Chiller Enable
This mandatory L
ON
W
ORKS
configuration variable sets the default power-up and restart mode of the
chiller, unless the configuration parameter nciDefaults = 1 (See Default Values). If nciDefaults = 1, the
default values are the values specified during manufacturing. Refer to the appropriate Operating
Manual for suitable variable values.
Measurement
Units
Data Type
Usable Range
Default Value
Chiller State
NA
structure
Enumerated
0 = Disable
L
ON
W
ORKS
L
ON
W
ORKS
Name Profile SNVT Type SNVT
Index
SNVT Size SCPT_Reference
SCPT_ Index
nciChillerEnable Chiller switch
95
two bytes SCPTpwrUpState 73
The chiller object uses the configuration value of nciChillerEnable on power-up or loss of
communication unless the configuration parameter nciDefaults =1 (See Default Values).
Valid Range
State
Value
Chiller Enable
0
unused
Request Chiller Off
1 unused Request Chiller Auto
(run)
-1 (0xff)
unused
Invalid
Chiller Enable Output
This read only network variable indicates if operation of the chiller is disabled or enabled. If the chiller
is disabled, it cannot run. If it is enabled, it is allowed to run.
Measurement
Units
Data Type
Usable Range
Default Value
Chiller State
NA
BACnet: Enumerated
L
ON
W
ORKS
: structure
See Below
0 = Disabled
BACnet
This read only
property indicates if operation of the chiller is disabled or enabled.
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
7
Present Value
85
Object Name
ChillerEnable
Property Values
0 = Disable (Inactive)
1 = Enable (Active)
LonWorks
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerEnable McQuayChiller
SNVT_switch
95
two
bytes
Valid Range
State
Value
Chiller Enable
0
unused
Request Chiller Off
1 unused
Request Chiller Auto
(run)
-1 (0xff)
unused
Invalid