background image

Product Information

www.DaikinApplied.com 

IM 916-5 • MICROTECH COMMUNICATION MODULE

Light Emitting Diodes (LEDs)

The BACnet communication module has a BSP LED and a 

BUS LED to indicate communication activity and status of the 

BACnet communication module. These indicators are visible 

when the communication module is connected to the unit 

controller and the unit is powered on.

BSP LED

The BSP LED indicates the communication status between the 

BACnet communication module and the unit controller. 

Table 1

 

describes the status of the BSP LED.

Table 1: BSP LED Activity

BSP LED Color

Meaning

Flashing between 

 

Red and Green

Board Support Package (BSP) upgrade in progress

Green

Communication is established between the 

communication module and the unit controller

Yellow

The communication module is capable of 

communicating to the unit controller. However, 

communication is not established

Red flashing with 2Hz Red flashing with 2Hz = Software error

1

Red

Hardware error

1

1

 In the event that this should occur, cycle power to the unit controller to 

attempt to clear the problem. Contact the Controls Customer Support Group at 

866-462-7829 for additional assistance if necessary.

BUS LED

The BUS LED indicates the communication status between the 

BACnet communication module and the BACnet IP network. 

Table 2

 describes the status of the BUS LED.

Table 2: BUS LED Activity

BUS LED Color Meaning

Green

The unit controller is capable of communicating to the 

network

Red

The unit controller is not capable of communicating to the 

network

Orange / Yellow

Communication module is initializing

BACnet Network Connector

An RJ45 connector connects the BACnet communication 

module to the IP Network.

Board-to-Board Connector

The board-to-board connector connects the unit controller to 

the BACnet communication module (

Figure 3

 and 

Figure 4

).

Figure 3: Board-to-Board Connector 

 

   

Figure 4: Communication Module and Knockout       

Knockout 

permanently 

removed

Slot in module 

must

 line up 

with baffle in the board-to-

board connector

Board-to-board connector

Summary of Contents for 090016709

Page 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Page 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Page 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Page 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Page 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Page 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Page 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Page 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Page 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Page 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Page 11: ......

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: