Troubleshooting
Si10-417
104
Service Diagnosis
(R2850)
Check No. 6
Check the thermistor
resistance value.
Replace the fin
thermistor.
Replace the outdoor
unit PCB.
l
Fin thermistor
Thermistor
as specified in its
characteristic
chart?
Above 90˚C?
YES
NO
NO
YES
Check the radiation fin
temperature.
A
B