24
ED 15117
Network Control Property
Page
Read,
Writ
e
1
Obje
ct
Type
Insta
n
ce
Description
77=Cmp1VFDHiPwrSupTemp
78=Cmp1VFDHiPwrSupVolt
79=Cmp1VFDClgFanFlt
80=Cmp1VFDProcessorFlt
81=Cmp1VFDMaintenanceMode
82=Cmp1SuctPressSenFlt
83=Cmp1DishPressSenFlt
84=Cmp1CondRfrCkt1PressSenFlt
85=Cmp1CondRfrCkt2PressSenFlt
86=Cmp1SuctTempSenFlt
87=Cmp1DischTempSenFlt
88=Cmp1MotorGapTempSenFlt
89=Cmp1RotorPmpTempSenFlt
90=Cmp1BearingOrbitSurgeFlt
91=Cmp1CommunicationsFlt
92=Cmp1EvapLvgWtrTempSenFlt
93=Cmp1CondLvgWtrTempSenFlt
94=Cmp1SoftwareFlt
95=Cmp1EvapWtrFlwLoss
96=Cmp1CondWtrFlwLoss
Alarm Problems
63 R AV 900
11=Cmp1LoEvapPressInhibitLoading
12=Cmp1EvapFreezeProtect
13=Cmp1CondFreezeProtect
14=Cmp1HiDischTemp
27=ChillerEvapPmp1Flt
28=ChillerEvapPmp2Flt
29=ChillerCondPmp1Flt
30=ChillerCondPmp2Flt
31=ChillerEvapEntWtrTempSenFlt
Alarm Warnings
63 R AV 902
1=Cmp1SoftwareProbWarn
5=ChillerEvapEntTempSenWarn
6=ChillerCondEntTempSenWarn
7=ChillerCondLvgTempSenWarn
8=ChillerLiqLn1RefTempSenWarn
9=ChillerLiqLn2RefTempSenWarn
10=ChillerSoftwareProbWarn
Clear Alarm Network
W
BV
8 0= Normal (Default), 1=Clear Alarm
*Boldface denotes data points for typical minimum integration.
1
This column refers to whether or not the Present Value property of the object is Read Only (R) or
read/write (W).