Model
Indoor
FD(P) 125D
FD(P) 150D
Outdoor
RC(P) 125D
RC(P) 150D
Voltage range**
Indoor
380-415V/3PH/50Hz+
!
Outdoor
Power supply cable size* /mm²
A) Indoor
B) Outdoor
C) Total
Number of conductors
A) Indoor
B) Outdoor
1
4
4
3
5
1
6
6
3
5
Interconnection cable size* / mm²
Number of conductors
1
4
1
4
Recommended time delay fuse* /A
A) Indoor
B) Outdoor
C) Total
6
40
40
6
50
50
2FD(P) 150/200/250/300D
4FD(P) 400/500D
N
R
S
T
N
R
S
T
COMP
N
L
COMP1
COMP2
N2
N1
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
Power Supply Cable
To Outdoor Unit 2
Circuit multiply according to the number of outdoor units.
Model
Indoor
2FD(P) 150D
2FD(P) 200D
2FG(P) 250D
2FG(P) 300D
4FG(P) 400D
4FG(P) 500D
Outdoor
RC(P) x 2
RC(P)
100D x 2
RC(P)
125D x 2
RC(P)
150D x 2
RC(P)
100D x 4
RC(P)
125D x 4
Voltage range**
Indoor
380-415V/3PH/50Hz+
!
Outdoor
Power supply cable size* /mm²
A) Indoor
B) Outdoor
C) Total
Number of conductors
A) Indoor
B) Outdoor
1
2.5
10
5
5
1
2.5
10
5
5
1
4
16
5
5
1
6
25
5
5
1.5
2.5
35
5
5
4
4
50
5
5
Interconnection cable size* / mm²
Number of conductors
1
1 x 2
1
1 x 2
1
1 x 2
1
1 x 2
1
1 x 4
1
1 x 4
Recommended time delay fuse* /A
A) Indoor
B) Outdoor
C) Total
6
25
50
12
32
63
16
40
80
20
50
100
20
32
150
40
40
175
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
!
1-IM-CC&SB-D_ER-0412(0)-DAIKIN-E15 15
1-IM-CC&SB-D_ER-0412(0)-DAIKIN-E15 15
7/19/12 2:34:27 PM
7/19/12 2:34:27 PM