![Daikin 2AMKS40BVMB Pocket Manual Download Page 84](http://html1.mh-extra.com/html/daikin/2amks40bvmb/2amks40bvmb_pocket-manual_501055084.webp)
Si10-417
Troubleshooting
Service Diagnosis
83
5.2.29 Position Sensor Abnormality
Remote
Controller
Display
H6
Method of
Malfunction
Detection
A compressor startup failure is detected by checking the
compressor running condition through the position
detection circuit.
Malfunction
Decision
Conditions
The compressor is not running in about 15 seconds
after the compressor run command signal is sent.
Clearing condition: Continuous run for about 5
minutes (normal)
The system will be shut down if the error occurs 8
times.
Supposed
Causes
Compressor relay cable disconnected
Compressor itself defective
Outdoor unit PCB defective
Stop valve closed
Input voltage out of specification
Si10-417.fm Page 83 Wednesday, September 22, 2004 6:38 PM