IM 916-5 • MICROTECH COMMUNICATION MODULE 8 

www.DaikinApplied.com

Integration

Table 3: Network Parameter Settings

Parameter

3

Range/Default

Description/Notes

Device Object Name

Up to 17 characters 

Default: Varies

This name must be unique throughout the entire BACnet network.  The last 6 characters of 

the default are the last 6 digits of the MAC Address, which is on a printed sticker affixed to the 

BACnet communication module.

Device Instance Number

0 - 4194302

 Default: 1579312

Device Instance of the BACnet communication module. This must be unique throughout the 

entire BACnet network.

Act IP

If DHCP set to On:

 

Address automatically assigned by 

network

If DHCP set to Off:

 

Address = Given IP

Actual IP Address of the BACnet communication module. This parameter is not changeable. 

Displays 0.0.0.0 if the network is not connected when power is applied to the unit controller.  If 

DHCP is set to On (enabled), the network automatically assigns this address.  If DHCP is set to 

Off (not enabled), the Actual IP Address is set equal to the Given IP Address (Gvn IP) provided 

the network is connected when Apply Changes is set to Yes.

Gvn IP

Default: 127.0.0.1

Given IP Address of the BACnet communication module. The BACnet IP address consists of the 

four-octet IP address followed by the two-octet UDP (User Datagram Protocol) port number. The 

IP address portion of the BACnet/IP address must be unique in the BACnet/IP network segment.

 

Set the four-octet IP Address to match the Static IP Address.

Gvn Msk

Default: 255.255.255.0

Given Subnet Mask of the BACnet communication module. Set the Given Subnet Mask to match 

the Static Subnet Mask Address.

Gvn Gwy

Default: 127.0.0.1

Given Gateway Address of the BACnet communication module. Set the Given Gateway Address 

to match the Static Gateway Address.

Act Msk

If DHCP set to On:

 

Address automatically assigned by 

network

If DHCP set to Off:

 

Address = Given Subnet Mask

Actual Subnet Mask of the BACnet communication module. 

Displays 0.0.0.0 if the network is not connected when power is applied to the unit controller. If 

DHCP is set to On (enabled), the network automatically assigns this address.  If DHCP is set 

to Off (not enabled), the Actual Subnet Mask is set equal to the Given Subnet Mask (Gvn Msk) 

provided the network is connected when Apply Changes is set to Yes.

Act Gwy

If DHCP set to On:

 

Address automatically assigned by 

network

If DHCP set to Off:

 

Address = Given Gateway Address

Actual Gateway Address. Item remains blank if the network is not connected when power 

is applied to the unit controller. If DHCP is set to On, the network automatically assigns this 

address. If DHCP is set to Off, the Actual Gateway Address is set equal to the Given Gateway 

Address (Gvn Gwy) provided the network is connected when Apply Changes is set to Yes.

DHCP

2

Off or On

Default: On

Dynamic Host Configuration Protocol (DHCP) is a network protocol that enables a server to 

automatically assign an IP Address. Set to Off if a static IP Address is needed. See 

Appendix A: 

BACnet IP Networks 

for more information.

UDP Port

Default: 47808 (BAC0 hex)

User Datagram Protocol. The UDP Port allows host-to-host communication via the IP network 

and is used to identify the application process in the destination unit.  Only change the UPD Port 

if there are multiple subnets. See network administrator before modification.

Unit Support

English or Metric 

Default: English

Controls the type of units that are passed through BACnet.

NC Dev 1

1

0-4194303 

Default: 0 (no device)

Alarm Recipient Device 1. This is the device instance of the BACnet workstation or device that 

will receive the alarm notification.  Use this in place of the Recipient List in the Notification Class.

NC Dev2

1

0-4194303 

Default: 0 (no device)

Alarm Recipient Device 2. This is the device instance of the BACnet workstation or device that 

will receive the alarm notification.  Use this in place of the Recipient List in the Notification Class.

BACnetBSP

Varies

Basic Support Package. Indicates the communication module firmware version. The BSP is 

read-only.

1. Parameter must be configured via the unit controller display menu.

2. The BACnet communication module defaults to DHCP-enabled.  See your system integrator for additional information regarding BACnet IP networks with DHCP 

functionality.

3. The parameters shown in boldface text are required for minimum network configuration.

NOTE: 

If the unit controller application software requires a 

field update, the network configuration parameters 

revert to their default values. Please contact the 

Applied Air Handling Customer Support Group at 

763-553-5330 for assistance with upgrading the unit 

controller application.

Summary of Contents for 090016709

Page 1: ...p Controls Part Number IM 916 Date August 2020 BACnet IP Communication Module for MicroTech III and MicroTech 4 Unit Controllers Applied Rooftop Systems and Self Contained Units Models DPS DPH MPS RAH RCE RCS RDE RDS RDT RFS RPE RPS SWP and SWT ...

Page 2: ...ght Emitting Diodes LEDs 5 BACnet Network Connector 5 Board to Board Connector 5 Installation 6 Installation and Mounting 6 Field Installation Kit 6 Installing a new Communication Module 6 Replacing a Communication Module 6 Integration 6 Configuring the BACnet Communication Module 7 BACnet IP Addressing 7 Configurable Parameters 7 Service Information 9 Troubleshooting 9 Parts 9 Technical Support 9...

Page 3: ...eath or serious injury if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes Revision History IM 916 Oct 2008 Initial release IM 916 1 May 2009 Modified Step 5 of To Configure the Module using the Keypad Display section Additional steps were added to describe how to properly set Given IP Address Given IP Mask or Given IP Ga...

Page 4: ...ature numbers and locations Specifications General Dimensions W x H x D 1 77 x 4 33 x 2 95 in 45 x 110 x 75 mm Weight 3 5 oz 98 g Material Base plastic pigeon blue Housing plastic light gray Operating Temperature 40 158 F 40 70 C Humidity 90 RH Atmospheric pressure Min 10 psi 70kPa corresponding to max 9 842 ft 3 000 m above sea level Storage and Transportation Temperature 40 158 F 40 70 C Humidit...

Page 5: ...flashing with 2Hz Software error1 Red Hardware error1 1 In the event that this should occur cycle power to the unit controller to attempt to clear the problem Contact the Controls Customer Support Group at 866 462 7829 for additional assistance if necessary BUS LED The BUS LED indicates the communication status between the BACnet communication module and the BACnet IP network Table 2 describes the...

Page 6: ...r tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller 5 Carefully remove the blue plastic knockout on the far right side of the BACnet communication module 6 Insert the board to board connector into the BACnet communication module Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet communication modu...

Page 7: ...ntered a password skip to step 3 2 Enter Password 6363 3 Continue to navigate to the BMS Communications BACnet IP Set Up menu NOTE The IP Setup menu only appears if a BACnet communication module installed correctly If the BACnet communication module is installed correctly and this menu still does not appear cycle power to the unit controller and repeat the procedure from Step 3 above 4 Modify the ...

Page 8: ...et Mask Gvn Msk provided the network is connected when Apply Changes is set to Yes Act Gwy If DHCP set to On Address automatically assigned by network If DHCP set to Off Address Given Gateway Address Actual Gateway Address Item remains blank if the network is not connected when power is applied to the unit controller If DHCP is set to On the network automatically assigns this address If DHCP is se...

Page 9: ...onfirm that the DHCP parameter is set to Off when a static IP address is being used for non DHCP networks Check that the defined UDP port e g BAC0 is open in the firewall Verify if BBMDs are required BBMD must be used if the BACnet client and BACnet server are located on different subnets Use the command tracert to check this Tracert shows all stations used to forward the signal to another segment...

Page 10: ...Identifier or their BACnet address The IP address is part of the BACnet address and may not be changed for the alarm recipient For this reason option Device Object Identifier must always be used Access rights If access rights are assigned based on IP address such as firewalls the address must be static Access rights are based off of the UDP Port Number ex UDP 47808 or the MAC Address of the BACnet...

Page 11: ......

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: