Integration

www.DaikinApplied.com 

IM 916-5 • MICROTECH COMMUNICATION MODULE

Configuring the BACnet 

Communication Module

The following section describes how to configure the BACnet 

IP communication module for BAS network integration. Follow 

these instructions to set addressing parameters for the BACnet 

communication module using the unit controller display menu.  

Configuration varies depending on the structure of your 

network and BACnet broadcasting requirements for IP subnets.

NOTE: 

Refer to MicroTech 4 Rebel Applied Unit Controller 

Operation Manual (OM 1303) or MicroTech III Applied 

Air Handling Unit Controller Operation Manual 

(OM 920) for default values and keypad operating 

instructions. Refer to the respective Unit Controller 

Integration Guide for all BACnet objects and other 

network communication information. Se

Reference 

Documents

 for literature descriptions and locations.

BACnet IP Addressing

There are three parameters that must be configured properly 

to establish communication between the unit controller and the 

BACnet IP network: BACnet IP Address, IP Subnet Mask, and 

IP Router Address. See your system integrator for additional 

information regarding BACnet IP addressing. 
The BACnet communication module is DHCP (Dynamic Host 

Configuration Protocol) enabled. See 

Appendix A: BACnet IP 

Networks

 for more information about IP network types.

To Configure the Module using the Unit 

Controller Display Menu:

1.  Navigate to the Enter Password screen if you have 

not already entered a password. If you have entered a 

password, skip to step 3. 

2. 

Enter Password: 6363.

3.  Continue to navigate to the BMS Communications\

BACnet IP Set-Up menu. 

NOTE: 

The IP Setup menu only appears if a BACnet 

communication module installed correctly. If the 

BACnet communication module is installed correctly 

and this menu still does not appear, cycle power to 

the unit controller and repeat the procedure from Step 

3 above. 

4.  Modify the parameters as necessary. See 

Table 3

 for 

details.

5. 

To modify the Given IP Address, Given IP Mask, or Given 

IP Gateway, follow steps a-c below:

a. 

Fully change all four octets of the desired field.

NOTE: 

After entering all four octets of the desired field, the 

cursor should blink in the open space to the right of 

the last character of the octet.

b.  Select Enter by pressing down on the circular knob 

on the unit controller keypad. 

Do not press the 

Back button until Enter has been selected.

c. 

From this screen, use the Back button to navigate 

to the BMS Communications\BACnet IP Set-Up 

menu and change “ApplyIPChgs” from No to Yes.

6. 

Check that the network cable is connected and navigate 

to the IP Setup menu to verify the Actual IP Address. The 

Actual IP Address displays 0.0.0.0 if the network cable 

is not attached. This procedure may take a minute while 

the BACnet communication module powers up.

Configurable Parameters

Table 3

 defines the network parameters of the BACnet 

communication module that must be set using the unit 

controller display menu in order to establish communication 

between the unit controller and the BAS. Change parameters 

as required for your network. 

NOTE: 

To save alteration of these parameters, select 

“ApplyIPChgs” under 

the BMS Communications\

BACnet IP Set-Up menu (see Step 5 from previous 

section).

Summary of Contents for 090016709

Page 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Page 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Page 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Page 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Page 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Page 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Page 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Page 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Page 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Page 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Page 11: ......

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: