O N 1 2 ...

Page 147: ...elected you should set the flap at a near horizontal angle in COOL or DRY mode to obtain the best performance In COOL or DRY mode if the flap is fixed at a downward position the flap automatically moves in about 60 minutes to prevent condensation on it ATTENTION Always use a remote controller to adjust the flap angle If you attempt to move it forcibly with hand when it is swinging the mechanism ma...

Page 148: ...unctions which are not available To cancel POWERFUL operation 2 Press POWERFUL button again NOTE Notes on POWERFUL operation In COOL and HEAT mode To maximize the cooling heating effect the capacity of outdoor unit must be increased and the air flow rate be fixed to the maximum setting The temperature and air flow settings are not variable In DRY mode The temperature setting is lowered by 2 5 C an...

Page 149: ...ing a multi system this function will work only when the OUTDOOR UNIT SILENT operation is set on all operated indoor units However if using priority room setting see Note for multi system This function is available in COOL HEAT and AUTO modes This is not available in FAN and DRY mode POWERFUL operation and OUTDOOR UNIT SILENT operation cannot be used at the same time Priority is given to POWERFUL ...

Page 150: ... time please set the temperature and air flow rate for HOME LEAVE operation Record your preferred temperature and air flow rate 1 Press HOME LEAVE button Make sure is displayed in the remote control display 2 Adjust the set temperature with or as you like 3 Adjust the air flow rate with FAN setting button as you like Home leave operation will run with these settings the next time you use this func...

Page 151: ... be welcomed by a comfortably air conditioned room Push the HOME LEAVE Opera tion button again and the air con ditioner will adjust capacity to the set temperature for normal opera tion Set the unit to HOME LEAVE Oper ation before leaving the living room when going to bed The unit will maintain the tem perature in the room at a com fortable level while you sleep When you enter the living room in t...

Page 152: ...movement To start INTELLIGENT EYE operation 1 Press SENSOR button To cancel the INTELLIGENT EYE operation 2 Press SENSOR button again EX C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SWING SILENT SENSOR ON CANCEL OFF 1 2 When somebody in the room Normal operation When nobody in the room 20 min after start energy saving operation Somebody back in the room Back to normal operation ...

Page 153: ...etect moving objects further than 5m away Check the application range Sensor detection sensitivity changes according to indoor unit location the speed of pass ersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and light reflected off of mirrors as passersby INTELLIGENT EYE operatipon will not go on during powerful operation Night set mode will not go o...

Page 154: ...art INTELLIGENT EYE operation 1 Press SENSOR button To cancel the INTELLIGENT EYE operation 2 Press SENSOR button again EX C TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SILENT ON CANCEL OFF SWING 1 2 SENSOR When somebody in the room Normal operation When nobody in the room 20 min after start energy saving operation Somebody back in the room Back to normal operation ...

Page 155: ...unit location the speed of passersby temperature range etc The sensor also mistakenly detects pets sunlight fluttering curtains and light reflected off of mirrors as passersby INTELLIGENT EYE operation will not go on during powerful operation Night set mode will not go on during you use INTELLIGENT EYE operation Do not place large objects near the sensor Also keep heating units or humidifiers outs...

Page 156: ...es the setting rapidly 3 Press OFF TIMER button again The TIMER lamp lights up To cancel the OFF TIMER operation 4 Press CANCEL button The TIMER lamp goes off Notes When TIMER is set the present time is not displayed Once you set ON OFF TIMER the time setting is kept in the memory The memory is canceled when remote controller batteries are replaced When operating the unit via the ON OFF Timer the ...

Page 157: ...ing rapidly 3 Press ON TIMER button again The TIMER lamp lights up To cancel ON TIMER operation 4 Press CANCEL button The TIMER lamp goes off To combine ON TIMER and OFF TIMER A sample setting for combining the two timers is shown below ATTENTION In the following cases set the timer again After a breaker has turned OFF After a power failure After replacing batteries in the remote controller C TEMP...

Page 158: ...IGHT QUIET Mode requires initial programming during installation Please consult your retailer or dealer for assistance NIGHT QUIET Mode reduces the operation noise of the outdoor unit during the night time hours to prevent annoyance to neighbors The NIGHT QUIET Mode is activated when the temperature drops 5 C or more below the highest temperature recorded that day Therefore when the temperature di...

Page 159: ...nd D are all operating If the unit in Room A enters POWERFUL operation operation capacity will be concentrated in Room A In such a case the cooling heating efficiency of the units in Rooms B C and D may be slightly reduced 3 Priority when using OUTDOOR UNIT SILENT operation Example Room A is the Priority Room in the examples Just by setting the unit in Room A to SILENT operation the air conditione...

Page 160: ...front grille Set the 3 keys of the front grille into the slots and push them in all the way Close the front grille slowly and push the grille at the 3 points 1 on each sides and 1 in the middle Check to see if the rotating axis in the upper center section is moving CAUTION Units Don t touch the metal parts of the indoor unit If you touch those parts this may cause an injury When removing or attach...

Page 161: ...hem with neutral detergent thinned with lukewarm water then dry them up in the shade It is recommended to clean the air filters every two weeks Air Purifying Filter green Replace approximately once every 3 months 1 Detach the filter element and attach a new one Insert with the green side up It is recommended to replace the air purifying filter every three months Photocatalytic Deodorizing Filter g...

Page 162: ...e leaking from the indoor unit Stop operation and consult the ser vice shop if this is the case Operation with dirty filters 1 cannot deodorize the air 2 cannot clean the air 3 results in poor heating or cooling 4 may cause odour The air purifying filter and Photocatalytic deodorizing filter cannot be reused even if washed In principle there is no need to replace the photocatalytic deodorizing fil...

Page 163: ...ter dry it with cloth dry it up in the shade after washing 4 Attach the front grille Align the rotation dowels on the left and right of the front panel with the slots then push them all the way in Close the front panel slowly Press the panel at both sides and the center CAUTION Units Don t touch the metal parts of the indoor unit If you touch those parts this may cause an injury When removing or a...

Page 164: ...t does not come off easily wash them with neutral detergent thinned with lukewarm water then dry them up in the shade It is recommended to clean the air filters every two weeks Air purifying filter with photocatalytie deodorizing function gray The air purifying capacity of the photocatalytic purifying filter can be renewed by washing it with water once every 6 months We recommend replacing it once...

Page 165: ...ing blocks the air inlets and the outlets of the indoor unit and the outdoor unit Check that the earth wire is not disconnected or broken Check that the drain comes smoothly out of the drain hose during COOL or DRY operation If no drain water is seen water may be leaking from the indoor unit Stop operation and consult the ser vice shop if this is the case Operation with dirty filters 1 cannot deod...

Page 166: ...ion 2 Clean the air filters and set them again 3 Take out batteries from the remote controller 4 Turn OFF the breaker for the room air conditioner When a multi outdoor unit is connected make sure the heating operation is not used at the other room before you use the fan operation NOTE Check that the base stand and other fittings of the outdoor unit are not decayed or corroded Check that nothing bl...

Page 167: ...indicated by Operation without air filters may result in troubles as dust will accumulate inside the indoor unit CAUTION Units Don t touch the metal parts of the indoor unit If you touch those parts this may cause an injury When opening and closing the front grille use a robust and stable stool and watch your steps carefully When opening and closing the front grille support the grille securely wit...

Page 168: ...ewarm water then dry them up in the shade It is recommended to clean the air filters every two weeks Air Purifying Filter green Replace approximately once every 3 months 1 Detach the filter element and attach a new one Insert with the green side up It is recommended to replace the air purifying filter every three months Photocatalytic Deodorizing Filter gray Maintenance 1 Dry the photocatalytic de...

Page 169: ...y be leaking from the indoor unit Stop operation and consult the ser vice shop if this is the case Operation with dirty filters 1 cannot deodorize the air 2 cannot clean the air 3 results in poor heating or cooling 4 may cause odour The air purifying filter and Photocatalytic deodorizing filter cannot be reused even if washed In principle there is no need to replace the photocatalytic deodorizing ...

Page 170: ... or steam when the air conditioner is in defrost operation In COOL or DRY mode Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips Mists come out of the indoor unit This happens when the air in the room is cooled into mist by the cold air flow during cooling operation The indoor unit gives out odour This happens when smells of the room furniture or cigaret...

Page 171: ...block the air inlet or the outlet of the indoor and the outdoor units Clean the air filters or take all obstacles away and turn the breaker OFF Then turn it ON again and try operating the air conditioner with the remote controller If the lamp still flashes call the service shop where you bought the air conditioner Are operation modes all the same for indoor units connected to outdoor units in the ...

Page 172: ...rmance It is recommended to have periodical maintenance by a specialist aside from regular cleaning by the user For specialist maintenance contact the service shop where you bought the air conditioner The maintenance cost must be born by the user Call the service shop immediately After a power failure The air conditioner automatically resumes operation in about 3 minutes You should just wait for a...

Page 173: ...Instruction Si12 411A 162 System Configuration ...

Page 174: ...8 5 8 Signal Transmission Error between Indoor and Outdoor Units 179 5 9 Unspecified Voltage between Indoor and Outdoor Units 180 5 10 Freeze up Protection Control 181 5 11 OL Activation Compressor Overload 183 5 12 Compressor Lock 184 5 13 DC Fan Lock 185 5 14 Input Over Current Detection 186 5 15 Four Way Valve Abnormality 188 5 16 Discharge Pipe Temperature Control 190 5 17 Position Sensor Abno...

Page 175: ...ure described in the following pages Location of Operation Lamp In case of FTK X S 20 25 35 Series FTK X E 25 35 Series ATXS 20 25 35 Series Grille type In case of FTK X S 50 60 71 Series FTK X D 50 60 71 Series ATXS 50 Series Grille type In case of CDK X S 25 35 50 60 C Series CDK X D 25 35 50 60 C Series In case of FVK X S 25 35 50 B Series In case of FLK X S 25 35 50 60 B Series FLK X 25 35 50 ...

Page 176: ... operation lamp is normal If the lamp stops blinking after the above steps there is no malfunction Operation stops and operation lamp blinks only for indoor unit which the different operation mode is set later The first set operation mode has priority Troubleshooting with the LED Indication Outdoor Unit There are green and red LEDs on the PCB The flashing green LED indicates normal equipment condi...

Page 177: ...agnosis with indoor unit LED indication 169 Diagnosis with outdoor unit LED indication 170 Some indoor units do not operate Check the type of the indoor units Check to make sure that the indoor unit type is compatible with the outdoor unit Diagnosis with indoor unit LED indication 169 Diagnosis with outdoor unit LED indication 170 Equipment operates but does not cool or does not heat only for heat...

Page 178: ... 7 E5 17 C4 27 L4 8 LC 18 C5 28 H6 9 C9 19 H9 29 H7 10 U0 20 J6 30 U2 C O N TEMP ON OFF POWERFUL HOME LEAVE MODE TIMER FAN SWING SILENT SENSOR ON CANCEL OFF Signal transmitter It sends signals to the indoor unit Display It displays the current settings In this illustration each section is shown with all its displays ON for the purpose of explanation HOME LEAVE button ON TIMER button ON OFF button ...

Page 179: ...rature thermistor abnormality C7 Shutter drive motor shutter limit switch abnormality C9 Room temperature thermistor abnormality Outdoor Unit E5 OL activation compressor overloaded E6 Compressor lock E7 DC fan lock E8 Input over current detection EA Four way valve abnormality F3 Discharge pipe temperature control H6 Position sensor abnormality H8 CT or related abnormality H9 Outdoor air thermistor...

Page 180: ...unit A1 Indoor unit PCB abnormality 171 A5 Freeze up protection control or high pressure control heat pump model only 172 A6 Fan motor or related abnormality AC motor Wall 20 35 Duct Floor Ceiling 174 DC motor Wall 50 71 Floor 175 C4 Heat exchanger thermistor or related abnormality 177 C7 Shutter drive motor shutter limit switch abnormality 178 C9 Room temperature thermistor abnormality 177 U4 Sig...

Page 181: ...d page Green Red A 1 2 3 4 5 3 3 3 3 00 Outdoor unit in normal condition Conduct a diagnosis of the indoor unit UA Unspecified voltage between indoor and outdoor units 205 UH Anti icing function in other rooms 205 5 3 3 4 4 U0 Insufficient gas 202 5 4 3 4 3 E5 OL activation compressor overload 183 5 3 4 4 3 E6 Compressor lock 184 5 4 3 4 3 F3 Discharge pipe temperature control 190 5 3 3 3 4 L4 Rad...

Page 182: ...Troubleshooting Note Connector Nos vary depending on models Control connector Connector connection check note YES Is it normal NO Correct connections Replace PCBs R1400 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Model Type Connector No Wall Mounted Type 20 25 35 class Terminal strip Control PCB Wall Mounted Type 50 60 71 class Te...

Page 183: ...n according to the temperature detected by the indoor unit heat exchanger thermistor Malfunction Decision Conditions High pressure control During heating operations the temperature detected by the indoor heat exchanger thermistor is above 65 C Freeze up protection When the indoor unit heat exchanger temperature is below 0 C during cooling operation Supposed Causes Operation halt due to clogged air...

Page 184: ...ger thermistor check Check the intake air filter Check the air passage YES YES R1401 Check the dust accumulation on the indoor unit heat exchanger YES YES Is there any short circuit Is it very dirty Is it very dirty Does it conform to the thermistor characteristic chart NO Provide sufficient air passage Clean the air filter Clean the heat exchanger Replace the indoor unit PCB Replace the thermisto...

Page 185: ...on error due to faulty control PCB Troubleshooting Check No 16 Refer to P 215 Rotate the fan by hand Check No 16 Check Hall IC Operate the fan Does it rotate NO Does it rotate smoothly Is there an output Is it at the rated voltage Is there conductivity NO Check the capacitor s conductivity Check the fan motor voltage immediately after re start Is it at the rated voltage Check the fan motor voltage...

Page 186: ...ion Malfunction Decision Conditions When the detected rotation speed is less than 50 of the H tap under maximum fan motor rotation demand Supposed Causes Operation halt due to short circuit inside the fan motor winding Operation halt due to breaking of wire inside the fan motor Operation halt due to breaking of the fan motor lead wires Operation halt due to faulty capacitor of the fan motor Detect...

Page 187: ...put of fan motor connector Is motor power voltage DC 200V generated Is motor control power voltage DC 15V generated Turn off power supply and disconnect fan motor connector then turn power ON again Does it rotate Stop fan motor Is rotation number command pulse generated Is rotation number command pulse generated Check No 01 Check output of fan motor connector Check No 01 Check output of fan motor ...

Page 188: ...an 120 ohms or below about 50 C more than 1 860 kohms Note The values vary slightly in some models Supposed Causes Faulty connector connection Faulty thermistor Faulty PCB Troubleshooting Check No 6 Refer to P 209 C4 Heat exchanger temperature thermistor C9 Room temperature thermistor Check the connector connection YES Correct the connection Replace the thermistor Replace the indoor unit PCB Repla...

Page 189: ... relay harness or disconnected connector Detection error due to defective PCB 2 Foreign substance in blow port Troubleshooting Check No 3 Refer to P 206 Turn off the power Check No 3 Check the limit switch continuity Remove such substance Replace the limit switch Reconnect the connector or replace the relay harness Replace the shutter drive motor or the PC board 2 Check the shutter s sealing mater...

Page 190: ...nal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units wire No 2 Troubleshooting Check No 10 Refer to P 212 Check the outdoor unit s LED A Check the indoor unit outdoor unit connection wires YES YES Correct the indoor unit outdoor unit connection wires Diagnose the outdoor unit Replace the connection wires between the indoor and outdoor units Re...

Page 191: ...models interconnected Wrong indoor unit PCB mounted Indoor unit PCB defective Wrong outdoor unit PCB mounted or defective Troubleshooting Check the indoor and outdoor unit model numbers Match the compatible models Change for the specified PC board 1 or 2 Replace the indoor unit PC board 1 or the outdoor unit PC board Q0347 Caution Be sure to turn off power switch before connect or disconnect conne...

Page 192: ...e following conditions A and B are kept together for 5 minutes A Indoor unit heat exchanger temperature 1 C B Indoor unit heat exchanger temperature Room temperature 10 C If the indoor unit icing protector is activated four times straight the system will be shut down The 4 time counter will reset itself if any of the following errors does not occur during the compressor running time total time OL ...

Page 193: ...hanger thermistor Do the vacuum drying Replace the indoor unit PCB and then start the wiring error check mode R3059 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Wiring or piping out of spec YES NO NO YES NO YES NO YES YES NO Error again Motor functioning Thermistor as specified in its characteristic chart Thermistor as specified in...

Page 194: ...t off valve defective Troubleshooting Check No 4 Refer to P 207 Check No 5 Refer to P 208 Check No 6 Refer to P 209 Check No 11 Refer to P 212 Insert the thermistor in position Replace the discharge pipe thermistor Replace the valve itself or the coil Replace the four way valve coil or the valve itself Replace the outdoor unit PCB Refer to the refrigerant line check procedure Replace the outdoor u...

Page 195: ...hut down if the error occurs 16 times Clearing condition Continuous run for about 5 minutes normal Supposed Causes Compressor locked Troubleshooting Turn off the power Disconnect the harnesses U V and W Inverter checker Part No 1225477 Correct the power supply or replace the SPM Replace the outdoor unit PCB Replace the compressor Check the electronic expansion valve Replace it as required Replace ...

Page 196: ...dition Continuous run for about 5 minutes normal Supposed Causes Fan motor breakdown Harness or connector disconnected between fan motor and PCB or in poor contact Foreign matters stuck in the fan Troubleshooting Check No 15 Refer to P 214 Turn off the power and reconnect the connector Remove Replace the outdoor unit fan motor Replace the outdoor unit PCB R2843 Caution Be sure to turn off power sw...

Page 197: ...on Conditions The following CT input with the compressor running continues for 2 5 seconds CT input Above 20 A The system will be shut down if the error occurs 16 times Clearing condition Continuous run for about 5 minutes normal Supposed Causes Over current due to compressor failure Over current due to defective power transistor Over current due to defective inverter main circuit electrolytic cap...

Page 198: ...above its stop level NO YES Normal NO YES Any LED off YES NO Check with the inverter checker Turn off the power and reconnect the harnesses Turn on the power again and get restarted Turn off the power and disconnect the harnesses U V and W Get restarted and measure the input current Check No 8 Check the discharge pressure Check No 7 Check the installation condition Check No 14 Check the main circu...

Page 199: ...thin their normal ranges in the operating mode Malfunction Decision Conditions Either of the following conditions occurs 3 minutes after the compressor has started Cooling dry operation Outdoor unit heat exchanger temperature Liquid pipe temperature 5 C Heating operation Liquid pipe temperature Outdoor unit heat exchanger temperature 5 C Supposed Causes Connector in poor contact Thermistor defecti...

Page 200: ...turn off power switch before connect or disconnect connector or parts damage may be occurred Four way valve coil disconnected loose YES YES NO Functioning NO Check No 11 Check the refrigerant line Malfunctioning z Water mixed z Shut off valve defective Harness out of connector NO YES Disconnect the harness from the connector Resistance between harnesses about 1500 ohms Malfunctioning Functioning C...

Page 201: ...set itself if this or any other error does not occur during the following 60 minute compressor running time total time Supposed Causes Refrigerant shortage Four way valve malfunctioning Discharge pipe thermistor defective heat exchanger or outdoor temperature thermistor defective Outdoor unit PCB defective Water mixed in the local piping Electronic expansion valve defective Stop valve defective Tr...

Page 202: ...ssor relay cable disconnected Compressor itself defective Outdoor unit PCB defective Stop valve closed Input voltage out of specification Troubleshooting Check No 13 Refer to P 213 Replace the outdoor unit PCB outdoor unit fan Replace the outdoor unit PCB Reconnect as specified Inverter checker Part No 1225477 Correct the power supply or replace the outdoor unit PCB Replace the compressor R2847 Ca...

Page 203: ...rrent Malfunction Decision Conditions The compressor running frequency is below 55 Hz and the CT input is below 0 1 V The input current is also below 1 25 A If this error repeats 4 times the system will be shut down The error counter will reset itself if this or any other error does not occur during the following 60 minute compressor running time total time Supposed Causes Power transistor defecti...

Page 204: ...itch before connect or disconnect connector or parts damage may be occurred Running current as shown at right with relay cable 1 or 2 YES Current guideline 2 sec Time Rising with increasing frequency Capacitor charged when the indoor unit or outdoor unit main relay turns on NO NO DC380 30V YES Voltage within the allowable range Supply voltage 15 YES NO Any LED off Compressor running YES NO YES NO ...

Page 205: ...istor Malfunction Decision Conditions When the thermistor input is above 4 96 V or below 0 04 V with the power on the J3 error is judged if the discharge pipe thermistor temperature is smaller than the condenser thermistor temperature or the system will be shut down if all the units are judged with the J8 error Supposed Causes Connector in poor contact Thermistor defective Outdoor unit PCB defecti...

Page 206: ...rature thermistor Replace the following thermistor z Indoor unit heat exchanger thermistor Replace the outdoor unit PC board Replace the indoor unit PC board Q0357 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Error displayed again on remote controller NO YES YES YES NO Indoor unit heat exchanger thermistor functioning NO Connector ...

Page 207: ...ecking the radiation fin thermistor with the compressor off Malfunction Decision Conditions With the compressor off the radiation fin temperature is above 80 C above 75 C in the case of 8 0 9 0kW class Reset is made when the temperature drops below 70 C Supposed Causes Fin temperature rise due to defective outdoor unit fan Fin temperature rise due to short circuit Fin thermistor defective Connecto...

Page 208: ...ution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Error again or outdoor unit fan activated YES z Fin thermistor NO Slightly dirty Check No 9 Check the outdoor unit fan or related Malfunctioning Radiation fin dirty Too dirty Functioning Thermistor as specified in its characteristic chart Above 80 C NO YES NO YES Check the radiation fin te...

Page 209: ...radiation fin temperature with the compressor on is above 90 C for 5 2 7 5 kW or smaller class systems or above 85 C for 8 0 9 0 kW class systems If a radiation fin temperature rise takes place 4 times successively the system will be shut down The error counter will reset itself if this or any other error does not occur during the following 60 minute compressor running time total time Supposed Cau...

Page 210: ...or the power transistor Replace the fan motor Correct the connectors and fan motor leads Replace the outdoor unit PCB Clean up the radiation fin R2851 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Error displayed again YES NO Slightly dirty Check No 9 Check the outdoor unit fan or related Malfunctioning Radiation fin dirty Too dirty...

Page 211: ...s while the compressor is running An output over current input is fed from the output over current detection circuit to the microcomputer The system will be shut down if the error occurs 16 times Clearing condition Continuous run for about 5 minutes normal Supposed Causes Over current due to defective power transistor Over current due to wrong internal wiring Over current due to abnormal supply vo...

Page 212: ...nected for part replacement for example and the system is interrupted by an output over current take the following procedure Error again NO YES NO YES Voltage as rated YES NO Short circuit or breakage between compressor s coil phases NO YES Normal YES NO Any LED off Turn off the power and turn it on again to get the system started See if the same error occurs Turn off the power and disconnect the ...

Page 213: ...as shortage detection I Input current 8 78 256 A Hz x Compressor running frequency 0 25 However when the status of running frequency 55 Hz is kept on for a certain time Note The values are different from model to model Gas shortage detection II If a gas shortage error takes place 4 times straight the system will be shut down The error counter will reset itself if this or any other error does not o...

Page 214: ... exchanger thermistor 1 Replace the PCB 2 Replace the compressor Procedure complete R2853 Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Any thermistor disconnected YES Malfunctioning Malfunctioning NO Functioning Stop valve closed NO YES Check the CT YES NO Gas shortage error again Functioning Check No 6 Check the thermistors YES NO...

Page 215: ... times Clearing condition Continuous run for about 60 minutes normal Supposed Causes Supply voltage not as specified Over voltage detector or DC voltage detection circuit defective PAM control part s defective Troubleshooting Check the supply voltage Correct the power supply Check for such factors for a long term Try to get restarted a couple of times Replace the SPM Replace the outdoor unit PCB R...

Page 216: ...tion halt due to unspecified internal and or external voltages Operation halt due to mismatching of indoor and outdoor units Supposed Causes Operation halt due to the anti icing function in other rooms Wrong connections at the indoor unit PCB wrongly connected Troubleshooting Check the model name The freeze protection function is activated in other rooms Refer to A5 Correct Reconnect R3066 Caution...

Page 217: ...the continuity of the switch connection The shutter can be opened and closed with hand Keep the shutter open and closed all the way for each continuity check steps 7 6 5 4 3 2 1 Motor power supply voltage Unused Unused P 0V reference potential Motor control voltage 15 VDC Rotation command voltage 1 5 VDC Rotation pulse input Upper fan connector 8 7 6 5 4 3 2 1 Motor power supply voltage Unused Unu...

Page 218: ...he no operation unit Flow noise of refrigerant in the no operation unit Operation halt due to icing protection Heating The unit does not heat Refrigerant flow rate vary by unit Discharge air temperatures are different by room Peak cut Reset power supply and conduct cooling operation unit by unit 2 Valve body catches at complete close position Symptom Cooling The only unit having problem does not c...

Page 219: ...nit PCB Replace the four way valve coil Replace the four way valve R2856 NO Four way valve coil Cooling dry No continuity Heating Continuity YES YES Four way valve coil resistance at 1500 ohms NO S80 voltage at DC 180 220 V with compressor on Fig 1 Disconnect the four way valve coil from the connector and check the continuity Fig 1 Voltage at S80 DC180 220V ON Compressor Time ...

Page 220: ...rs on the PCB and measure the resistance of each thermistor using tester The relationship between normal temperature and resistance is shown in the graph and the table below Thermistor R25 C 20kΩ B 3950 Temperature C 20 211 0 kΩ 15 150 10 116 5 5 88 0 67 2 5 51 9 10 40 15 31 8 20 25 25 20 30 16 35 13 40 10 6 45 8 7 50 7 2 ...

Page 221: ...ger Change the installation location or direction Check the outside air temperature temperature of air taken in by the outdoor unit The outside air temperature shall be 43 C or lower Check the allowable dimensions of the air suction and discharge area Is the air flow blocked by obstacles or winds blowing in the opposite direction R1438 Abnormal YES YES YES Does the discharged air from other outdoo...

Page 222: ...p valve Replace the pipe installed at the site Clean Replace the compressor R1443 YES YES YES NO NO NO NO At the heat exchanger and air filter dirty Is the stop valve open Is the connection pipe deformed YES High Check the outdoor unit fan system Reconnect R2857 Outdoor unit fan running YES Fan motor lead wire connector disconnected YES NO NO Outdoor unit fan system functioning Go to Check No 15 ...

Page 223: ...eform disturbance near the zero cross sections circled in Fig 2 6 1 10 Inverter Units Refrigerant System Check Check No 11 Fig 1 Fig 2 Refrigerant system check Check for gas leaks See the section on insufficient gas detection Conduct the check after operating the equipment for a sufficient length of time Correct the problem Conduct vacuum drying Replace the refrigerant Is the discharge thermister ...

Page 224: ...re the power transistor s supply voltage is below 50 V using the tester z For the UVW make measurements at the Faston terminal on the board or the relay connector Fan motor lead wire Solenoid valve coil lead wire Room A Solenoid valve coil lead wire Room B Solenoid valve coil lead wire Room C Solenoid valve lead wire Thermistor lead wire liquid pipe Thermistor lead wire gas pipe Thermistor lead wi...

Page 225: ...s being applied 1 Stop the operation first and then the power and disconnect the connector S70 2 Make sure there is about DC 270 V between pins 4 and 7 3 With the system and the power still off reconnect the connector S70 4 Make a turn of the fan motor with a hand and make sure the pulse 0 15 V appears twice at pins 1 and 4 If the fuse is blown out the outdoor unit fan may also be in trouble Check...

Page 226: ...nnected check the following Output voltage of about 5 V between pins 1 and 3 Generation of 3 pulses between pins 2 and 3 when the fan motor is operating Failure of 1 Æ faulty PCB Æ Replace the PCB Failure of 2 Æ faulty hall IC Æ Replace the fan motor Both 1 and 2 result Æ Replace the PCB The connector has 3 pins and there are two patterns of lead wire colors ...

Page 227: ...Check Si12 411A 216 Service Diagnosis ...

Page 228: ... 235 1 8 Removal of Shunt 237 1 9 Removal of Solenoid Valve and Four Way Valve 238 1 10 Removal of Compressor 240 2 Outdoor Unit 50 52 58 68 75 Class 242 2 1 Removal of Outer Panels 242 2 2 Removal of Electrical BOX 243 2 3 Removal of PCB 247 2 4 Removal of Fan Motor 250 2 5 Removal of Sound Insulation 251 2 6 Removal of Four Way Valve Coil Solenoid Valve Coil Electronic Expansion Valve Coil and T...

Page 229: ...90 Class 1 1 Removal of Outer Panels Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 External appearance Remove the piping in the backward direction 2 Remove 11 screws of the top panel ...

Page 230: ...19 3 Unscrew 3 screws of the right panel slide it downwards and release the tabs to remove 4 The figure shows the view of piping connections 5 Unscrew 1 screw of the front right panel slide it downwards and release the tabs to remove Step Procedure Points ...

Page 231: ...ss Si12 411A 220 Removal Procedure 6 Unscrew 3 screws of the front panel to remove 7 Remove 4 screws of the discharge outlet grill 8 Slide the discharge outlet grill upwards and release 6 tabs to remove Step Procedure Points ...

Page 232: ...after turning off all power supplies before disassembling work Step Procedure Points Remove the discharge outlet grill 1 To take off propeller fan remove the washer fitted nut M8 2 Remove the propeller fan For reassembling align mark of propeller fan with D cut section of motor shaft Mount the propeller fan while positioning mark to the top ...

Page 233: ...such as top and front panels Match the colors of the tie wires to A B C and D ports as follows 1 Black Power 2 White Power 3 Red Transmission Wires are fixed to the terminal board with screws 1 The figure shows the right side view 1 Remove the tie wire 1 Loosen the terminal board screws and remove the wires at A and B ports 2 Open the terminal board cover and remove the wires at C and D ports When...

Page 234: ...earth wire 4 Remove 1 screw of the terminal board 5 Release the tab on the top right of the terminal board 6 Pull out the terminal board and open it Glass tube fuse and varistor cannot be replaced individually because lead free soldering is provided Step Procedure Points ...

Page 235: ...sion valve lead wires When reconnecting make sure to match the wire to the correct connector 2 Remove the four way valve connector S80 3 Remove the connector S93 for liquid pipe thermistor Step Procedure Points Connector Electronic expansion valve No Harness length S20 White EVA 630 S21 Red EVB 730 S22 Blue EVC 825 S23 Yellow EVD 940 ...

Page 236: ...he connector S92 for gas pipe thermistor 5 Remove the connector S90 for thermistor Outdoor air thermistor Blue Discharge pipe thermistor Black Heat exchanger thermistor Gray 6 Remove the overload relay connector S40 7 Remove the reactor lead wire Step Procedure Points ...

Page 237: ...90 Class Si12 411A 226 Removal Procedure 8 Remove the relay connector for compressor 9 Remove the electrical box cover 10 Disconnect the fan motor connector 11 Remove the discharge pipe thermistor Step Procedure Points ...

Page 238: ...thermistor so that its end comes up to the end of the presser spring Be careful not to lose the presser spring for the discharge pipe thermistor 3 Removing the electrical box 1 Remove 2 screws of the electrical box 2 Turn the electrical box up side down halfway and disconnect the thermistor lead wire from the hook Step Procedure Points ...

Page 239: ...r Unit 80 90 Class Si12 411A 228 Removal Procedure 3 Remove the outdoor air thermistor lead wire from the groove 4 Remove each wire harness and dismount the electrical box by lifting it Step Procedure Points ...

Page 240: ...t 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Removing the controller PCB 1 Release the tab of the electrical box and open the terminal board 2 Disconnect each connector of the terminal board 3 Unscrew 1 screw and release two tabs to remove the PCB ...

Page 241: ...Outdoor Unit 80 90 Class Si12 411A 230 Removal Procedure 4 Lift the PCB at the terminal board side 5 Disconnect each wire harness connector linked to the inverter PCB Step Procedure Points ...

Page 242: ...ic expansion valve coil D port S31 To CN14 Pin 9 S32 To CN11 Pin 5 S33 To S34 Pin 10 S40 Overload relay S71 To S72 Pin 8 S80 Four way valve coil S90 Thermistor Outdoor air heat exchanger and discharge pipe S92 Gas pipe thermistor S93 Liquid pipe thermistor 2 Removing the service monitor PCB 1 Remove the service monitor PCB by releasing its tab 3 Removing the inverter PCB 1 Remove the 9 screws of t...

Page 243: ...ng off all power supplies before disassembling work Step Procedure Points Remove the outer panels 1 Remove the fan motor lead wire connector S70 2 Remove the propeller fans For reassembling align mark of propeller fan with D cut section of motor shaft Mount the fan motor so as to position Q mark on the top 3 Remove 2 screws of the fan motor mount ...

Page 244: ... 90 Class Removal Procedure 233 4 Remove 4 screws of the fan motor When reassembling fix the lead wire to avoid contact with the propeller fan 5 Cut the wrapper fixing the lead wire 6 Remove the fan motor Step Procedure Points ...

Page 245: ...the thermistor so that its end comes up to the end of the presser spring Be careful not to lose the presser spring for the discharge pipe thermistor 2 Take off the putty and remove each thermistor S90 Outdoor air thermistor Blue Heat exchanger thermistor Gray Discharge pipe thermistor Black S92 Gas pipe thermistor Room A Black Room B Gray Room C Brown Room D Red S93 Liquid pipe thermistor Room A B...

Page 246: ...pplies before disassembling work Step Procedure Points 1 Release the clip fixing the compressor lead wire 2 Remove 2 screws of the partition board and move the board leftward The partition board is not removable as it is fixed with the fitting screw in the rear bottom 3 Remove the noise insulation outer Carefully remove the noise insulation which is easily torn in the piping section ...

Page 247: ...411A 236 Removal Procedure 4 Remove the noise insulation top Carefully remove the noise insulation which is easily torn in the piping section 5 Remove the noise insulation inner 6 Remove 1 screw of the reactor Step Procedure Points ...

Page 248: ...sten the rubber packing with double faced adhesive tape when mounting 3 Remove the putty Caution Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas welding rod Warning If refrigerant gas leaks during the job ventilate the room Bear in mind that if the refrigerant gas is exposed to open flames noxious gas may be generated Before taking this procedure make...

Page 249: ...enoid valve 1 Remove 1 screw of the solenoid valve coil Before taking this procedure make sure there is no refrigerant gas left in the refrigerant pipes 2 Disconnect the 2 brazed points a and b in this order Warning If refrigerant gas leaks during the job ventilate the room Bear in mind that if the refrigerant gas is exposed to open flames noxious gas may be generated 2 Removing the four way valve...

Page 250: ... the pipes be careful not to over tighten them with pliers The pipes may get deformed If the gas welding machine fails to remove the four way valve take the steps below 1 Disconnect the brazed pipe sections that are readily easy to separate and join together later 2 With a small copper tube cutter cut off the internal pipes to easily take out the four way valve Note Never use a hack saw The sawdus...

Page 251: ... off all power supplies before disassembling work Step Procedure Points 1 Remove the terminal cover Be careful to avoid burning the compressor terminals or the nameplate 2 Remove the overload relay 3 Disconnect the flag shape terminal As precaution keep the contents in memorandum 4 There is one nut fixing the compressor Remove the nut with a spanner ...

Page 252: ...ks during the job ventilate the room Bear in mind that if the refrigerant gas is exposed to open flames noxious gas may be generated Caution Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas welding rod When heating up the brazed parts make sure to carry out the N2 replacement 5 Remove the 2 sheets of putty 6 Disconnect the brazed part a at discharge si...

Page 253: ...er Panels Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 External appearance 2 Remove 4 screws of the top panel and 6 screws of the front panel 3 Remove 4 screws of the discharge outlet grill 4 Remove 2 screws of the piping cover ...

Page 254: ...mbling work Step Procedure Points 1 Removing the tie wires Remove the piping in the backward direction 1 The figure shows the tie pipe connections 2 Remove the terminal board fitting screw Match the colours of the tie wires to A B C and D ports as follows 1 Black Power 2 White Power 3 Red Transmission Wires are fixed to the terminal board with screws Terminal board is made of integral moulded resi...

Page 255: ...o the correct connector 1 Disconnect 4 connectors of the electronic expansion valve lead wires 2 Remove the four way valve connector S80 3 Disconnect the thermistor connector and the overload relay connector S40 Overload relay S90 Thermistor Outdoor air heat exchanger discharge pipe S92 Gas pipe thermistor S93 Liquid pipe thermistor Step Procedure Points Connector Electronic expansion valve No Har...

Page 256: ...l Procedure 245 4 Disconnect the compressor relay connector 5 Remove the reactor lead wire 3 Removing the wiring fixture 1 Remove 6 screws of the wiring fixture 4 Removing the electrical box 1 Remove 1 screw of the electrical box Step Procedure Points ...

Page 257: ... 58 68 75 Class Si12 411A 246 Removal Procedure 2 Remove 1 screw of the electrical box 3 Remove the drip proof cover 4 Disconnect the fan motor lead wire 5 Lift up the electrical box and dismount it Step Procedure Points ...

Page 258: ...r supplies before disassembling work Step Procedure Points 1 Removing the controller PCB 1 Remove 1 screw of the PCB and release two tabs 2 Release the tabs of the terminal board and open the terminal board 3 Disconnect each connector on the back of the terminal board 4 Disconnect the service monitor PCB connector Release the tab to remove the service monitor PCB ...

Page 259: ...75 Class Si12 411A 248 Removal Procedure 5 Lift up the control PCB 6 Disconnect each wire harness connector linked to the control PCB S31 Pin 9 To CN14 S32 Pin 5 To CN11 S33 Pin 10 To S34 S71 Pin 8 To S72 Step Procedure Points ...

Page 260: ...Removal Procedure 249 7 The figure shows the control PCB Glass tube fuse 3A 2 Removing the service monitor PCB 1 The figure shows the service monitor PCB 3 Removing the inverter PCB 1 Remove the 7 screws of the inverter PCB Step Procedure Points ...

Page 261: ...d wire connector For reassembling align mark of propeller fan with D cut section of motor shaft Mount the propeller fan while positioning Q mark to the top 1 Remove the propeller fan by removing the washer fitted nut 2 Remove the fan motor Remove 1 screw of the fan motor mount When reassembling fix the lead wire to avoid contact with the propeller fan 3 Disconnect the lead wire by releasing the 2 ...

Page 262: ...ion Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1 Remove 5 screws of the right side panel 2 Remove 2 screws of the partition board and remove the board 3 Remove the noise insulation top outer and inner ...

Page 263: ...ower supplies before disassembling work Step Procedure Points 1 Remove 1 screw of the four way valve coil 2 Remove one screw of the solenoid valve coil 3 Remove the electronic expansion valve coil for each room Place the thermistor so that its end comes up to the end of the presser spring 4 Release the thermistor presser spring and remove the discharge pipe thermistor Be careful not to lose the pr...

Page 264: ...esser spring Be careful not to lose the presser spring for the discharge pipe thermistor 6 Remove the wire harness S90 Outdoor air thermistor Blue Heat exchanger thermistor Gray Discharge pipe thermistor Black S92 Gas pipe thermistor Room A Black Room B Gray Room C Brown Room D Red S93 Liquid pipe thermistor Room A Black Room B Gray Room C Yellow Room D Blue Step Procedure Points ...

Page 265: ... C In pulling the pipes be careful not to over tighten them with pliers The pipes may get deformed If the gas welding machine fails to remove the four way valve take the steps below 1 Disconnect the brazed pipe sections that are readily easy to separate and join together later 2 With a small copper tube cutter cut off the internal pipes to easily take out the four way valve Note Never use a hack s...

Page 266: ...reful not to get yourself burnt with the pipes and other parts that are heated by the gas welding rod Warning If refrigerant gas leaks during the job ventilate the room Bear in mind that if the refrigerant gas is exposed to open flames noxious gas may be generated Reassembling precautions Wrap the solenoid valve body with wet cloth Splash water over the cloth before it is dried to prevent the valv...

Page 267: ...end spanner Make sure there is no refrigerant gas left inside the refrigerant pipes before starting the job When heating up the brazed parts make sure to carry out the N2 replacement Warning The compressor s refrigerating machine oil may catch fire Have wet cloth at hand for quickly putting out the fire Warning If refrigerant gas leaks during the job ventilate the room Bear in mind that if the ref...

Page 268: ...Si12 411A Others 257 Part 8 Others 1 Others 258 1 1 Test Run from the Remote Controller 258 1 2 Jumper Settings 259 ...

Page 269: ...w Trial operation from Remote Controller 1 Press ON OFF button to turn on the system 2 Simultaneously press center of TEMP button and MODE buttons 3 Press MODE button twice T will appear on the display to indicate that Trial Operation mode is selected 4 Trial run mode terminates in approx 30 minutes and switches into normal mode To quit a trial operation press ON OFF button After trial operation i...

Page 270: ... box Cut the jumper JA on PCB Wireless remote controller in case of wall mounted type Cut the jumper J4 1 2 2 Jumper Setting Wireless remote controller Address J4 CUT EXIST 1 2 JA ADDRESS J4 ADDRESS CUT EXIST 1 2 JA JB JC Metallic cover Sensor parts cover PCB Electric parts box Claws 4 points R2587 Jumper On indoor PCB Function When connected factory set When cut JC Power failure recovery function...

Page 271: ...of center Gently push and slide the sensor to adjust the angle Aim so that the sensor is pointing to the center of the room or to the part of the room that is most frequently used After adjusting the angle gently wipe the sensor with a clean cloth being careful not to scratch the sensor Caution Do not hit or violently push the Intelligent eye sensor This can lead to damage and malfunction Do not p...

Page 272: ...Si12 411A Appendix 261 Part 9 Appendix 1 Piping Diagrams 262 1 1 Indoor Units 262 1 2 Outdoor Units 266 2 Wiring Diagrams 273 2 1 Indoor Units 273 2 2 Outdoor Units 276 ...

Page 273: ...N HEAT EXCH INDOOR UNIT M 6 4CuT 7 0CuT 9 5CuT HEAT EXCHANGER REFRIGERANT FLOW HEATING COOLING 6 4CuT 6 4CuT 4D032969C M 4D033698D FIELD PIPING FIELD PIPING 6 4CuT 9 5CuT 7 9CuT REFRIGERANT FLOW FAN MOTOR ON HEAT EXCH THERMISTOR INDOOR UNIT HEATING COOLING 7 0CuT 6 4CuT 9 5CuT HEAT EXCHANGER 6 4CuT 6 4CuT CROSS FLOW FAN FIELD PIPING FIELD PIPING 12 7CuT 6 4CuT CROSS FLOW FAN FAN MOTOR 7 9CuT INDOO...

Page 274: ...agrams Appendix 263 FTKD71BVM FTK X D71BVMA 15 9CuT FIELD PIPING FIELD PIPING 9 5CuT CROSS FLOW FAN FAN MOTOR 7 9CuT INDOOR UNIT 12 7CuT M HEAT EXCHANGER REFRIGERANT FLOW ON HEAT EXCH THERMISTOR COOLING HEATING 4D040083F ...

Page 275: ... HEAT EXCH CuT 4D045450 FIELD PIPING FIELD PIPING CuT 6 4CuT INDOOR UNIT SIROCCO FAN 6 4CuT CuT FAN MOTOR M REFRIGERANT FLOW HEAT EXCHANGER COOLING HEATING THERMISTOR ON HEAT EXCH CDKS35CVMB CDXS25CVMA CDXS35CVMA FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS35CVMB CDKS25CVMB CDXS25CVMB CDKS60CVMB CDXS50CVMA CDXS60CVMA CDXS60CVMB CDKS50CVMB CDXS50CVMB 12 7 9 5 4D045449B FIELD PIPING FIELD PIPING...

Page 276: ...DOOR UNIT 7 9CuT CROSS FLOW FAN CROSS FLOW FAN COOLING HEATING FAN MOTOR FAN MOTOR 9 5CuT M M HEAT EXCHANGER 7 0CuT 7 0CuT ON HEAT EXCH THERMISTOR 4D034714B FIELD PIPING FIELD PIPING 12 7CuT 6 4CuT REFRIGERANT FLOW INDOOR UNIT 9 5CuT MUFFLER MUFFLER CROSS FLOW FAN CROSS FLOW FAN HEATING COOLING FAN MOTOR FAN MOTOR 9 5CuT M M 4 8CuT 4 8CuT 7 0CuT HEAT EXCHANGER 7 0CuT 7 0CuT 7 0CuT ON HEAT EXCH THE...

Page 277: ...CuT 12 7 CuT 12 7 CuT 3D036222B ROOM B ROOM A ROOM B ROOM A GAS FIELD FIELD PIPING PIPING LIQUID REFRIGERANT FLOW 9 5CuT HEAT EXCHANGER THERMISTOR DE OUTDOOR UNIT COOLING 7 9CuT PROPELLER FAN DC FAN MOTOR HEAT EXCHANGER DISCHARGE PIPE THERMISTOR DO COMPRESSOR M OUTDOOR TEMPERATURE THERMISTOR DOA CAPILLARY TUBE ACCUMULATOR 12 7CuT DISTRIBUTOR ACCUMULATOR 9 5CuT 12 7CuT FILTER STOP VALVE LIQUID LINE...

Page 278: ... A ROOM B ROOM C ROOM B ROOM C ROOM A 3D036220B GAS FIELD FIELD PIPING LIQUID PIPING REFRIGERANT FLOW 9 5CuT HEAT EXCHANGER THERMISTOR DE OUTDOOR UNIT COOLING 7 9CuT PROPELLER FAN DC FAN MOTOR HEAT EXCHANGER DISCHARGE PIPE THERMISTOR DO COMPRESSOR M OUTDOOR TEMPERATURE THERMISTOR DOA CAPILLARY TUBE ACCUMULATOR 12 7CuT DISTRIBUTOR ACCUMULATOR 9 5CuT 12 7CuT FILTER STOP VALVE LIQUID LINE STOP VALVE ...

Page 279: ...R FILTER FILTER FILTER 6 4CuT 6 4CuT 9 5CuT 9 5CuT 12 7CuT 15 9CuT 15 9CuT 15 9CuT ROOM A ROOM B ROOM C ROOM D ROOM A ROOM C ROOM B ROOM D PIPING FIELD FIELD GAS LIQUID PIPING OUTDOOR UNIT 3D036504B REFRIGERANT FLOW 9 5CuT HEAT EXCHANGER THERMISTOR DE OUTDOOR UNIT COOLING 7 9CuT PROPELLER FAN DC FAN MOTOR HEAT EXCHANGER DISCHARGE PIPE THERMISTOR DO COMPRESSOR M OUTDOOR TEMPERATURE THERMISTOR DOA C...

Page 280: ...CuT 6 4 CuT 12 7 CuT 12 7 CuT ROOM D ROOM C ROOM B ROOM A ROOM D ROOM C ROOM B ROOM A 3D034514C GAS FIELD FIELD PIPING PIPING LIQUID REFRIGERANT FLOW 9 5CuT HEAT EXCHANGER THERMISTOR DE OUTDOOR UNIT COOLING 7 9CuT PROPELLER FAN DC FAN MOTOR HEAT EXCHANGER DISCHARGE PIPE THERMISTOR DO COMPRESSOR M OUTDOOR TEMPARATURE THERMISTOR DOA CAPILLARY TUBE ACCUMULATOR 12 7CuT DISTRIBUTOR ACCUMULATOR 9 5CuT 1...

Page 281: ...S LINE STOP VALVE 9 5CuT 12 7CuT HEADER HEADER FILTER MOTOR OPERATED VALVE MOTOR OPERATED VALVE 7 9CuT 7 9CuT 7 9CuT 7 9CuT MOTOR OPERATED VALVE MOTOR OPERATED VALVE 12 7CuT 12 7CuT 12 7CuT 12 7CuT EVA EVB EVC EVD GAS PIPE THERMISTOR DGA GAS PIPE THERMISTOR DGB GAS PIPE THERMISTOR DGC GAS PIPE THERMISTOR DGD LIQUID PIPE THERMISTOR DLB LIQUID PIPE THERMISTOR DLD LIQUID PIPE THERMISTOR DLC LIQUID PI...

Page 282: ...R FILTER 9 5 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 12 7 CuT ROOM A ROOM B ROOM C ROOM A ROOM B ROOM C 3D034512D GAS FIELD FIELD PIPING LIQUID PIPING REFRIGERANT FLOW HEADER HEAT EXCHANGER THERMISTOR DE OUTDOOR UNIT COOLING HEATING 12 7CuT PROPELLER FAN DC FAN MOTOR HEAT EXCHANGER DISCHARGE PIPE THERMISTOR DO COMPRESSOR M REVERSING SOLENOID VALVE MUFFLER 7 9CuT OUTDOOR TEMPERATURE THERMISTOR DOA 12 7...

Page 283: ...OOM D 3D034511C GAS FIELD FIELD PIPING PIPING LIQUID REFRIGERANT FLOW HEADER 12 7CuT OUTDOOR UNIT HEAT EXCHANGER THERMISTOR DE COOLING HEATING 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT PROPELLER FAN DC FAN MOTOR DISCHARGE PIPE THERMISTOR DO COMPRESSOR HEAT EXCHANGER 12 7CuT MUFFLER M 7 9CuT 7 9CuT ACCUMULATOR 7 9CuT VALVE 4 WAY OUTDOOR TEMPERATURE THERMISTOR DOA CAPILLARY TUBE 12 7Cu...

Page 284: ...RED BLK YLW X1M 2 3 1 NOTE THAT OPERATION WILL THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK RESTART AUTOMATICALLY IF ON AGAIN CAUTION FIELD WIRING 2 3 1 outdoor 3D033599E 3D038065G CONTROLLER WIRELESS REMOTE PCB4 PCB3 PCB5 INTELLIGENT EYE LED1 H1P R1T SENSOR t S37 S38 LED2 H2P LED3 H3P PCB2 S27 S36 S1W RECEIVER SIGNAL S26 S35 S21 S29 S28 PCB1 R2T S32 t RECTIFIER 1 RED M1S M S6 ORG YLW PNK 5 B...

Page 285: ...ION SWITCH X1M 3 2 1 PROTECTIVE EARTH THE MAIN POWER SUPPLY IS ON AGAIN TURNED OFF AND THEN BACK NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF FIELD WIRING CAUTION 3 2 1 3D038530J OUTDOOR PCB2 RECEIVER SIGNAL LED H1P CONTROLLER REMOTE WIRELESS LED H2P S1W LED H3P 2RTH1 R1T t 10 1 S1 1 C1 BRN F1U S26 2 PCB1 S32 R2T t 1 10 BRN S21 1 FUSE CAPACITOR M1F PROTECTIVE EARTH TERMINAL FOR CENTRALIZED CO...

Page 286: ...AUTOMATICALLY IF ON AGAIN S1W OPERATION SWITCH SW7 S6 S37 X11A X21A CONNECTOR PCB1 PCB4 PRINTED CIRCUIT BOARD R1T R2T THERMISTOR X1M TERMINAL STRIP CAUTION FIELD WIRING 2 3 1 3D033909D outdoor CONTROLLER WIRELESS REMOTE indoor H1P S1W S2W 4 S4W M2S H2P M1S PCB4 PCB3 H3P RECEIVER SIGNAL M M L1S S24 S42 S26 S41 S23 S25 S6 PCB2 S31 R1T S21 TRANSMISSION S32 R2T CIRCUIT HA 3 15A FU S7 S302 S203 S201 S3...

Page 287: ...RN BLU BRN RED YLW 1 X11A 10 10 BLU 3D034318D S93 YLW BRN BLU RED 1 GRY S40 V 1 M1F M1C 3 M BLK M 4 W U Q1L BLK 9 N ROOM A ROOM B ROOM C TO INDOOR UNIT 3 3 3 2 2 2 POWER SUPPLY 1 1 1 FIELD WIRING 60Hz 220 230V 50Hz 220 240V V2 V5 MRC W MRB MRD S2 S102 E AC1 AC2 L2 HE HL HN Y1E Y3E R1T R12T H1P H5P Z1C Z3C MRM10 MRM20 X1M X4M H1 H2 L1 MID1 MID2 FU1 FU2 FU201 X3M X4M X2M X1M L 3 3 3 2 2 2 N 1 1 1 FU...

Page 288: ...S34 8 t YLW WHT RED ORG BRN BLU BLU RED BRN YLW 1 3D034848F X11A 10 10 BLU S93 YLW BRN BLU RED 1 GRY S40 V 1 M1F M1C 3 M BLK M 4 W U Q1L BLK 9 N N L TO INDOOR UNIT POWER SUPPLY ROOM A ROOM B ROOM C FIELD WIRING 3 3 3 2 2 2 1 1 1 60Hz 220 230V 50Hz 220 240V V2 V5 MRC W E AC1 AC2 L2 HE HL HN S2 S102 CN11 CN14 MRB MRD H1 H2 L1 Z1C Z3C X1M X4M Y1E Y3E R1T R12T H1P H5P MRM10 MRM20 MID1 MID2 FU1 FU2 FU2...

Page 289: ...ESSOR MOTOR SELECT SW SW2 DIODE BRIDGE WIRING ERROR CHECK SW SW3 NIGHT QUIET MODE SETTING SW SW5 PRINTED CIRCUIT BOARD PRIORITY ROOM SETTING SW SW4 BLU 12 S2 12 BLU S3W 1 1 RED S102 S101 BLK V5 S4W WHT 5 5 GRN MRM20 MRM10 FU2 3 15A MRB 1MRD MRC W S80 CT1 9 H2 H1 S91 1 WHT YLW BLU t YLW Y1E S20 R12T 1 M A ORG BLK Z2C BLU 3 BRN 6 RED 1 WHT DB1 1 BLK YLW Y2E S21 BLK M B ORG BLK BLU BLK RED PCB BLK BR...

Page 290: ...B X11A 10 t 10 R5T BLU GRY ROOM C S93 YLW t BRN BLU RED R6T 1 YLW GRY V S40 t 1 3 M1F M1C M M BLK 4 W U Q1L BLK 9 N ROOM A ROOM B ROOM C ROOM D TO INDOOR UNIT POWER SUPPLY 50Hz 220 240V 60Hz 220 230V 3 3 3 3 2 2 2 2 1 1 1 1 FIELD WIRING Z1C Z3C FERRITE CORE X1M X5M TERMINAL STRIP Y1E Y4E ELECTRONIC EXPANSION VALVE COIL V2 V5 VARISTOR FU1 FU2 FU201 FUSE HE HL HN E AC1 AC2 H1 H2 L1 L2 CONNECTOR MRM1...

Page 291: ...RRENT TRANSFORMER M1C COMPRESSOR MOTOR Q1L OVERLOAD PROTECTOR BLU BLU S1W H1P BLU BLU BLU 12 S2 12 BLU S3W 1 1 RED S102 S101 BLK V5 S4W WHT 5 5 GRN MRM20 MRM10 FU2 3 15A MRB 1 MRD Y1S BLU MRC W Y1R BLK S80 CT1 BLU 9 BLK H2 H1 S91 1 WHT YLW BLU t SPM SYSTEM POWER MODULE MID1 MID2 MOLDED INTER CONNECT DEVICE YLW Y1E S20 R12T 1 M A ORG BLK Z2C BLU 3 BRN 6 RED 1 WHT DB1 1 BLK YLW Y2E S21 BLK M B ORG B...

Page 292: ...k No 8 211 check No 9 211 compressor 240 256 compressor lock 184 compressor overload 183 compressor protection function 93 connection pipe condensation preventing function 107 control PCB 62 63 64 68 69 248 controller PCB 231 cooling heating mode lock 108 CT or related abnormality 192 D DC fan lock 185 defrost control 97 discharge pipe 100 discharge pipe control 94 discharge pipe temperature contr...

Page 293: ...202 insufficient gas control 103 INTELLIGENT EYE 79 INTELLIGENT EYE operation 141 INTELLIGENT EYE sensor 260 INTELLIGENT EYE sensor PCB 62 inverter PCB 231 249 inverter powerful operation 82 inverter units refrigerant system check 212 J J3 194 J4 259 J6 194 J8 194 J9 194 JA 58 61 63 64 66 259 JB 58 61 63 64 66 259 JC 58 61 63 64 66 259 jumper setting 259 L L3 196 L4 198 L5 200 LED A 58 61 63 64 66...

Page 294: ...31 244 253 S93 69 224 231 244 253 SC control 101 self diagnosis digital display 84 sensor malfunction detection 103 service check function 167 service monitor PCB 231 247 249 shunt 237 254 255 shutter drive motor shutter limit switch abnormality 178 signal receiver PCB 62 65 68 signal receiving sign 83 signal transmission error between indoor and outdoor units 179 solenoid valve 238 254 255 soleno...

Page 295: ...Si12 411A iv Index ...

Page 296: ...el 88 heat pump model 86 H Hall IC check 215 heating peak cut control 95 HOME LEAVE operation 81 I indoor unit PCB abnormality 171 input current control 94 input over current detection 186 installation condition check 210 insufficient gas 202 insufficient gas control 103 INTELLIGENT EYE 79 INTELLIGENT EYE sensor PCB 62 inverter features 73 inverter powerful operation 82 inverter units refrigerant ...

Page 297: ...177 thermistor or related abnormality outdoor unit 194 thermistor resistance check 209 troubleshooting with the LED indication 165 turning speed pulse input on the outdoor unit PCB check 214 U unspecified voltage between indoor and outdoor units 180 205 W wiring diagrams indoor units 273 outdoor units 276 wiring error check 105 ...

Page 298: ...Si12 411A Printed in Singapore 03 2005 AK COS ...