64
ED 15117
Alarm Faults
This BACnet object indicates the index number of fault alarms. If the present value is zero, no alarm
has occurred. See Table 8.
Measurement
Units
Data Type
Valid Range
Default Value
NA NA Integer
Enumerated
NA
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
2
901
Present Value
85
Object Name
AVFaultAlarm
Alarm Digital Output
The Alarm Digital Output method requires that one Binary Output object in the BACnet
Communication Module be polled for alarm notification. This object indicates whether an alarm
condition has occurred. The unit controller OITS panel displays the alarm text.
Measurement
Units
Data Type
Usable Range
Default Value
NA NA Integer
Enumerated
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Output
4
5
Present Value
85
Object Name
AlarmDigitalOutput
Property Values
0 = No Alarm
1 = Alarm