8. Input and output relationship
LAG/LEAD polarity
LEAD 0.5 to LAG 0.5
[V][mA]
0 0
OUTPUT
5 1
-5 -1
0 0.5 1 0.5 0 0.5 1 0.5 0
LAG LEAD LEAD LAG INPUT
Power
transmission
Power
receiving
[V][mA]
3 12
OUTPUT
5 20
1 4
0 0.5 1 0.5 0 0.5 1 0.5 0
LAG LEAD LEAD LAG INPUT
Power
transmission
Power
receiving
[V][mA]
2.5 0.5
OUTPUT
5 1
0 0
0 0.5 1 0.5 0 0.5 1 0.5 0
LAG LEAD LEAD LAG INPUT
Power
transmission
Power
receiving
LEAD 0 to LAG 0
0 1 0 1 0
LAG LEAD LEAD LAG INPUT
[V][mA]
0 0
OUTPUT
5 1
-5 -1
Power
transmission
Power
receiving
[V][mA]
3 12
OUTPUT
5 20
1 4
0 1 0 1 0
LAG LEAD LEAD LAG INPUT
Power
transmission
Power
receiving
[V][mA]
2.5 0.5
OUTPUT
5 1
0 0
0 1 0 1 0
LAG LEAD LEAD LAG INPUT
Power
transmission
Power
receiving
9. Calibration
Because this product is adjusted, there is not need of calibration especially.
However, if discrepancy arises in an output in long-term use, please adjust in the next way.
Remove the terminal cover and VR cap before adjustment, and attach the VR cap and terminal cover after adjustment.
(1) For the output load, connect an actual load (within the output load range indicated on the name plate)
or a simulated load with the same resistance value as the actual load.
(2) Apply the auxiliary power supply (rated) and the input equivalent to 50% of the rated output value,
and energize for 15 minutes.
(3) When the input of power factor 1 is applied, the BIAS adjustment VR is adjusted so that it becomes
the output value when the power factor 1.
Next, adjust the MAX. adjustment VR so that the rated output value is obtained when an input with a
power factor 0 or power factor 0.5 is applied.
(The screwdriver for adjustment:Tip width of 1.8 to 2.3mm, Phillips-head screwdriver or flat-blade
screwdriver)
0°
90°
180°
270°
LAG
LEAD
LEAD
LAG
Power receiving (Power purchase)
Power transmission (Power selling)
Polarity seen from the power receiving side even during
power transmission (P<0) (fixed V reference)
V
reference
Current of
leading phase
Current of
lagging phase