1. Features of product 

 

 

Complied to JIS C 1111:2019 and IEC 60688:2012 

 

Free power supply specifications compatible with 80 to 264 VAC and 80 to 264 VDC, and 24 VDC/48 VDC  
power supply specifications are available. 

 

Power consumption and weight have been reduced by about 50% compared to our conventional products. 

 

Compatible with two types of mounting methods for IEC/DIN rail mounting and wall mounting. 

 
 

2. Outline dimension 

 
    Please refer to the wiring diagram for the terminal arrangement. 

(12.5)

BIAS adjustment VR

(With VR cap)

MAX. adjustment VR

(With VR cap)

Terminal cover

92

110

120

56

28

5

130

M4screw

7

1

1

 

 
Note(

) Dimensions when IEC/DIN rail (height 15mm) is installed. (Please use a rail with a width of 35mm) 

The terminal cover is standard equipment. 

 
 

3. Bundled items 

 

① Inspection certificate:1 (Packed in an envelope) 

② Terminal screw in a bag.  SPTT2-92A-12  M4 screw 4-piece set:1, M4 screw 5-piece set:1 

SPTT2-92A-33  M4 screw 4-piece set:1, M4 screw 7-piece set:1 
SPTT2-92A-34  M4 screw 4-piece set:2, M4 screw 5-piece set:1 

 
 

4. Mounting method 

 

Please install indoors in a place with low mechanical vibration, dust, and corrosive gas. 
And, please select indoors that are not affected by a strong electromagnetic field by large current bus, 
saturable reactor etc. in the vicinity.  There is no restriction on mounting position.  
Mounting can be done on 35mm width DIN rail mounting or screw mounting.  
For screw mounting, please install with M4 screw or M5 screw. (However, the screw is not attached.   
The tightening torque of a screw, M4:1.00 to 1.30N・m, M5:2.0 to 2.5N・m) 
There is no particular rule for the side-by-side spacing. 
Considering heat dissipation and wiring space, please leave 90mm or more space between the top and bottom.  
Please leave space between terminal and metal panel for 10mm or more. 

<Caution> Be sure to turn off the power and input signals before installing or removing the product to  

prevent danger. 

Summary of Contents for SPTT2-92A-12

Page 1: ...Q 222 040 INSTRUCTION MANUAL POWER FACTOR TRANSDUCER SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 MODEL B...

Page 2: ...ase do not install in the place where sunlight hits directly Discoloration and degradation of a name plate and deformation of the case by the surface temperature rise may occur If the average daily te...

Page 3: ...our company Failure caused by violating various conditions regarding use storage etc specified by the supplier When the faults or defects are caused by a reason not belongs to purchased or delivered p...

Page 4: ...thod 4 5 Connection 6 6 Handling explanation 7 7 Specification 7 1 Rating 7 7 2 Performance 8 7 3 Electrical strength Mechanical strength 9 7 4 Noise immunity 9 7 5 EMC 10 7 6 Structure and environmen...

Page 5: ...92A 12 M4 screw 4 piece set 1 M4 screw 5 piece set 1 SPTT2 92A 33 M4 screw 4 piece set 1 M4 screw 7 piece set 1 SPTT2 92A 34 M4 screw 4 piece set 2 M4 screw 5 piece set 1 4 Mounting method Please inst...

Page 6: ...e this product from the IEC DIN rail Please insert a flathead screwdriver in the hole where a slider is square Next a slider is lowered in the direction of an arrow This product can be removed from th...

Page 7: ...tening torque 1 0 to 1 3 N m SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 Connection diagram SPTT2 92A 12 SPTT2 92A 33 SPTT2 92A 34 AUX SUPPLY L P1 K U 2 1 V 1S E A B OUTPUT P2 AUX SUPPLY P1 A B OUTPUT P2 A...

Page 8: ...power supply and voltage input are applied is the output equivalent to the power factor 1 7 Specification 7 1 Rating Item Specification Input Power factor LEAD 0 5 to 1 to LAG 0 5 Please specify LEAD...

Page 9: ...erter output Cycle control PWM inverter SCR phase angle control Adjustment range The output adjustment range is BIAS 5 of the output span MAX 5 of the output span Use only when adjustment is required...

Page 10: ...es 1 second of rated voltage 10 times 10 second intervals 40 times 1 second and 20 times 4 seconds and 10 times 16 seconds of rated current 2 times 1 minute intervals 10 times 1 second of rated curren...

Page 11: ...61000 4 6 Power frequency magnetic field immunity test Frequency 50 60Hz Field strength 30A m Performance standard A During testing Within 20 error After test Within inherent error EN61000 6 2 EN61000...

Page 12: ...its 10 to 55 5 to 90 RH Non condensing Storage temperature limits 40 to 70 Product warranty period One year period 7 7 Technical standards Item Specification Transducer JIS C 1111 2019 IEC 60688 2012...

Page 13: ...ust in the next way Remove the terminal cover and VR cap before adjustment and attach the VR cap and terminal cover after adjustment 1 For the output load connect an actual load within the output load...

Page 14: ...r less Z Other Power Factor Transducer Three phase four wire Type Specification code SPTT2 92A 34 Model Input Rated voltage Rated current Output Output load range Auxiliary supply B Model B 1 LEAD 0 5...

Reviews: