Troubleshooting
Si10-417
44
Service Diagnosis
5.2.7 Compressor Lock
Remote
Controller
Display
E6
Method of
Malfunction
Detection
A compressor lock is detected by checking the
compressor running condition through the position
detection circuit.
Malfunction
Decision
Conditions
The position detection circuit detects a compressor
frequency of below 10 Hz for 20 seconds or a
frequency of above 160 Hz.
40 seconds after the compressor has started, the
position detection circuit detects a compressor
frequency of above 180 Hz.
The system will be shut down if the error occurs 16
times.
Clearing condition: Continuous run for about 5
minutes (normal)
Supposed
Causes
Compressor locked
Trouble
shooting
Caution
Turn off the power. Disconnect
the harnesses U, V and W.
System shut
down after errors repeated
several times?
Normal?
Emergency stop
without compressor
running?
Check with the inverter
checker (
∗
).
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
∗
Inverter checker
Part No.: 1225477
Correct the power
supply or replace the
SPM.
(Replace the outdoor
unit PCB.)
Replace the
compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.