IM 916-5 • MICROTECH COMMUNICATION MODULE 6 

www.DaikinApplied.com

Installation

Installation

Installation and Mounting

The following section describes how to field install a new 

BACnet IP communication module or replace an existing 

module on the unit controller.

 CAUTION

Electrostatic  discharge  hazard .  Can  cause  equipment 

damage .

This equipment contains sensitive electronic components that may be 

damaged by electrostatic discharge from your hands.  Before you handle 

a communication module, you need to touch a grounded object, such as 

the metal enclosure, in order to discharge the electrostatic potential from 

your body.

 WARNING

Electric  shock  hazard .  Can  cause  personal  injury  or 

equipment damage

.

This equipment must be properly grounded. Only personnel knowledgeable 

in the operation of the equipment being controlled must perform connections 

and service to the unit controller.

Field Installation Kit 

The BACnet communication module field-installed kit ships 

with the following items:

•  The BACnet IP communication module 
• 

Board-to-board connector (

Figure 4)

Refer to the 

Parts 

section for replacement information. 

Installing a new Communication Module

Follow these steps to install a BACnet communication module 

on the unit controller.  The module can be connected directly to 

the unit controller itself or to an existing module, if present.

NOTE: 

There is a limit of three devices that can be attached 

to the left side of the unit controller. 

1. 

Set the “Control Mode = Off” from the main menu on the 

unit controller display menu. This must be done prior to 

installing a new communication module.

2.  Remove power from the unit controller.
3. 

Carefully remove the blue plastic knockout strip on 

the far left end of the unit controller itself (or additional 

module, if present). 

Figure 4

 shows the knockout strip 

after it has been removed from the unit controller. 

4.  To prevent damage to the unit controller, insert a small 

screwdriver or other tool to the tab on the bottom of the 

unit controller and pull the screwdriver away from the 

controller.

5. 

Carefully remove the blue plastic knockout on the far 

right side of the BACnet communication module.

6. 

Insert the board-to-board connector into the BACnet 

communication module. Note that it only fits one way and 

that the baffles must line up with corresponding slots in 

BACnet communication module and the unit controller 

(

Figure 3

 and 

Figure 5

).

7. 

Insert the other end of the board-to-board connector 

to the far left side of the unit controller or other 

communication module, if attached (

Figure 1

).

8. 

Insert a CAT 5 Ethernet cable into the communication 

module’s network connector  (

Figure 2 

shows the 

location of network connector).

9.  Power up the unit controller.

10.  The unit controller automatically resets itself 

approximately 30 seconds after it is powered up. This 

reset is necessary so that the BACnet communication 

module is synchronized with the unit controller.

Figure 5: Communication Module with Board-to-Board 

Connector Inserted 

Replacing a Communication Module

Follow these steps to remove and replace a BACnet 

communication module. Note that it may already be connected 

to either the unit controller or to an existing module.

1. 

Set the “Control Mode = Off” from the main menu on the 

unit controller display menu. This must be done prior to 

replacing a communication module.

2.  Remove power from the unit controller.
3.  Locate the BACnet communication module to the left of 

the unit controller (

Figure 1

).

4. 

Pull the network cable connector from the BACnet 

communication module.

5. 

Grasp the BACnet communication module and gently 

pull it from the unit controller (or from an adjacent 

module, if it is attached to one).

6.  Install the new BACnet communication module.
7. 

Insert a CAT 5 Ethernet cable into the communication 

module’s network connector (

Figure 2)

.

8.  Apply power to the unit controller.

NOTE: 

The unit controller automatically resets itself 

approximately 30 seconds after power has been 

applied to it. This reset is necessary so that the 

BACnet communication module can synchronize with 

the unit controller.

Integration

Summary of Contents for 090016709

Page 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Page 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Page 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Page 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Page 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Page 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Page 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Page 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Page 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Page 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Page 11: ......

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...