ED15117
61
Property Values
0 = Off (Inactive)
1 = Run Allowed (Active)
L
ON
W
ORKS
The L
ON
W
ORKS
equivalent of this data point is part of the Chiller Status network variable.
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerStat Chiller chlr_status 127
3
bytes
Property Values
(run_enabled)
0 = Off (Inactive)
1 = Run Allowed (Active)
Structure
typedef struct {
chiller_t chlr_run_mode;
hvac_t chlr_op_mode;
struct{
unsigned in_alarm :1;
// offset 0
unsigned run_enabled :1;
// offset 1
unsigned local :1;
// offset 2
unsigned limited :1;
// offset 3
unsigned chw_flow :1;
// offset 4
unsigned condw_flow :1;
// offset 5
/* The last two bits (offset 6) are not defined */
}
chlr_state;
} SNVT_chlr_status;
Software Identification (Major Version)
This property displays the major revision number for the chiller L
ON
W
ORKS
communication module
firmware.
Measurement
Units
Data Type
Usable Range
Default Value
Version Number
NA
Structure
0-255
1
L
ON
W
ORKS
LonWorks Name
Profile
SCPT Reference
SCPT Number
SCPT Size
nciDevMajVer
Node Object
SCPTdevMajVer
165
1 byte
Software Identification (Minor Version)
This configuration property displays the minor revision number for the chiller L
ON
W
ORKS
communication module firmware.
Measurement
Units
Data Type
Usable Range
Default Value
Version Number
NA
Structure
0-255
0
L
ON
W
ORKS
LonWorks Name
Profile
SCPT Reference
SCPT Number
SCPT Size
nciDevMinVer
Node Object
SCPTdevMinVer
166
1 byte
Units
This binary value allows you to select the units of measure that are being passed through BACnet.
Measurement
Units
Data Type
Usable Range
Default Value
Unit Type
NA
Unsigned Integer
See Below
1 = English
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Value
19
4
Present Value
85