Troubleshooting
Si10-417
94
Service Diagnosis
Trouble
shooting
Check No.6
Refer to
P.157
P4 :
Radiation fin thermistor
J3 :
Discharge pipe thermistor
J6 :
Outdoor heat exchanger thermistor
H9 :
Outdoor air thermistor
Turn on the power again.
(R2849)
Reconnect.
Reconnect.
Replace defective
one(s) of the following
thermistors.
l
Radiation fin
thermistor
l
Discharge pipe
temperature
thermistor
l
Outdoor unit heat
exchanger
temperature
thermistor
l
Outdoor air
thermistor
Replace the following
thermistor.
l
Indoor unit heat
exchanger
thermistor
Replace the outdoor
unit PCB. (Replace
the indoor unit PCB.)
Error
displayed again on remote
controller?
NO
YES
YES
YES
NO
Indoor unit
heat exchanger thermistor
functioning?
Connector
or thermistor
disconnected?
NO
NO
YES
Normal?
C
heck No.
6
Check the thermistor
resistance value.
C
heck No.
6
Check the indoor unit heat
exchanger thermistor
resistance value in the
heating mode.
Caution
Be sure to turn off power switch before connect or
disconnect connector, or parts damage may be occurred.
Si10-417.fm Page 94 Wednesday, September 22, 2004 6:38 PM