background image

1-20

SPECIAL PRECAUTIONS WHEN CHARGING UNIT WITH SCROLL COMPRESSORS

These precautions are intended for use with Scroll compressors only with R22 and R407C refrigerants but are not applied to 
others competitive Scroll compressors. 
Scroll compressors have a very high volumetric efficiency and quickly pump a deep vacuum if there is insufficient refrigerant 
in the system or if refrigerant is added too slowly. Operation with low suction pressure will quickly lead to very high discharge 
temperatures. While this process is happening, the scrolls are not being well lubricated – scrolls depend on the oil mist in the 
refrigerant for lubrication. A lack of lubrication leads to high friction between the scroll flanks and tips and generates additional 
heat. The combination of heat of compression and heat from increased friction is concentrated in a small localized discharge 
area where temperatures can quickly rise to more than 300°C. These extreme temperatures damage the Scroll spirals and the 
orbiting Scroll bearing. This damage can occur in less than one minute especially on larger compressors. Failure may occur 
in the first few hours or the damage done during field charging may show up some time later. Other typical field charging 
problems include undercharging, overcharging, moisture or air in the system etc. In time each one of these problems can 
cause compressor failure.
Minimal equipment is required for field charging. The minimum equipment required to do a satisfactory job is:-

ADDITIONAL CHARGE

The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming 
is not necessary. When the piping length is more than 7.5m, use the table below.

R22

R407C

Liquid pipe OD

Additional charge kg/m

Additional charge kg/m

3/8"

0.06

0.05

1/2"

0.10

0.10

5/8"

0.16

0.15

3/4"

0.25

0.23

Set of service gauges
Hoses
Vacuum pump

1.
2.
3.

Vacuum gauge
Scales
Thermometer

4.
5.
6.

The proper refrigerant charge should follow the volume as recommended by manufacturer and recommendation should be 
followed by the installer.

Charging procedures – Single phase compressors

 Evacuate the system to -760mmHg. To reduce evacuation time, use short, large diameter hoses and connect to unrestricted 
service ports on the system. Quality of vacuum cannot be determined by time – a reliable vacuum gauge must be used. 
(etc. electronic vacuum gauge)
 Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line charging port 
until refrigerant no longer flows or until the correct charge has been weighed in. If additional charge is required start the 
system and slowly bleed liquid into the suction side until the system is full.
 

It recommends charging liquid in a CONTROLLED manner into the suction side until the system is full

This recommendation does not hold true for reciprocating compressors where liquid charging into the suction side could 
cause severe damage.
 Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not fall below 25 psig 
(1.7 bar) at any time during the charging process.

1.

NOTE

The additional refrigerant charge amount recommended is a guideline for long piping application.
The actual charge required may be different from the guideline due to different application and variation in site conditions.

1-IM-CC&SB-D_ER-0412(0)-DAIKIN-E20   20

1-IM-CC&SB-D_ER-0412(0)-DAIKIN-E20   20

7/19/12   2:34:28 PM

7/19/12   2:34:28 PM

Summary of Contents for 2FD150DXY1

Page 1: ...YP150EXY1 RCYP150E G XY1 2FDYP150EXY1 RCYP75E G XY1 x 2 2FDYP200EXY1 RCYP100E G XY1 x 2 2FGYP250EXY1 RCYP125E G XY1 x 2 2FGYP300EXY1 RCYP150E G XY1 x 2 3FGYP300EXY1 RCYP100E G XY1 x 3 3FGYP350EXY1 RCY...

Page 2: ......

Page 3: ...s are in mm Original Instruction Dimension Model A B C D E F G H I J K L 75D 1120 1264 336 699 336 1370 710 746 103 53 63 56 100D 1349 1493 331 940 328 1599 710 746 103 53 60 56 Dimension Model M N O...

Page 4: ...4 1654 590 1794 54 114 48 20 680 474 70 89 150D 150E 1805 2033 1933 730 2073 54 114 48 20 680 474 70 89 Dimension Model N O P Q R S T U V W X Y 125D 125E 408 213 25 1009 104 130 215 89 35 710 125 305...

Page 5: ...sion Model A B C D E F G H I J K L M 150D 150E 1805 2033 1933 730 474 20 48 680 54 114 2073 70 408 Dimension Model N O P Q R S T U V W X Y Z 150D 150E 89 213 25 1014 109 215 130 710 89 35 60 245 187 I...

Page 6: ...982 1011 300D 1226 1501 1461 1381 1129 1552 1405 482 841 982 1214 Dimension Model L M N O P Q R S T U V 200D 678 301 295 474 796 1324 60 22 130 150 25 250D 779 353 333 560 897 1486 60 22 130 150 25 3...

Page 7: ...1 1742 1596 816 1405 185 150 130 1462 60 500D 2047 2007 1927 2098 1952 1172 1760 185 150 130 1462 60 Dimension Model M N O P Q R S T U V W X 400D 1367 25 1090 695 384 1722 273 358 698 972 1175 22 500D...

Page 8: ...sions are in mm Dimension Model A B C D E F G H I J K L 200E 1624 1834 1794 1040 48 754 117 53 50 20 660 474 Dimension Model M N O P Q R S T U V W X 200E 257 408 220 885 35 130 850 60 193 103 747 1894...

Page 9: ...22 2122 560 731 542 407 286 50 55 48 400 450 500E 2234 2004 1271 1451 1556 2174 2274 694 740 758 407 286 50 55 48 Dimension Model P Q R S T U V W X Y Z ZA ZB 250 300E 20 1196 35 528 482 60 129 1069 13...

Page 10: ...74 20 48 1679 50 55 115 1978 60 Dimension Model O P Q R S T U V W X Y Z ZA ZB ZB 600E 1775 130 286 35 1758 38 90 129 1883 1905 939 736 100 850 NOTE FOR VERTICAL AIR DISCHARGE X S T V U E C G G B K L D...

Page 11: ...5 100 125 150D RCY P 75 100 125 150E Dimension Model A B C D E F G H I 75 100D 75 100E 571 396 350 981 946 1041 200 95 50 125D 150E 673 396 350 1083 946 1041 200 95 50 150D 150E 673 493 354 1083 1047...

Page 12: ...going into suction of the unit This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage fluctuates greatly Do not install the units at area like hot spring or...

Page 13: ...of fan coil unit is level in the two horizontal directions taking into account the gradient recommended for drainage flow as shown Check the gradient recommended for drainage flow as follow Provide c...

Page 14: ...lace where the unit will not be buried in snow A place where air outlet port is not exposed to strong wind A place where the air discharge and operating sound level will not annoy the neighbours The l...

Page 15: ...gfromthefaceoftheswaging block is determined by the flaring tool See Figure III Fix the pipe firmly on the swaging block Match the centers of both the flare die and the flaring punch and tighten flari...

Page 16: ...ck Outdoor Unit Terminal Block Power Supply Cable Power Supply Cable FD P 125 150D IMPORTANT These values are for information only they should be checked and selected to comply with the local and or n...

Page 17: ...2 Circuit multiply according to the number of outdoor units Model Indoor 2FD P 150D 2FD P 200D 2FG P 250D 2FG P 300D 4FG P 400D 4FG P 500D Outdoor RC P x 2 RC P 100D x 2 RC P 125D x 2 RC P 150D x 2 R...

Page 18: ...nductors A Indoor B Outdoor 1 2 5 2 5 5 1 4 4 5 Interconnection cable size mm Number of conductors 1 7 1 7 Recommended time delay fuse A A Indoor B Outdoor C Total 10 25 32 12 40 40 FDY P 125 150E R S...

Page 19: ...Y P 250E 2FGY P 300E 3FGY P 350E 4FGY P 400E 4FGY P 500E Outdoor RCY P 75E x 2 RCY P 100E x 2 RCY P 125E x 2 RCY P 150E x 2 RCY P 100E RCY P 125E x 2 RCY P 100E x 4 RCY P 125E x 4 Voltage range Indoor...

Page 20: ...oners This is to minimise the contamination of moisture and dirt in the refrigerant system Filter dryer must be of molecular sieve type For a heat pump system install a two way flow filter dryer along...

Page 21: ...imately 30 minutes The evacuation time varies with different vacuum pump capacity Confirm that the charging gauge needle has moved towards 760mmHg Caution If the gauge needle does not move to 760mmHg...

Page 22: ...ping length is less than 7 5m then additional charge after vacuuming is not necessary When the piping length is more than 7 5m use the table below R22 R407C Liquid pipe OD Additional charge kg m Addit...

Page 23: ...ich are very effective in preventing dangerously high discharge temperatures during charging The protection module will trip and lock the compressor out for 30 minutes It is not normally necessary to...

Page 24: ...the unit Check the 3 phase wiring R phase missing Switch off the unit Check the 3 phase wiring S T phase missing Switch off the unit Check the 3 phase wiring Overload High discharge temperature Check...

Page 25: ...ditioner unit is noted immediately switch off the power supply to the unit Check the following fault conditions and causes for some simple troubleshooting tips TROUBLESHOOTING Fault Causes Action The...

Page 26: ...MEMO...

Page 27: ......

Page 28: ...caso ci fossero conflitti nell interpretazione di questo manuale o delle sue stesse traduzioni in altre lingue la versione in lingua inglese prevale Il fabbricante mantiene il diritto di cambiare qual...

Reviews: