IM 916-5 • MICROTECH COMMUNICATION MODULE

Service Information

Troubleshooting

Follow these procedures if you can control the unit controller 

from the display menu, but unable to communicate from the 

network.

Network Parameters

→  

Verify that network parameters are set correctly as 

shown in 

Table 3

→  

Make sure there are no duplicate devices on the 

network (Device Name and Device ID, for example).

→  

Check the use of the character # at the end of each 

IP setting. There should not be a “space” at the end.

→  

Be aware that the unit controller must be restarted 

when a “Reset Required” message appears. Power 

off/on the unit controller after all settings have been 

configured and then select Apply Changes from the unit 

conroller display menu. 

Network wiring

→  

Check for loose connections and that devices are 

plugged in properly.

→  

Confirm that the link light for each device’s connector 

is on, which indicates that information is capable of being 

sent and received.

Compatibility

→  

Verify the unit controller software application version 

and communication module BSP version. 

Network Communications

→  

Confirm that the DHCP parameter is set to “Off” 

when a static IP address is being used for non-DHCP 

networks.

→  

Check that the defined UDP port, e.g. BAC0, is open 

in the firewall.

→  

Verify if BBMDs are required.  BBMD must be used 

if the BACnet client and BACnet server are located on 

different subnets.  Use the command “tracert” to check 

this. Tracert shows all stations used to forward the 

signal to another segment. See 

Figure 6 

for the result 

of a BBMD network as displayed by using the “tracert” 

command.

 

Figure 6: 

Example of Confirmed BBMD Network

Contact the 

Parts

Table 4: Replacement Parts List

Description

Part Number

MicroTech III Applied Rooftop/MicroTech 4 Rebel Applied 

BACnet IP Communication Module Kit. Kit includes 

communication module, board-to-board connector, and 

Installation Manual

090016709

Technical Support

Contact the Daikin Applied Controls Customer Support Group 

at 866-462-7829 for additional assistance, if necessary.
Refer to the appropriate Unit Controller Operation Manual for 

additional information about using the unit controller display 

menu options for setting unit parameters and modifying 

unit setpoints. Also refer to the respective Unit Controller 

Integration Guide for all BACnet objects and other network 

communication information. See 

Reference Documents 

for 

literature descriptions and locations.

Summary of Contents for 090016709

Page 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Page 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Page 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Page 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Page 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Page 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Page 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Page 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Page 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Page 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Page 11: ......

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: